Sequence networks of Y load, neutral current
Short answer
For a balanced Y load with neutral impedance Zn, the positive and negative sequence networks each consist of the phase impedance Zs. The zero sequence network includes Zs plus 3Zn in series because neutral current equals 3Ia0. The neutral current In = Ia+Ib+Ic = 3Ia0, as positive and negative components cancel.
Deduce the sequence networks for balanced Y connected load with neutral grounded through impedance Zn and show also that current through neutral impedance is three times the zero sequence current.
For a balanced star load with neutral grounded through , the sequence networks are three separate circuits with impedances and , and the neutral carries .
Neutral current is three times zero sequence current
By the symmetrical component definitions:
Adding and using :
So only zero sequence currents flow through the neutral, and the neutral current is . Positive and negative sequence currents form balanced sets that cancel at the star point.
Circuit and phase equations
Ia --> Zs
a o-----/\/\---+
Ib --> Zs |
b o-----/\/\---+ n
Ic --> Zs |
c o-----/\/\---+
| In = Ia+Ib+Ic
Zn
|
ground
Voltage of each phase to ground = drop in + drop in :
In matrix form with
Transformation to sequence quantities
Put and :
with , .
Write , where is the unit matrix and is the matrix of all ones. Then . For : every row of is (since column sums of are ), and times that gives
Hence
Sequence networks
Positive Negative Zero
a1 --Ia1--> a2 --Ia2--> a0 --Ia0-->
| | |
Zs Zs Zs
| | |
n1 (ref) n2 (ref) 3Zn
|
n0 (ref)
- , , .
- The impedance appears as in the zero sequence network only because the voltage drop across it is , while the network is drawn for one phase carrying .
- Solidly grounded neutral: ; ungrounded neutral: zero sequence network open between and the reference.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Sequence impedances of star load with Zn · Power System Analysis II, chapter 4 · asked 2×
- Sequence impedance of load with mutual coupling · Power System Analysis II, chapter 4
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Sequence networks with parallel transformer banks · Power System Analysis II, chapter 4
- Sequence network of loaded generator with Zn · Power System Analysis II, chapter 4
- Line currents with isolated and grounded neutral · Power System Analysis II, chapter 4
- Neutral current and power, 380 V unbalanced load · Basic Electrical Engineering, chapter 8
- Star system with three loads, neutral current · Basic Electrical Engineering, chapter 8
- Balanced circulating current: 10 kV alternator · Switchgear and Protection, chapter 7
- Current through inductor, equivalent impedance · Basic Electrical Engineering, chapter 2