Short answer

A loaded synchronous generator grounded through impedance Zn produces only positive-sequence EMF. Sequence networks: V_{a1} = E_a - I_{a1} Z_1, V_{a2} = -I_{a2} Z_2, V_{a0} = -I_{a0}(Z_{g0}+3Z_n). Only zero sequence sees the neutral impedance as 3Z_n because neutral current is 3I_{a0}.

What is significance of sequence components? Deduce the sequence network for a loaded synchronous generator grounded through impedance Zn.

Significance of sequence components

Sequence components let an unbalanced three-phase system be analysed as three independent balanced single-phase networks (positive, negative, zero). For balanced equipment the sequence impedances are uncoupled, so unbalanced faults are solved by connecting the sequence networks only at the fault point.

Sequence networks of a synchronous generator grounded through ZnZ_n

A generator produces only balanced positive sequence EMFs EaE_a, Eb=a2EaE_b = a^2E_a, Ec=aEaE_c = aE_a. Let Z1Z_1 and Z2Z_2 be its positive and negative sequence impedances and Zg0Z_{g0} its zero sequence impedance per phase. The neutral is grounded through ZnZ_n.

            Ia -->
    +-(Ea)--Zg--o a
    |
 n  +-(Eb)--Zg--o b     Va, Vb, Vc measured
    |                   to ground
    +-(Ec)--Zg--o c
    |
   Zn  In = Ia+Ib+Ic
    |
  ground

Here ZgZ_g is the winding impedance of each phase.

Positive sequence: the EMF is purely positive sequence, and positive sequence currents are balanced, so no current flows in ZnZ_n:

Va1=Ea−Ia1Z1V_{a1} = E_a - I_{a1}Z_1

Negative sequence: there is no negative sequence EMF, and the currents are balanced, so no current flows in ZnZ_n:

Va2=−Ia2Z2V_{a2} = -I_{a2}Z_2

Zero sequence: there is no zero sequence EMF. The neutral current is In=3Ia0I_n = 3I_{a0}, so the drop in ZnZ_n is 3Ia0Zn3I_{a0}Z_n:

Va0=−Ia0Zg0−3Ia0Zn=−Ia0(Zg0+3Zn)=−Ia0Z0V_{a0} = -I_{a0}Z_{g0} - 3I_{a0}Z_n = -I_{a0}(Z_{g0} + 3Z_n) = -I_{a0}Z_0

In matrix form:

[Va0Va1Va2]=[0Ea0]−[Z0000Z1000Z2][Ia0Ia1Ia2]\begin{bmatrix} V_{a0}\\V_{a1}\\V_{a2} \end{bmatrix} = \begin{bmatrix} 0\\E_a\\0 \end{bmatrix} - \begin{bmatrix} Z_0&0&0\\0&Z_1&0\\0&0&Z_2 \end{bmatrix}\begin{bmatrix} I_{a0}\\I_{a1}\\I_{a2} \end{bmatrix}
 Positive          Negative          Zero
 F1 o              F2 o              F0 o
    | Ia1 ^           | Ia2 ^           | Ia0 ^
   Z1                Z2               Zg0
    |                 |                 |
  (Ea)                |                3Zn
    |                 |                 |
 N1 o (ref)        N2 o (ref)        N0 o (ground)

Loaded generator: when the generator supplies a balanced load before the fault, the load appears in the positive sequence network (and in the negative and zero sequence networks with its own sequence impedances). Using Thevenin's theorem at the fault point, EaE_a is replaced by the prefault voltage VfV_f at that point, and Z1Z_1 by the Thevenin impedance of the generator in parallel with the load. The zero sequence network still contains 3Zn3Z_n.