- 2079 Bhadra · 2+6 marks
Sequence network of loaded generator with Zn
Short answer
A loaded synchronous generator grounded through impedance Zn produces only positive-sequence EMF. Sequence networks: V_{a1} = E_a - I_{a1} Z_1, V_{a2} = -I_{a2} Z_2, V_{a0} = -I_{a0}(Z_{g0}+3Z_n). Only zero sequence sees the neutral impedance as 3Z_n because neutral current is 3I_{a0}.
What is significance of sequence components? Deduce the sequence network for a loaded synchronous generator grounded through impedance Zn.
Significance of sequence components
Sequence components let an unbalanced three-phase system be analysed as three independent balanced single-phase networks (positive, negative, zero). For balanced equipment the sequence impedances are uncoupled, so unbalanced faults are solved by connecting the sequence networks only at the fault point.
Sequence networks of a synchronous generator grounded through
A generator produces only balanced positive sequence EMFs , , . Let and be its positive and negative sequence impedances and its zero sequence impedance per phase. The neutral is grounded through .
Ia -->
+-(Ea)--Zg--o a
|
n +-(Eb)--Zg--o b Va, Vb, Vc measured
| to ground
+-(Ec)--Zg--o c
|
Zn In = Ia+Ib+Ic
|
ground
Here is the winding impedance of each phase.
Positive sequence: the EMF is purely positive sequence, and positive sequence currents are balanced, so no current flows in :
Negative sequence: there is no negative sequence EMF, and the currents are balanced, so no current flows in :
Zero sequence: there is no zero sequence EMF. The neutral current is , so the drop in is :
In matrix form:
Positive Negative Zero
F1 o F2 o F0 o
| Ia1 ^ | Ia2 ^ | Ia0 ^
Z1 Z2 Zg0
| | |
(Ea) | 3Zn
| | |
N1 o (ref) N2 o (ref) N0 o (ground)
Loaded generator: when the generator supplies a balanced load before the fault, the load appears in the positive sequence network (and in the negative and zero sequence networks with its own sequence impedances). Using Thevenin's theorem at the fault point, is replaced by the prefault voltage at that point, and by the Thevenin impedance of the generator in parallel with the load. The zero sequence network still contains .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Sequence impedances of star load with Zn · Power System Analysis II, chapter 4 · asked 2×
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Sequence impedance of load with mutual coupling · Power System Analysis II, chapter 4
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Sequence networks of Y load, neutral current · Power System Analysis II, chapter 4 · asked 2×
- L-G fault through Zf: currents and voltages · Power System Analysis II, chapter 5
- Hunting; loaded operation of synchronous motor · Electrical Machines, chapter 6
- Current through inductor, equivalent impedance · Basic Electrical Engineering, chapter 2
- Impedance diagram: 25 MVA generator, two motors · Power System Analysis I, chapter 3
- Synchronous generator constructional diagram · Basic Electrical and Electronics Engineering, chapter 2