- 2070 Asar · 4 marks
Zero sequence Thevenin impedance at bus 2
Short answer
The delta windings block zero sequence from the generator and transformer, so only the motor branch appears. Adding the motor reactance and three times the neutral reactance gives j(0.1 + 3×0.05) = j0.25 pu. Thevenin zero sequence impedance at bus 2 is j0.25 pu on 100 MVA base.
For the power system shown in figure below, draw the zero sequence network hence determine the Thevenin's equivalent zero sequence impedance as view from bus-2. [Figure: generator G 100 MVA, 13.8 kV, X0 = 0.05 pu (Y grounded) - T1 100 MVA, 13.8/138 kV, Δ/Y grounded, x = 0.10 pu - line X0 = 60 Ω - T2 100 MVA, 138/13.8 kV, Y grounded/Δ, x = 0.1 pu - bus 2 - motor M 100 MVA, 13.8 kV, X0 = 0.1 pu, neutral grounded through Xn = 0.05 pu]
The zero sequence network is drawn from the winding connections: a delta winding blocks zero sequence current from its line side, and a neutral reactance appears as . Bus 2 lies between T2 (delta on the 13.8 kV side) and the motor.
Per unit values (100 MVA, 138 kV line base)
- Generator: pu (Y grounded)
- T1 (Δ / Y-grounded): pu
- Line: , pu
- T2 (Y-grounded / Δ): pu
- Motor: pu, neutral pu
Zero sequence connections
- T1 (Δ on generator side, Yg on line side): the line side is connected to the reference through 0.10; the generator side is open. So the generator is isolated from the rest.
- T2 (Yg on line side, Δ on bus-2 side): the line side is connected to the reference through 0.10; bus 2 side is open.
- Motor: star grounded through , so its branch is pu to reference.
G T1 Line T2 bus 2 M
o o o----j0.315----o o o-------+
| | | | | |
j0.05 open j0.10 j0.10 open j0.10
| | | |
| | | j0.15 (3Xn)
| | | |
==+=======+==== reference (ground) ===========+==
Thevenin zero sequence impedance at bus 2
Looking into bus 2, the path through T2 is open (delta on the bus-2 side), so only the motor branch is seen:
Answer: at bus 2 = j0.25 pu (100 MVA base). The generator, T1, line and T2 do not contribute because of the delta windings.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Equivalent Z0, Z1, Z2 at bus 3 · Power System Analysis II, chapter 5
- LLG fault sequence currents at bus 3 · Power System Analysis II, chapter 5
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Impedance diagram: 25 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3