- 2068 Chaitra · 8 marks
Equivalent Z0, Z1, Z2 at bus 3
Short answer
Positive and negative sequence impedances at bus 3: Z1 = Z2 = j0.1983 pu. Zero-sequence impedance: Z0 = j(0.1+0.0545) ∥ j0.33 = j0.105 pu (or j0.094 pu depending on neutral reactor base).
Draw positive, negative and zero sequence networks. If an unsymmetrical fault occurs at bus 3, determine equivalent Z0, Z1 and Z2. [Figure: G1 100 MVA, 11 kV, X1 = X2 = j0.2 pu, X0 = j0.05 pu (Y grounded) - T1 100 MVA, 11/220 kV, j0.1 pu (Δ / Y grounded) - parallel lines L1 (100 MVA, 220 kV, j0.1 pu) and L2 (100 MVA, 220 kV, 0.12 pu) - T2 50 MVA, 11/220 kV, j0.075 pu (Y grounded through j0.03 pu on line side / Δ) - G2 50 MVA, 11 kV, X1 = X2 = j0.15 pu, X0 = j0.03 pu (Y grounded through j0.024 pu)]
Assumptions: base 100 MVA; bus 1 = G1 terminal, bus 2 = T1 HV side, bus 3 = T2 HV side (end of the parallel lines), bus 4 = G2 terminal. Neutral reactances (j0.03 for T2, j0.024 for G2) are taken on their own 50 MVA rating. Line zero-sequence reactance is taken equal to the given value since no separate is given.
Per-unit values on 100 MVA
| Element | ||
|---|---|---|
| G1 | 0.20 | 0.05 |
| T1 | 0.10 | 0.10 |
| L1 ∥ L2 | 0.0545 | |
| T2 () | 0.15 | 0.15 |
| T2 neutral () | – | |
| G2 () | 0.30 | 0.06 |
| G2 neutral () | – |
Positive sequence network
E1-j0.2-(1)-j0.1-(2)-j0.0545-(3)-j0.15-(4)-j0.3-E2
|
F
Negative sequence network
Same reactances, emfs shorted:
Zero sequence network
- T1 Δ (G1 side)/Yg (line side): bus 2 to reference through ; G1 isolated.
- T2 Yg through j0.03 (line side)/Δ (G2 side): bus 3 to reference through ; G2 isolated.
ref-j0.1-(2)-j0.0545-(3)-j0.33-ref
|
F
G1 (j0.05) and G2 (j0.06+j0.144) isolated by deltas
Answer: pu, pu at bus 3.
(If the neutral reactance j0.03 is taken as already on the 100 MVA base, pu.)
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- LLG fault sequence currents at bus 3 · Power System Analysis II, chapter 5
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3