L-G fault at bus 1 through Zf

Short answer

Thevenin impedances at bus 1 are Z1=Z2=j0.2024 pu, Z0=j0.0845 pu. With fault impedance j0.05 pu, Ia1 = 1/(j0.6393) = -j1.564 pu. Fault current I_f = 3Ia1 = 4.692 pu = 1.03 kA at 132 kV.

Figure shows a power system network. Draw positive, negative and zero sequence network. If LG fault occurs at bus 1, find fault current. Assume fault impedance Zf = 0.05 p.u.

EquipmentMVA ratingVoltage ratingX1 (p.u.)X2 (p.u.)X0 (p.u.)
G15011 KV0.200.200.08
G23011 KV0.250.250.1
Transformer T15011/132 KV0.10.10.1
Transformer T1 (T2)3011/132 KV0.090.090.09
Line L145132 KV0.10.10.25
Line L1 (L2)45132 KV0.10.10.25

[Figure: G1 (Y grounded) - T1 (Δ on generator side, Y grounded on bus 1 side) - bus 1 - two parallel lines - bus 2 - T2 (Y grounded on bus 2 side, Y grounded through j0.03 on generator side) - G2 (Y grounded); fault F at bus 1]

Assumptions: base 50 MVA, 11 kV (generators) and 132 kV (lines). The neutral reactance j0.03 of T2 is taken as already on the 50 MVA base. Pre-fault voltage 1 pu, no load.

Per-unit values on 50 MVA

ElementX1=X2X_1 = X_2X0X_0
G10.200.08
G2 (×50/30\times 50/30)0.41670.1667
T10.100.10
T2 (×50/30\times 50/30)0.150.15
Each line (×50/45\times 50/45)0.11110.2778
Two lines in parallel0.05560.1389

Sequence networks

Positive (negative same, no emf):
 E1-j0.2-j0.1-(1)-j0.0556-(2)-j0.15-j0.4167-E2
               F
Zero:
 ref-j0.1-(1)-j0.1389-(2)-j0.15-[3x j0.03]-j0.1667-ref
 (G1 cut off by T1 delta; T2 is Yg-Yg, so G2
  zero seq path continues through T2)

Thevenin impedances at bus 1

Z1=Z2=j0.30 ∥ j(0.0556+0.15+0.4167)=j0.30 ∥ j0.6222=j0.2024 puZ0=j0.10 ∥ j(0.1389+0.15+0.09+0.1667)=j0.10 ∥ j0.5456=j0.0845 pu\begin{aligned} Z_1 = Z_2 &= j0.30\ \|\ j(0.0556 + 0.15 + 0.4167) = j0.30\ \|\ j0.6222 = j0.2024\ \text{pu} \\ Z_0 &= j0.10\ \|\ j(0.1389 + 0.15 + 0.09 + 0.1667) = j0.10\ \|\ j0.5456 = j0.0845\ \text{pu} \end{aligned}

Fault current (L-G through Zf=0.05Z_f = 0.05 pu)

Ia0=Ia1=Ia2=VfZ1+Z2+Z0+3ZfI_{a0} = I_{a1} = I_{a2} = \frac{V_f}{Z_1 + Z_2 + Z_0 + 3Z_f}

Taking ZfZ_f as a reactance j0.05j0.05 (usual in these problems), 3Zf=j0.153Z_f = j0.15:

Ia0=1j(0.2024+0.2024+0.0845+0.15)=1j0.6393=−j1.564 puIf=3Ia0=−j4.692 pu\begin{aligned} I_{a0} &= \frac{1}{j(0.2024+0.2024+0.0845+0.15)} = \frac{1}{j0.6393} = -j1.564\ \text{pu} \\ I_f &= 3I_{a0} = -j4.692\ \text{pu} \end{aligned}

Base current at 132 kV:

Ibase=50×1063×132×103=218.7 AI_{base} = \frac{50\times10^6}{\sqrt3 \times 132\times10^3} = 218.7\ \text{A} If=4.692×218.7=1026 AI_f = 4.692 \times 218.7 = 1026\ \text{A}

Answer: L-G fault current at bus 1 ≈ 4.69 pu ≈ 1.03 kA.

(If ZfZ_f is taken as a pure resistance 0.05 pu, ∣If∣=3/∣0.15+j0.4893∣=5.86|I_f| = 3/|0.15 + j0.4893| = 5.86 pu.)