LLG fault sequence currents at bus 3
Short answer
Thevenin Z1=j0.2200 pu, Z0=j0.3032 pu at bus 3. With Zf=j0.1 pu, sequence currents: I_a1 = -j2.624 pu, I_a2 = j1.923 pu, I_a0 = j0.701 pu. Ground fault current = 3I_a0 = j2.103 pu.
Compute the sequence currents for a LLG fault at bus 3 of the following network. The fault impedance is j0.1 pu. All the parameters are in pu. [Figure: G1 (Y grounded) - T1 (Y grounded/Y grounded) - bus 1; G2 (Y grounded) - T2 (Δ on generator side/Y grounded) - bus 2; L1 between buses 1 and 2, L2 between buses 1 and 3, L3 between buses 2 and 3]
| Item | Base MVA | X1 | X2 | X0 |
|---|---|---|---|---|
| G1 | 100 | 0.15 | 0.15 | 0.05 |
| G2 | 100 | 0.15 | 0.15 | 0.05 |
| T1 | 100 | 0.1 | 0.1 | 0.1 |
| T2 | 100 | 0.1 | 0.1 | 0.1 |
| L1 | 100 | 0.12 | 0.12 | 0.3 |
| L2 | 100 | 0.15 | 0.15 | 0.35 |
| L3 | 100 | 0.25 | 0.25 | 0.71 |
Approach: find the Thevenin impedances at bus 3 from the bus impedance matrices of the positive and zero sequence networks ( since all ), then connect the networks for an LLG fault. Pre-fault voltage pu, no load; pu is the impedance from the faulted phases' common point to ground.
Positive sequence network
Generator + transformer branches to reference: bus 1: ; bus 2: . Lines: 1-2 , 1-3 , 2-3 .
E1 E2
| |
j0.25 j0.25
| |
(1)--j0.12--(2)
\ /
j0.15 j0.25
\ /
(3) F
Forming and inverting gives
So pu.
Zero sequence network
- G1 (Yg) + T1 (Yg/Yg): zero-seq path passes, bus 1 to reference
- G2 behind T2 (Δ on generator side, Yg on bus side): bus 2 to reference through only; G2 is cut off
- Lines: 1-2 , 1-3 , 2-3
So pu.
Sequence currents for LLG fault (phases b, c to ground through )
The negative network is in parallel with the zero network plus :
Check: .
Phase and fault currents
Answer: pu, pu, pu; fault (ground) current pu; pu.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- p.u. impedance diagram: G, T1, line, T2, M · Power System Analysis I, chapter 3
- Impedance diagram: 25 MVA generator, two motors · Power System Analysis I, chapter 3
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3