Short answer

Use 20 MVA base with base voltages 6.6 kV, 79.2 kV, 6.6 kV. Per-unit values are XG=0.15, XT1=0.2222, Zline=0.0319+j0.1913, XT2=0.2778, XM=0.5556. Draw the series impedance diagram from generator to motor with a common reference bus.

Draw the p.u. impedance diagram for the system shown below. [Figure: G (6.6 kV, 20 MVA, X = 0.15 p.u.) → T1 (11/132 kV, 25 MVA, X = 0.1 p.u.) → line 10 + j60 Ω → T2 (132/11 kV, 20 MVA, X = 0.1) → motor M (11 kV, 15 MVA, X = 0.15 p.u.).]

Choose the generator rating as base: 20 MVA, 6.6 kV in the generator circuit. (The 6.6 kV generator feeds the 11 kV winding of T1, so the transformer and motor values need voltage correction.)

Base voltages

  • Generator zone: Vb1=6.6V_{b1} = 6.6 kV
  • Line zone (T1 11/132 kV): Vb2=6.6×13211=79.2V_{b2} = 6.6\times\frac{132}{11} = 79.2 kV
  • Motor zone (T2 132/11 kV): Vb3=79.2×11132=6.6V_{b3} = 79.2\times\frac{11}{132} = 6.6 kV
Zb2=79.2220=313.63 ΩZ_{b2} = \frac{79.2^2}{20} = 313.63\ \Omega

Per-unit values

XG=0.15 puXT1=0.1×2025×(116.6)2=0.2222 puZline=10+j60313.63=0.0319+j0.1913 puXT2=0.1×2020×(13279.2)2=0.2778 puXM=0.15×2015×(116.6)2=0.5556 pu\begin{aligned} X_G &= 0.15\ \text{pu}\\ X_{T1} &= 0.1\times\frac{20}{25}\times\left(\frac{11}{6.6}\right)^2 = 0.2222\ \text{pu}\\ Z_{line} &= \frac{10 + j60}{313.63} = 0.0319 + j0.1913\ \text{pu}\\ X_{T2} &= 0.1\times\frac{20}{20}\times\left(\frac{132}{79.2}\right)^2 = 0.2778\ \text{pu}\\ X_M &= 0.15\times\frac{20}{15}\times\left(\frac{11}{6.6}\right)^2 = 0.5556\ \text{pu} \end{aligned}

Impedance diagram

     j0.2222  0.0319+j0.1913  j0.2778
 +---/\/\/-------/\/\/--------/\/\/---+
 |    T1          line          T2    |
j0.15                              j0.5556
 |                                    |
(Eg)                                 (Em)
 |                                    |
 +------------------------------------+
            reference bus

Answer: On 20 MVA (base 6.6 / 79.2 / 6.6 kV): XG=0.15X_G = 0.15, XT1=0.2222X_{T1} = 0.2222, Zline=0.0319+j0.1913Z_{line} = 0.0319 + j0.1913, XT2=0.2778X_{T2} = 0.2778, XM=0.5556X_M = 0.5556 pu.