- 2068 Bhadra · 5 marks
Reactance diagram: G, T1, j18 Ω line, T2, M
Short answer
Using 25 MVA and 13.8/66/11 kV bases: generator reactance 0.0858 pu, both transformers 0.12 pu, line j18 ohm gives 0.1033 pu, and motor 0.13 pu. Draw a single loop from generator through T1, line, T2 to motor with these reactances to neutral.
Draw a reactance diagram of the electric power system given below and express all reactances in per unit system by choosing appropriate base values. G1: 14 kV, 30 MVA, 10%; M: 11 kV, 25 MVA, 13%; T1: 66/11 kV, 25 MVA, 12%; T1: 13.8/66 kV, 25 MVA, 12% (as printed; one of these is T2). [Figure: G → T1 → line j18 Ohms/phase → T2 → motor M.]
The two transformers are read as T1: 13.8/66 kV (at the generator) and T2: 66/11 kV (at the motor), both 25 MVA, 12 %.
Choice of base: 25 MVA (transformer rating), 66 kV on the line. Then the base is 13.8 kV in the generator zone and 11 kV in the motor zone.
Per-unit reactances
| Element | Base kV | X (pu, 25 MVA) |
|---|---|---|
| G (30 MVA, 14 kV) | 13.8 | 0.0858 |
| T1 | 13.8/66 | 0.1200 |
| Line j18 Ω | 66 | 0.1033 |
| T2 | 66/11 | 0.1200 |
| Motor M | 11 | 0.1300 |
Reactance diagram
j0.12 j0.1033 j0.12
+----/\/\/----/\/\/------/\/\/----+
| T1 line T2 |
j0.0858 j0.13
| |
(Eg) (Em)
| |
+---------------------------------+
reference bus
Answer: On 25 MVA (13.8 / 66 / 11 kV): , , , , pu.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: two generators, two motors, j50 Ω line · Power System Analysis I, chapter 3
- 30 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×