- 2073 Magh · 10 marks
Reactance diagram: 30 MVA, 6.6 kV base, three lines
Short answer
Using 30 MVA base, XG1=0.24, XG2=0.30, XM=0.15, XT1=0.10, XT2=0.20 pu; assume T3 is 30 MVA, 115/13.2 kV, X=0.10 pu. Line zone base is 115 kV, Zb=440.83 ohm, so each line reactance in pu is X(ohm)/440.83. Draw the reactance diagram with these series reactances and grounded generator references.
Compute the per unit values taking power base of 30 MVA and 6.6 kV in the circuit of generator G1 and draw the reactance diagram of a power system shown in figure below. The system has the following data: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; M: 30 MVA, 13.2 kV, X = 0.15 p.u.; T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Y grounded–Y grounded) → bus; Line-1 from this bus to a junction; Line-3 from the junction to a bus feeding T3 (Y grounded on line side, Δ on motor side) → motor M; Line-2 from the junction down to a bus feeding T2 (grounded windings) → G2 (Y, grounded). No line impedances or T3 rating are printed.]
Base: 30 MVA and 6.6 kV in the G1 circuit. The line impedances and the T3 rating are not printed, so T3 is assumed to be 30 MVA, 115/13.2 kV, X = 0.1 pu, and the line reactances are kept as symbols (Ω).
Base voltages
- G1 zone: 6.6 kV
- Line zone (T1 6.6/115 kV): 115 kV,
- G2 zone (T2 115/6.6 kV): 6.6 kV
- Motor zone (T3 115/13.2 kV): 13.2 kV
Per-unit values (30 MVA base)
For example, a line reactance of 100 Ω would be pu.
| Element | X (pu, 30 MVA) |
|---|---|
| G1 | 0.24 |
| G2 | 0.30 |
| Motor M | 0.15 |
| T1 | 0.10 |
| T2 | 0.20 |
| T3 (assumed) | 0.10 |
| Lines 1, 2, 3 |
Reactance diagram
j0.10 jXL1 jXL3 j0.10
+---/\/\/---/\/\/--+--/\/\/---/\/\/---+
| T1 Line1 | Line3 T3 |
j0.24 | j0.15
| jXL2 (Line2) |
(E1) | (Em)
| j0.20 (T2) |
| | |
| j0.30 (G2) |
| | |
| (E2) |
+------------------+------------------+
reference (neutral) bus
Answer: , , , , , pu, and each line pu on the 30 MVA, 115 kV base.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Block diagram reduction with G1, G2, H1, H2, feedforward · Control Systems, chapter 3 · asked 2×
- Salient pole generator phasor diagram in per unit · Electric Machines II, chapter 1