Short circuit MVA of feeder circuit breaker
Short answer
Each source branch 0.15 pu, lines 0.10 pu; symmetrical network gives Xth = 0.125 pu at bus 3. Short-circuit MVA of feeder CB = 800 MVA, fault current = 3.50 kA at 132 kV.
For the 3 bus power system shown in figure below the generators are rated 100 MVA with transient reactance of 10% each. Both the transformers are 100 MVA with a leakage reactance of 5%. The reactance of each of the line to a base of 100 MVA, 132 KV is 10%. Find the short circuit MVA of circuit breaker in outgoing feeder from bus-3, if a 3-phase fault occurs beyond the CB at point F. Assume pre-fault voltage of bus-3 is 1 pu and pre-fault current through feeder is zero. [Figure: G1 - T1 (11/132 kV; labelled 11/110 kV in the 2070 Asar paper) - bus 1; G2 - T2 (11/132 kV) - bus 2; lines 1-2, 1-3 and 2-3, each j0.1; outgoing feeder from bus 3 through circuit breaker CB to the fault point F]
The short-circuit MVA that the feeder circuit breaker must interrupt is the fault level at bus 3, since the fault is just beyond the breaker and the feeder impedance up to F is negligible. Base: 100 MVA, 11 kV / 132 kV. Pre-fault pu and pre-fault current is zero, so all source EMFs are 1 pu.
Per-unit reactances (100 MVA base)
- G1, G2: 0.10 pu each; T1, T2: 0.05 pu each, so each source branch is pu.
- Lines 1-2, 1-3, 2-3: 0.10 pu each.
E=1 E=1
| |
j0.15 j0.15
| |
bus1 ---- j0.1 ---- bus2
\ /
j0.1 j0.1
\ /
bus 3 --CB-- F
Thevenin reactance at bus 3
The network is symmetrical about bus 3: buses 1 and 2 are always at the same potential, so line 1-2 carries no current. Each path is pu, and the two are in parallel:
Short-circuit MVA of the breaker
Answer: the circuit breaker should be rated for a short-circuit capacity of 800 MVA, with a fault current of about 3.50 kA at 132 kV. (For the 11/110 kV variant the per-unit values and the 800 MVA result are the same; only the current in amperes changes, to 4.20 kA at 110 kV.)
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- Short circuit MVA at bus 2 · Power System Analysis II, chapter 3
- Fault at both ends of a 50 Ω line · Power System Analysis II, chapter 3
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3