Fault at both ends of a 50 Ω line

Short answer

Using 50 MVA, 132 kV base, per-unit reactances: G1,G2 0.1033, T1,T2 0.10, line 0.1435. At P, Thevenin reactance is parallel combination of (0.2033 and 0.3468) = 0.1282 pu. Fault current = 1/0.1282 = 7.80 pu = 1706 A (1.71 kA). Same at Q due to symmetry.

The single line diagram of a power system is shown in figure below. Compute the fault current in p.u. and in absolute value if a 3 phase to ground fault occurs at (consider no fault impedance): i. the point P i.e. connection point between transmission line and HV side of transformer T1 ii. the point Q i.e. connection point between transmission line and HV side of transformer T2 (printed as T1). [Figure: G1 6 kV, 40 MVA, X = 10% - bus - T1 6.6/132 kV, 50 MVA, X = 10% - point P - line X = 50 Ω - point Q - T2 132/6.6 kV, 50 MVA, X = 10% - bus with load - G2 6 kV, 40 MVA, X = 10%]

For a bolted 3-phase fault, If=1/XthI_f = 1/X_{th} pu, where XthX_{th} is the parallel combination of the reactances from the fault point back to each generator (prefault voltage 1 pu, load current neglected).

Data and per unit values

Base: 50 MVA; 132 kV on the line, hence 6.6 kV on the generator buses (from the 6.6/132 kV transformers). Zb,line=1322/50=348.48 ΩZ_{b,line} = 132^2/50 = 348.48\ \Omega.

ElementCalculationX (pu)
G1, G2 (6 kV, 40 MVA, 10%)0.10×5040×(66.6)20.10 \times \frac{50}{40} \times \left(\frac{6}{6.6}\right)^20.1033 each
T1, T2 (50 MVA, 10%)on own base0.10 each
Line (50 Ω)50/348.4850/348.480.1435

Base current at 132 kV: Ib=50×1063×132×103=218.7I_b = \dfrac{50\times10^6}{\sqrt3 \times 132\times10^3} = 218.7 A.

 G1      T1      P    Line     Q     T2     G2
(~)-0.1033-0.10--o--0.1435--o--0.10-0.1033-(~)
 |                                          |
 +============= reference (EMF 1 pu) =======+

i. Fault at point P

Xleft=XG1+XT1=0.1033+0.10=0.2033Xright=Xline+XT2+XG2=0.1435+0.10+0.1033=0.3468Xth=0.2033×0.34680.2033+0.3468=0.1282 puIf=10.1282=7.80 puIf=7.80×218.7=1706 A\begin{aligned} X_{left} &= X_{G1} + X_{T1} = 0.1033 + 0.10 = 0.2033 \\ X_{right} &= X_{line} + X_{T2} + X_{G2} = 0.1435 + 0.10 + 0.1033 = 0.3468 \\ X_{th} &= \frac{0.2033 \times 0.3468}{0.2033 + 0.3468} = 0.1282\ \text{pu} \\ I_f &= \frac{1}{0.1282} = 7.80\ \text{pu} \\ I_f &= 7.80 \times 218.7 = 1706\ \text{A} \end{aligned}

Contribution from G1 side =7.80×0.3468/0.5501=4.92= 7.80 \times 0.3468/0.5501 = 4.92 pu, from G2 side =2.88= 2.88 pu. Fault MVA =50/0.1282=390= 50/0.1282 = 390 MVA.

ii. Fault at point Q

Xleft=XG1+XT1+Xline=0.3468Xright=XT2+XG2=0.2033Xth=0.3468×0.20330.5501=0.1282 puIf=7.80 pu=1706 A\begin{aligned} X_{left} &= X_{G1} + X_{T1} + X_{line} = 0.3468 \\ X_{right} &= X_{T2} + X_{G2} = 0.2033 \\ X_{th} &= \frac{0.3468 \times 0.2033}{0.5501} = 0.1282\ \text{pu} \\ I_f &= 7.80\ \text{pu} = 1706\ \text{A} \end{aligned}

Now G2 side supplies 4.92 pu and G1 side 2.88 pu.

The network is symmetrical about the middle of the line, so the fault current magnitude is the same at P and Q; only the sharing between the generators changes.

Answer: At P and at Q, IfI_f = 7.80 pu ≈ 1706 A (≈ 1.71 kA at 132 kV), fault level ≈ 390 MVA.

✓ Answer checked by Claude Sonnet 5.5

All Power System Analysis II chapter 3 questions →