- 2069 Chaitra · 6+6 marks
Fault at both ends of a 50 Ω line
Short answer
Using 50 MVA, 132 kV base, per-unit reactances: G1,G2 0.1033, T1,T2 0.10, line 0.1435. At P, Thevenin reactance is parallel combination of (0.2033 and 0.3468) = 0.1282 pu. Fault current = 1/0.1282 = 7.80 pu = 1706 A (1.71 kA). Same at Q due to symmetry.
The single line diagram of a power system is shown in figure below. Compute the fault current in p.u. and in absolute value if a 3 phase to ground fault occurs at (consider no fault impedance): i. the point P i.e. connection point between transmission line and HV side of transformer T1 ii. the point Q i.e. connection point between transmission line and HV side of transformer T2 (printed as T1). [Figure: G1 6 kV, 40 MVA, X = 10% - bus - T1 6.6/132 kV, 50 MVA, X = 10% - point P - line X = 50 Ω - point Q - T2 132/6.6 kV, 50 MVA, X = 10% - bus with load - G2 6 kV, 40 MVA, X = 10%]
For a bolted 3-phase fault, pu, where is the parallel combination of the reactances from the fault point back to each generator (prefault voltage 1 pu, load current neglected).
Data and per unit values
Base: 50 MVA; 132 kV on the line, hence 6.6 kV on the generator buses (from the 6.6/132 kV transformers). .
| Element | Calculation | X (pu) |
|---|---|---|
| G1, G2 (6 kV, 40 MVA, 10%) | 0.1033 each | |
| T1, T2 (50 MVA, 10%) | on own base | 0.10 each |
| Line (50 Ω) | 0.1435 |
Base current at 132 kV: A.
G1 T1 P Line Q T2 G2
(~)-0.1033-0.10--o--0.1435--o--0.10-0.1033-(~)
| |
+============= reference (EMF 1 pu) =======+
i. Fault at point P
Contribution from G1 side pu, from G2 side pu. Fault MVA MVA.
ii. Fault at point Q
Now G2 side supplies 4.92 pu and G1 side 2.88 pu.
The network is symmetrical about the middle of the line, so the fault current magnitude is the same at P and Q; only the sharing between the generators changes.
Answer: At P and at Q, = 7.80 pu ≈ 1706 A (≈ 1.71 kA at 132 kV), fault level ≈ 390 MVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- Mid-line fault cleared at 60°, E = 1.04 · Power System Analysis II, chapter 6
- No zero sequence in line-to-line fault · Power System Analysis II, chapter 5 · asked 2×
- Mid-line fault, cleared at 60° · Power System Analysis II, chapter 6
- L-L fault at point q with two motors · Power System Analysis II, chapter 5
- L-L fault at point B · Power System Analysis II, chapter 5
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Maximum power with 132 kV at both ends · Power System Analysis I, chapter 6
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×