- 2073 Chaitra · 8 marks
Mid-line fault, cleared at 60°
Short answer
For a sustained fault, Pe_max during fault (1.2 pu) is below Pm (1.5 pu), so stable operation is impossible. Clearing at 60° yields a stable case with maximum swing about 105.9°; the critical clearing angle is 68.5°.
A balanced 3-phase fault occurs at the middle point of line 2 when power transfer is 1.5 pu in the system shown in the figure below. Given: E = 1.2, V = 1, X'd = 0.2, X1 = X2 = 0.4 pu. i) Determine whether the system is stable for a sustained fault. ii) The fault is cleared at δ = 60°. Is the system stable? If so find the maximum rotor swing iii) Find the critical clearing angle. [Figure: generator E∠δ behind X'd feeding two parallel lines X1 and X2 (circuit breakers at both ends) to the infinite bus V∠0; fault F at the middle of line 2]
Data: , , , pu, pu.
Power-angle curves
Pre-fault:
During the fault (midpoint of line 2): the network is a star with to node A: ; A to : (line 1); A to ground: (half of line 2). The other half of line 2, from the fault to , only shunts the infinite bus. Star-delta conversion gives the transfer reactance:
Post-fault (line 2 open):
(i) Sustained fault
During the fault, . The electrical output can never equal the input, so the rotor keeps accelerating and no decelerating area exists. The system is unstable for a sustained fault.
(ii) Fault cleared at
Accelerating area:
Decelerating area available:
Since , the system is stable. For the maximum swing , set . Solving numerically gives .
(iii) Critical clearing angle
Answer: (i) unstable for a sustained fault; (ii) stable, maximum swing ≈ 105.9°; (iii) .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Mid-line fault cleared at 60°, E = 1.04 · Power System Analysis II, chapter 6
- Fault cleared at 45°: stability and maximum swing · Power System Analysis II, chapter 6
- SLG fault at mid-line through 4.033 Ω · Power System Analysis II, chapter 5
- L-L fault at point q with two motors · Power System Analysis II, chapter 5
- Fault cleared at 30°, Pe = 2.1 sin δ · Power System Analysis II, chapter 6
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Find x3[n] from X3=X1X2, x1 5-point, x2 4-point · Digital Signal Analysis and Processing, chapter 7 · asked 3×
- Two-mass system X1/F, X2/F with F-V analogy · Control Systems, chapter 2 · asked 3×
- Free body diagram and X1/F, X2/F of two-mass system · Control Systems, chapter 2
- Vertical two-mass system transfer function X1/F · Control Systems, chapter 2