L-L fault at point q with two motors

Short answer

Positive/negative Thevenin impedances at bus q: Z1=j0.0929 pu, Z2=j0.0998 pu. For the L-L fault, Ia1 = -Ia2 = -j5.19 pu. Fault currents: Ib = -8.99 pu, Ic = 8.99 pu, Ia = 0.

A single line diagram of a power system network is shown in figure below. The system data is given in the table below:

ElementX1 (pu)X2 (pu)X0 (pu)
G0.10.120.05
M10.050.060.025
M20.050.060.025
T10.070.070.07
T20.080.080.08
Line0.10.10.3

i) Draw sequence networks ii) Find fault current for a line-to-line fault on phase b and c at point q. Assume 1.0 pu pre-fault voltage throughout. [Figure: G - bus p - T1 (Δ/Y grounded) - bus q - line - bus r - T2 (Y grounded/Δ) - bus s, which feeds motors M1 (Y, ungrounded) and M2 (Y grounded)]

Assumptions: all reactances on a common base; pre-fault voltage 1 pu everywhere (no load current); bolted fault between phases b and c at q.

(i) Sequence networks

Positive (emfs Eg, Em):
 Eg-j0.1-(p)-j0.07-(q)-j0.1-(r)-j0.08-(s)-+-j0.05-Em1
                    |                     +-j0.05-Em2
                    F
Negative: same layout, G j0.12, T1 j0.07,
 line j0.1, T2 j0.08, M1 j0.06, M2 j0.06, no emfs
Zero:
 ref-j0.07-(q)-j0.3-(r)-j0.08-ref
 G (j0.05) cut off by T1 delta; M1 ungrounded,
 M2 (j0.025) cut off by T2 delta

T1 is Δ/Yg with the grounded star at q, and T2 is Yg/Δ with the grounded star at r, so the zero network is the line between two transformer reactances to ground.

(ii) L-L fault at q

Motors in parallel: positive 0.05∥0.05=0.0250.05\|0.05 = 0.025, negative 0.06∥0.06=0.030.06\|0.06 = 0.03.

Z1=j(0.1+0.07) ∥ j(0.1+0.08+0.025)=j0.17∥j0.205=j0.0929 puZ2=j(0.12+0.07) ∥ j(0.1+0.08+0.03)=j0.19∥j0.21=j0.0998 pu\begin{aligned} Z_1 &= j(0.1+0.07)\ \|\ j(0.1+0.08+0.025) = j0.17 \| j0.205 = j0.0929\ \text{pu} \\ Z_2 &= j(0.12+0.07)\ \|\ j(0.1+0.08+0.03) = j0.19 \| j0.21 = j0.0998\ \text{pu} \end{aligned}

Sequence currents (Ia0=0I_{a0} = 0):

Ia1=−Ia2=1j(0.0929+0.0998)=1j0.1927=−j5.190 puI_{a1} = -I_{a2} = \frac{1}{j(0.0929+0.0998)} = \frac{1}{j0.1927} = -j5.190\ \text{pu}

Fault current:

Ib=−j3Ia1=−8.989 puIc=−Ib=8.989 pu\begin{aligned} I_b &= -j\sqrt3 I_{a1} = -8.989\ \text{pu} \\ I_c &= -I_b = 8.989\ \text{pu} \end{aligned}

Answer: fault current for L-L fault at q = 8.99 pu (in phases b and c, opposite in sign; Ia=0I_a = 0). The zero-sequence network does not take part in an L-L fault.