SLG fault at mid-line through 4.033 Ω

Short answer

On 100 MVA, 110 kV line base, pre-fault voltage 1.047 pu, Thevenin impedances Z1=j0.1624, Z2=j0.1449, Z0=j0.1562 pu and 3Rf=0.1 pu give sequence current 2.208 pu; fault current = 3 × I_a0 = 6.62 pu = 3.48 kA.

Two alternators are operating in parallel and supplying a synchronous motor which is receiving 60 MW power at 0.8 pf (lag) at 6 kV. Single line diagram for the system and its data are given below. Compute the fault current when a single line to ground fault occurs at the middle of the line through a fault resistance of 4.033 ohm. Data: G1 & G2: 11 kV, 100 MVA, xg1 = 0.20 pu, xg2 = xg0 = 0.10 pu; T1: 180 MVA, 11.5/115 kV, xT1 = 0.10 pu; T2: 170 MVA, 6.6/115 kV, xT2 = 0.10 pu; M: 6.3 kV, 160 MVA, xM1 = xM2 = 0.30 pu, xM0 = 0.10 pu; Line: xLINE1 = xLINE2 = 30.25 ohm, xLINE0 = 60.5 ohm. [Figure: G1 and G2 (star, grounded) in parallel on a bus - T1 - line - T2 - motor M (star, grounded)]

Assumptions: the figure does not mark transformer windings, so the usual arrangement is taken: T1 and T2 are Δ on the machine side and star-grounded on the 115 kV line side. Then the machine zero-sequence reactances are isolated by the deltas. Base: 100 MVA, 11 kV in the generator circuit.

Base voltages and per-unit values

Vb,line=11×11511.5=110 kV,Zb,line=1102100=121 ΩVb,motor=110×6.6115=6.313 kV\begin{aligned} V_{b,line} &= 11 \times \frac{115}{11.5} = 110\ \text{kV}, \quad Z_{b,line} = \frac{110^2}{100} = 121\ \Omega \\ V_{b,motor} &= 110 \times \frac{6.6}{115} = 6.313\ \text{kV} \end{aligned}
ElementCalculationpu
G1 ∥ G2, X1X_10.2∥0.20.2 \| 0.20.10
G1 ∥ G2, X2X_20.1∥0.10.1 \| 0.10.05
T10.1×100180×(11.511)20.1 \times \frac{100}{180}\times(\frac{11.5}{11})^20.0607
Line X1=X2X_1 = X_230.25/12130.25/1210.25
Line X0X_060.5/12160.5/1210.50
T20.1×100170×(6.66.313)20.1 \times \frac{100}{170}\times(\frac{6.6}{6.313})^20.0643
Motor X1=X2X_1 = X_20.3×100160×(6.36.313)20.3 \times \frac{100}{160}\times(\frac{6.3}{6.313})^20.1867
Fault resistance RfR_f4.033/1214.033/1210.0333

Pre-fault voltage at the middle of the line

Motor voltage Vm=6/6.313=0.9504∠0∘V_m = 6/6.313 = 0.9504\angle0^\circ pu (reference). Motor input S=60/0.8=75S = 60/0.8 = 75 MVA =0.75= 0.75 pu. Half of the line is Xline/2=0.125X_{line}/2 = 0.125 pu.

IL=0.750.9504∠−36.87∘=0.7891∠−36.87∘ puVf=Vm+IL⋅j(XT2+Xline/2)=0.9504+0.7891∠−36.87∘×j(0.0643+0.125)=0.9504+0.7891∠−36.87∘×j0.1893=1.0469∠6.55∘ pu\begin{aligned} I_L &= \frac{0.75}{0.9504}\angle{-36.87^\circ} = 0.7891\angle{-36.87^\circ}\ \text{pu} \\ V_f &= V_m + I_L \cdot j(X_{T2} + X_{line}/2) = 0.9504 + 0.7891\angle{-36.87^\circ} \times j(0.0643 + 0.125) \\ &= 0.9504 + 0.7891\angle{-36.87^\circ} \times j0.1893 = 1.0469\angle{6.55^\circ}\ \text{pu} \end{aligned}

Thevenin impedances at the fault point (mid-line)

Z1=j(0.10+0.0607+0.125) ∥ j(0.125+0.0643+0.1867)=j0.2857∥j0.3760=j0.1624 puZ2=j(0.05+0.0607+0.125) ∥ j0.3760=j0.2357∥j0.3760=j0.1449 puZ0=j(0.0607+0.25) ∥ j(0.0643+0.25)=j0.3107∥j0.3143=j0.1562 pu\begin{aligned} Z_1 &= j(0.10 + 0.0607 + 0.125)\ \|\ j(0.125 + 0.0643 + 0.1867) = j0.2857 \| j0.3760 = j0.1624\ \text{pu} \\ Z_2 &= j(0.05 + 0.0607 + 0.125)\ \|\ j0.3760 = j0.2357 \| j0.3760 = j0.1449\ \text{pu} \\ Z_0 &= j(0.0607 + 0.25)\ \|\ j(0.0643 + 0.25) = j0.3107 \| j0.3143 = j0.1562\ \text{pu} \end{aligned}

(Zero sequence: each half of the line, X0/2=0.25X_0/2 = 0.25, goes to ground through the grounded star of its transformer.)

Fault current (sequence networks in series with 3Rf3R_f)

Ia0=Ia1=Ia2=VfZ1+Z2+Z0+3Rf=1.0469∠6.55∘0.1+j0.4635=2.208∠−71.27∘ puIf=3Ia0=6.624∠−71.27∘ pu\begin{aligned} I_{a0} = I_{a1} = I_{a2} &= \frac{V_f}{Z_1+Z_2+Z_0+3R_f} = \frac{1.0469\angle{6.55^\circ}}{0.1 + j0.4635} \\ &= 2.208\angle{-71.27^\circ}\ \text{pu} \\ I_f &= 3I_{a0} = 6.624\angle{-71.27^\circ}\ \text{pu} \end{aligned}

Base current on the line:

Ibase=100×1063×110×103=524.9 AI_{base} = \frac{100\times10^6}{\sqrt3 \times 110\times10^3} = 524.9\ \text{A} ∣If∣=6.624×524.9=3477 A|I_f| = 6.624 \times 524.9 = 3477\ \text{A}

Answer: SLG fault current ≈ 6.62 pu ≈ 3.48 kA (angle measured from the motor terminal voltage).

Note: 3Rf=0.13R_f = 0.1 pu adds resistance in series, so it both reduces the current and makes it lag by less than 90°.

✓ Answer checked by Claude Sonnet 5.5