SLG fault at mid-line through 4.033 Ω
Short answer
On 100 MVA, 110 kV line base, pre-fault voltage 1.047 pu, Thevenin impedances Z1=j0.1624, Z2=j0.1449, Z0=j0.1562 pu and 3Rf=0.1 pu give sequence current 2.208 pu; fault current = 3 × I_a0 = 6.62 pu = 3.48 kA.
Two alternators are operating in parallel and supplying a synchronous motor which is receiving 60 MW power at 0.8 pf (lag) at 6 kV. Single line diagram for the system and its data are given below. Compute the fault current when a single line to ground fault occurs at the middle of the line through a fault resistance of 4.033 ohm. Data: G1 & G2: 11 kV, 100 MVA, xg1 = 0.20 pu, xg2 = xg0 = 0.10 pu; T1: 180 MVA, 11.5/115 kV, xT1 = 0.10 pu; T2: 170 MVA, 6.6/115 kV, xT2 = 0.10 pu; M: 6.3 kV, 160 MVA, xM1 = xM2 = 0.30 pu, xM0 = 0.10 pu; Line: xLINE1 = xLINE2 = 30.25 ohm, xLINE0 = 60.5 ohm. [Figure: G1 and G2 (star, grounded) in parallel on a bus - T1 - line - T2 - motor M (star, grounded)]
Assumptions: the figure does not mark transformer windings, so the usual arrangement is taken: T1 and T2 are Δ on the machine side and star-grounded on the 115 kV line side. Then the machine zero-sequence reactances are isolated by the deltas. Base: 100 MVA, 11 kV in the generator circuit.
Base voltages and per-unit values
| Element | Calculation | pu |
|---|---|---|
| G1 ∥ G2, | 0.10 | |
| G1 ∥ G2, | 0.05 | |
| T1 | 0.0607 | |
| Line | 0.25 | |
| Line | 0.50 | |
| T2 | 0.0643 | |
| Motor | 0.1867 | |
| Fault resistance | 0.0333 |
Pre-fault voltage at the middle of the line
Motor voltage pu (reference). Motor input MVA pu. Half of the line is pu.
Thevenin impedances at the fault point (mid-line)
(Zero sequence: each half of the line, , goes to ground through the grounded star of its transformer.)
Fault current (sequence networks in series with )
Base current on the line:
Answer: SLG fault current ≈ 6.62 pu ≈ 3.48 kA (angle measured from the motor terminal voltage).
Note: pu adds resistance in series, so it both reduces the current and makes it lag by less than 90°.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault on bus with three alternators · Power System Analysis II, chapter 5
- Mid-line fault cleared at 60°, E = 1.04 · Power System Analysis II, chapter 6
- Mid-line fault, cleared at 60° · Power System Analysis II, chapter 6
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.95 pf · Power System Analysis I, chapter 5
- Fault current: two 500 kVA alternators · Power Plant Equipment, chapter 4
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3