Fault current: two 500 kVA alternators

Short answer

Using ohmic values, each generator reactance is 36.3 Ω; with 20 Ω feeder, total is 38.15 Ω, giving 166.47 A fault current, 83.24 A per alternator. With 10 Ω between A and B, total is 40.347 Ω, giving 157.40 A; G1 supplies 69.17 A and G2 supplies 88.23 A.

Below figure shows two Alternators operating in parallel. [Figure: G1 500 kVA, X1 = 15%, connected through a breaker to point A; G2 500 kVA, X2 = 15%, connected through a breaker to point C; points A, B, C lie on the 11 kV busbar; the feeder leaves from point B through a breaker and a reactor X = 20 ohms, with a 3 phase to ground fault on the feeder] (i) Calculate the fault current in outgoing feeder and fault current supplied by each alternator. (ii) If a reactor of 10 ohm is connected between point A and point B, calculate new fault current in outgoing feeder and fault current supplied by each alternator.

Work in ohms. Phase voltage Vph=11000/3=6350.85V_{ph} = 11000/\sqrt3 = 6350.85 V, and If=Vph/XtotalI_f = V_{ph}/X_{total}.

Zbase=1120.5=242 ΩXG1=XG2=0.15×242=36.3 Ω\begin{aligned} Z_{base} &= \frac{11^2}{0.5} = 242\ \Omega \\ X_{G1} = X_{G2} &= 0.15\times242 = 36.3\ \Omega \end{aligned}
   G1 500kVA        G2 500kVA
    15%              15%
     |                |
    CB               CB
     |                |
  ===A==[10]===B======C=== 11 kV
              |   ([10] only in part ii)
             CB
              |
            X=20 ohm
              |
              F

(i) Without reactor between A and B

Xpar=36.32=18.15 ΩXtotal=18.15+20=38.15 ΩIf=6350.8538.15=166.47 A\begin{aligned} X_{par} &= \frac{36.3}{2} = 18.15\ \Omega \\ X_{total} &= 18.15 + 20 = 38.15\ \Omega \\ I_f &= \frac{6350.85}{38.15} = 166.47\ \text{A} \end{aligned}

Each alternator supplies 166.47/2=83.24166.47/2 = 83.24 A.

(ii) With 10 Ω between A and B

XG1,path=36.3+10=46.3 ΩXpar=46.3×36.346.3+36.3=20.347 ΩXtotal=20.347+20=40.347 ΩIf=6350.8540.347=157.40 A\begin{aligned} X_{G1,path} &= 36.3 + 10 = 46.3\ \Omega \\ X_{par} &= \frac{46.3\times36.3}{46.3+36.3} = 20.347\ \Omega \\ X_{total} &= 20.347 + 20 = 40.347\ \Omega \\ I_f &= \frac{6350.85}{40.347} = 157.40\ \text{A} \end{aligned}

Sharing (inversely as path reactance):

IG1=157.40×36.382.6=69.17 AIG2=157.40×46.382.6=88.23 A\begin{aligned} I_{G1} &= 157.40\times\frac{36.3}{82.6} = 69.17\ \text{A} \\ I_{G2} &= 157.40\times\frac{46.3}{82.6} = 88.23\ \text{A} \end{aligned}

Answer: (i) IfI_f = 166.47 A, each alternator 83.24 A. (ii) IfI_f = 157.40 A; G1 supplies 69.17 A, G2 supplies 88.23 A.