- 2069 Chaitra · 8 marks
Fault current: two 50 MW generators, reactor inductance
Short answer
On a 50 MVA, 11 kV base, the feeder fault current is 2895 A. To reduce fault current by 40%, add a series reactor of 1.462 ohm, which is 4.65 mH at 50 Hz.
Figure below shows the single line diagram of parallel operated generators. Their ratings are: G1: capacity = 50 MW, 11kV, X1 = 0.16 pu based on its rating; G2: capacity = 50MW, 11kV, X2 = 0.16 pu based on its rating; Xl = 2 ohms. [Figure: G1 (through X1) and G2 (through X2), both star-grounded, connected to a common busbar; the feeder leaves the busbar through Xl] Calculate the fault current in the feeder during 3 phases to ground fault on the feeder. Calculate the value of inductance (in mH) of the reactor to be connected in series with Xl so that the fault current decreases by 40%.
Ratings in MW are taken as MVA (unity power factor). Fault current ; ohms to pu: .
Base: 50 MVA, 11 kV; ; .
G1 50MW,0.16 G2 50MW,0.16
| |
====+======+=======+==== 11 kV
|
Xl=2 ohm + new L
|
F
Fault current
(Fault MVA MVA.)
Reactor for 40 % reduction in fault current
New A, so the total reactance must become :
Answer: ≈ 2895 A; series reactor ≈ 1.462 Ω, i.e. L ≈ 4.65 mH (fault current falls to about 1737 A).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault current: four 1600 kVA generators · Power Plant Equipment, chapter 4
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×
- Fault level: two 50 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: two generators, two motors, j50 Ω line · Power System Analysis I, chapter 3
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- HV bus fault and limiting reactor · Power System Analysis II, chapter 3