- 2074 Chaitra · 14 marks
HV bus fault and limiting reactor
Short answer
On 30 MVA base, Thevenin reactance at HV bus is 0.33 pu. Fault level is 90.9 MVA, fault current 397.6 A at 132 kV. To reduce fault level by 25% to 68.2 MVA, add a reactor of 0.393 pu (228 Ω/phase) in series with T2 secondary.
Figure below shows a three-phase power system. (i) Calculate the short circuit MVA and the fault current when a 3-phase balanced short-circuit fault occurs at the High Voltage (HV) bus. (ii) Calculate the ohmic value of reactor 'X' to be placed on the secondary side of transformer 'T2' to limit the Fault Level to by 25%. Assume the system data as under: Generators: G1: 20 MVA, 11 kV, XG1 = 50%; G2: 30 MVA, 11 kV, XG2 = 50%. Transformers: T1: 20 MVA, 11/132 kV, XT1 = 5%; T2: 30 MVA, 11/132 kV, XT2 = 5%. [Figure: G1-T1 and G2-T2 both connected to the HV bus, which supplies a load; fault on the HV bus]
Base: 30 MVA, 11 kV / 132 kV. Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation). The load on the HV bus is neglected.
Per-unit reactances (30 MVA base)
| Element | Calculation | pu |
|---|---|---|
| G1 | 0.75 | |
| T1 | 0.075 | |
| G2 | 0.50 (already on 30 MVA) | 0.50 |
| T2 | 0.05 | 0.05 |
G1--j0.75--T1 j0.075--+
+-- HV bus (F)
G2--j0.50--T2 j0.05--[X]--+
(i) Fault at the HV bus
(ii) Reactor to reduce the fault level by 25%
"Limit the fault level by 25%" is read as reducing it by 25%, i.e. to 75% of the value above. (Reducing it to 25% is impossible here, because the G1 branch alone gives MVA, which is 40% of the present level.)
With reactor (pu) in series with T2 on its 132 kV (secondary) side:
In ohms on the 132 kV side, :
Answer: (i) SC MVA MVA, fault current A at 132 kV. (ii) A reactor of about 228 Ω per phase (0.393 pu on 30 MVA) on the 132 kV side of T2 reduces the fault level to 68.2 MVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Short circuit at load B (ohmic data) · Power System Analysis II, chapter 3
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- SLG fault on bus with three alternators · Power System Analysis II, chapter 5
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4