HV bus fault and limiting reactor

Short answer

On 30 MVA base, Thevenin reactance at HV bus is 0.33 pu. Fault level is 90.9 MVA, fault current 397.6 A at 132 kV. To reduce fault level by 25% to 68.2 MVA, add a reactor of 0.393 pu (228 Ω/phase) in series with T2 secondary.

Figure below shows a three-phase power system. (i) Calculate the short circuit MVA and the fault current when a 3-phase balanced short-circuit fault occurs at the High Voltage (HV) bus. (ii) Calculate the ohmic value of reactor 'X' to be placed on the secondary side of transformer 'T2' to limit the Fault Level to by 25%. Assume the system data as under: Generators: G1: 20 MVA, 11 kV, XG1 = 50%; G2: 30 MVA, 11 kV, XG2 = 50%. Transformers: T1: 20 MVA, 11/132 kV, XT1 = 5%; T2: 30 MVA, 11/132 kV, XT2 = 5%. [Figure: G1-T1 and G2-T2 both connected to the HV bus, which supplies a load; fault on the HV bus]

Base: 30 MVA, 11 kV / 132 kV. Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation). The load on the HV bus is neglected.

Per-unit reactances (30 MVA base)

ElementCalculationpu
G10.50×30/200.50 \times 30/200.75
T10.05×30/200.05 \times 30/200.075
G20.50 (already on 30 MVA)0.50
T20.050.05
 G1--j0.75--T1 j0.075--+
                       +-- HV bus (F)
 G2--j0.50--T2 j0.05--[X]--+

(i) Fault at the HV bus

X1=0.75+0.075=0.825,X2=0.50+0.05=0.55Xth=0.825×0.550.825+0.55=0.33 puSC MVA=300.33=90.91 MVAIbase=30×1063×132×103=131.22 AIf=10.33×131.22=3.0303×131.22=397.6 A\begin{aligned} X_1 &= 0.75 + 0.075 = 0.825, \quad X_2 = 0.50 + 0.05 = 0.55 \\ X_{th} &= \frac{0.825 \times 0.55}{0.825 + 0.55} = 0.33\ \text{pu} \\ \text{SC MVA} &= \frac{30}{0.33} = 90.91\ \text{MVA} \\ I_{base} &= \frac{30 \times 10^6}{\sqrt{3} \times 132 \times 10^3} = 131.22\ \text{A} \\ I_f &= \frac{1}{0.33} \times 131.22 = 3.0303 \times 131.22 = 397.6\ \text{A} \end{aligned}

(ii) Reactor to reduce the fault level by 25%

"Limit the fault level by 25%" is read as reducing it by 25%, i.e. to 75% of the value above. (Reducing it to 25% is impossible here, because the G1 branch alone gives 30/0.825=36.430/0.825 = 36.4 MVA, which is 40% of the present level.)

New fault level=0.75×90.91=68.18 MVAXth,new=3068.18=0.44 pu\begin{aligned} \text{New fault level} &= 0.75 \times 90.91 = 68.18\ \text{MVA} \\ X_{th,new} &= \frac{30}{68.18} = 0.44\ \text{pu} \end{aligned}

With reactor XX (pu) in series with T2 on its 132 kV (secondary) side:

10.44=10.825+10.55+X10.55+X=2.2727−1.2121=1.06060.55+X=0.9429X=0.3929 pu\begin{aligned} \frac{1}{0.44} &= \frac{1}{0.825} + \frac{1}{0.55 + X} \\ \frac{1}{0.55 + X} &= 2.2727 - 1.2121 = 1.0606 \\ 0.55 + X &= 0.9429 \\ X &= 0.3929\ \text{pu} \end{aligned}

In ohms on the 132 kV side, Zbase=1322/30=580.8 ΩZ_{base} = 132^2/30 = 580.8\ \Omega:

X=0.3929×580.8=228.2 ΩX = 0.3929 \times 580.8 = 228.2\ \Omega

Answer: (i) SC MVA =90.91= 90.91 MVA, fault current ≈397.6\approx 397.6 A at 132 kV. (ii) A reactor of about 228 Ω per phase (0.393 pu on 30 MVA) on the 132 kV side of T2 reduces the fault level to 68.2 MVA.