Short circuit at load B (ohmic data)
Short answer
On 30 MVA, 3.81 kV base, the short-circuit MVA is 148.3 MVA and the short-circuit current is 22.48 kA at the load B bus.
Calculate short circuit MVA and short circuit current when three phase fault occur at load B of the following single line diagram. [Figure: G1 20 MVA, 6.6 kV, X = 0.655 ohm and G2 10 MVA, 6.6 kV, X = 1.31 ohm on a common 6.6 kV bus which also supplies Load A (15 MVA, 6.6 kV, pf = 0.9 lag); transformer Tr-1 30 MVA, 6.6/66 kV, X = 14.52 ohm (referred to HV side); transmission line x = 17.4 ohm; transformer Tr-2 30 MVA, 66/3.81 kV, X = 14.52 ohm (referred to HV side); 3.81 kV bus with generator G3 (30 MVA, 3.81 kV, X = 0.1452 ohm) and Load B (30 MW, 3.81 kV, pf = 0.9 lag)]
Base: 30 MVA, with base voltages 6.6 kV, 66 kV and 3.81 kV in the three zones. Loads are neglected and the pre-fault voltage is 1.0 pu (usual for fault level), so all generator EMFs are 1 pu. The fault is on the 3.81 kV bus of load B.
Base impedances
Per-unit reactances
| Element | Ohms | Zone base (Ω) | pu |
|---|---|---|---|
| G1 | 0.655 | 1.452 | 0.4511 |
| G2 | 1.31 | 1.452 | 0.9022 |
| Tr-1 (HV) | 14.52 | 145.2 | 0.1000 |
| Line | 17.4 | 145.2 | 0.1198 |
| Tr-2 (HV) | 14.52 | 145.2 | 0.1000 |
| G3 | 0.1452 | 0.48387 | 0.3001 |
G1--+
+--Tr1--line--Tr2--+-- 3.81 kV bus (F, load B)
G2--+ |
G3
Thevenin reactance at load B
Short-circuit MVA and current
Answer: short-circuit MVA MVA, short-circuit current kA at 3.81 kV.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- HV bus fault and limiting reactor · Power System Analysis II, chapter 3
- Fault at far end of 33 kV line · Power System Analysis II, chapter 3
- SLG fault on bus with three alternators · Power System Analysis II, chapter 5
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3