Short circuit at load B (ohmic data)

Short answer

On 30 MVA, 3.81 kV base, the short-circuit MVA is 148.3 MVA and the short-circuit current is 22.48 kA at the load B bus.

Calculate short circuit MVA and short circuit current when three phase fault occur at load B of the following single line diagram. [Figure: G1 20 MVA, 6.6 kV, X = 0.655 ohm and G2 10 MVA, 6.6 kV, X = 1.31 ohm on a common 6.6 kV bus which also supplies Load A (15 MVA, 6.6 kV, pf = 0.9 lag); transformer Tr-1 30 MVA, 6.6/66 kV, X = 14.52 ohm (referred to HV side); transmission line x = 17.4 ohm; transformer Tr-2 30 MVA, 66/3.81 kV, X = 14.52 ohm (referred to HV side); 3.81 kV bus with generator G3 (30 MVA, 3.81 kV, X = 0.1452 ohm) and Load B (30 MW, 3.81 kV, pf = 0.9 lag)]

Base: 30 MVA, with base voltages 6.6 kV, 66 kV and 3.81 kV in the three zones. Loads are neglected and the pre-fault voltage is 1.0 pu (usual for fault level), so all generator EMFs are 1 pu. The fault is on the 3.81 kV bus of load B.

Base impedances

Zb,6.6=6.6230=1.452 ΩZb,66=66230=145.2 ΩZb,3.81=3.81230=0.48387 Ω\begin{aligned} Z_{b,6.6} &= \frac{6.6^2}{30} = 1.452\ \Omega \\ Z_{b,66} &= \frac{66^2}{30} = 145.2\ \Omega \\ Z_{b,3.81} &= \frac{3.81^2}{30} = 0.48387\ \Omega \end{aligned}

Per-unit reactances

ElementOhmsZone base (Ω)pu
G10.6551.4520.4511
G21.311.4520.9022
Tr-1 (HV)14.52145.20.1000
Line17.4145.20.1198
Tr-2 (HV)14.52145.20.1000
G30.14520.483870.3001
 G1--+
     +--Tr1--line--Tr2--+-- 3.81 kV bus (F, load B)
 G2--+                  |
                        G3

Thevenin reactance at load B

XG1∥G2=0.4511×0.90220.4511+0.9022=0.3007Xleft=0.3007+0.1000+0.1198+0.1000=0.6206Xth=0.6206×0.30010.6206+0.3001=0.2023 pu\begin{aligned} X_{G1\|G2} &= \frac{0.4511 \times 0.9022}{0.4511 + 0.9022} = 0.3007 \\ X_{left} &= 0.3007 + 0.1000 + 0.1198 + 0.1000 = 0.6206 \\ X_{th} &= \frac{0.6206 \times 0.3001}{0.6206 + 0.3001} = 0.2023\ \text{pu} \end{aligned}

Short-circuit MVA and current

SC MVA=300.2023=148.32 MVAIbase=30×1063×3.81×103=4546.1 AIf=10.2023×4546.1=4.9439×4546.1=22475 A\begin{aligned} \text{SC MVA} &= \frac{30}{0.2023} = 148.32\ \text{MVA} \\ I_{base} &= \frac{30 \times 10^6}{\sqrt{3} \times 3.81 \times 10^3} = 4546.1\ \text{A} \\ I_f &= \frac{1}{0.2023} \times 4546.1 = 4.9439 \times 4546.1 = 22475\ \text{A} \end{aligned}

Answer: short-circuit MVA ≈148.3\approx 148.3 MVA, short-circuit current ≈22.48\approx 22.48 kA at 3.81 kV.