- 2078 Bhadra · 8 marks
Fault at far end of 33 kV line
Short answer
On 30 MVA, 33 kV base with pre-fault voltage 1 pu and neglecting load current, the three-phase fault current at the far end is 1605 A, and fault level is 91.8 MVA.
For the system shown in figure below, determine the fault current, fault level if three phase balanced short circuit fault occurs at the far end F. [Figure: G1 11 kV, 20 MVA, 15% and G2 11 kV, 10 MVA, 10% on a common 11 kV bus; transformer 30 MVA, 5%, ratio 1:3 (to 33 kV); line of (3 + j5) Ω at 33 kV to the fault point F at the far end]
Base: 30 MVA (transformer rating), 11 kV on the generator side and 33 kV on the line side (ratio 1:3). Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation).
Per-unit impedances
| Element | Calculation | pu |
|---|---|---|
| G1 | 0.225 | |
| G2 | 0.300 | |
| Transformer | 5% on 30 MVA | 0.05 |
| Line | 0.0826 + j0.1377 |
at 33 kV .
E=1--jX_G1--+
+--j0.05--(3+j5 ohm)--F
E=1--jX_G2--+
Total impedance up to F
Fault current and fault level
Answer: fault current A at 33 kV, fault level MVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4