- 2079 Bhadra · 5 marks
Fault level: two 25 MVA generators, 50% reduction
Short answer
Fault level is 250 MVA. To halve it, double the existing 0.1 pu reactance to 0.2 pu; add a feeder reactor of 0.1 pu (0.484 Ω), giving 125 MVA.
For the system shown in figure below, calculate the fault level in MVA at out going feeder for a three phase to ground fault on this feeder. Calculate the value of reactance to be connected in the feeder in order to reduce the fault level by 50%. [Figure: G1 25 MVA, 11 kV, E = 1 pu, X1 = 0.15 pu and G2 25 MVA, 11 kV, E = 1 pu, X2 = 0.3 pu connected to a common busbar; outgoing feeder through a C.B. with fault point 'F' on the feeder]
Fault MVA , with pu. Feeder reactance (not given) is taken as zero before adding the reactor.
Base: 25 MVA, 11 kV; .
G1 25MVA,0.15 G2 25MVA,0.3
| |
=====+=======+=======+==== 11 kV
|
C.B.--[X]-- F
Fault level
Reactance for 50 % reduction
New fault MVA = 125 MVA.
Answer: Fault level = 250 MVA; feeder reactance = 0.1 pu = 0.484 Ω (fault level becomes 125 MVA).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault level: two 50 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Feeder reactor: 40 and 30 MVA, 50% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: three generators, two 220 kV lines · Power System Analysis I, chapter 3