Fault level: two 40 MVA generators, 2 Ω feeder
Short answer
On 40 MVA, 11 kV base, parallel generator reactance is 0.02222 pu, feeder 2 Ω = 0.66116 pu, total 0.68338 pu. Fault level = 40/0.68338 = 58.53 MVA, fault current ≈ 3072 A. To reduce by 40% (to 35.12 MVA), add series reactor of 1.378 Ω (0.4556 pu).
Two generators each of capacities 40 MVA, 11 kV having their sub transient reactance of 5% and 4% respectively operating in parallel and supplying to a common load by single feeder of reactance 2 Ω. Calculate the fault level when 3-phase to ground fault occurs on the outgoing feeder. Also calculate the value of reactor to be connected in series with 2 Ω reactor to reduce the fault level by 40 %.
Work in per unit on a common base. Fault level and a reactor of ohms has .
Base: 40 MVA, 11 kV.
G1 40MVA,5% G2 40MVA,4%
| |
====+=====+=======+==== 11 kV bus
|
X=2 ohm feeder
|
F (3-ph fault)
Fault level
Fault current: , so .
Reactor to reduce fault level by 40 %
New fault level MVA.
Answer: Fault level = 58.53 MVA (about 3.07 kA). A reactor of about 1.378 Ω (0.4556 pu on 40 MVA) in series with the 2 Ω feeder reduces it by 40 % to 35.12 MVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Feeder reactor: 40 and 30 MVA, 50% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Feeder reactor: 40 and 30 MVA, 40% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Fault level: two 50 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4
- Fault level: adding a third generator · Power Plant Equipment, chapter 4
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3