Short answer

On 40 MVA, 11 kV base, parallel generator reactance is 0.02222 pu, feeder 2 Ω = 0.66116 pu, total 0.68338 pu. Fault level = 40/0.68338 = 58.53 MVA, fault current ≈ 3072 A. To reduce by 40% (to 35.12 MVA), add series reactor of 1.378 Ω (0.4556 pu).

Two generators each of capacities 40 MVA, 11 kV having their sub transient reactance of 5% and 4% respectively operating in parallel and supplying to a common load by single feeder of reactance 2 Ω. Calculate the fault level when 3-phase to ground fault occurs on the outgoing feeder. Also calculate the value of reactor to be connected in series with 2 Ω reactor to reduce the fault level by 40 %.

Work in per unit on a common base. Fault level =Base MVAXpu= \dfrac{\text{Base MVA}}{X_{pu}} and a reactor of XX ohms has Xpu=X⋅MVAbkVb2X_{pu} = X\cdot\dfrac{\text{MVA}_b}{\text{kV}_b^2}.

Base: 40 MVA, 11 kV.

Zbase=11240=3.025 ΩZ_{base} = \frac{11^2}{40} = 3.025\ \Omega
 G1 40MVA,5%   G2 40MVA,4%
     |             |
 ====+=====+=======+==== 11 kV bus
           |
          X=2 ohm feeder
           |
           F  (3-ph fault)

Fault level

XG1=0.05 pu,XG2=0.04 puXG1∥XG2=0.05×0.040.05+0.04=0.02222 puXfeeder=23.025=0.66116 puXeq=0.02222+0.66116=0.68338 puFault MVA=400.68338=58.53 MVA\begin{aligned} X_{G1} &= 0.05\ \text{pu},\quad X_{G2} = 0.04\ \text{pu} \\ X_{G1}\parallel X_{G2} &= \frac{0.05\times0.04}{0.05+0.04} = 0.02222\ \text{pu} \\ X_{feeder} &= \frac{2}{3.025} = 0.66116\ \text{pu} \\ X_{eq} &= 0.02222 + 0.66116 = 0.68338\ \text{pu} \\ \text{Fault MVA} &= \frac{40}{0.68338} = 58.53\ \text{MVA} \end{aligned}

Fault current: Ibase=40×1063×11×103=2099.5 AI_{base} = \dfrac{40\times10^6}{\sqrt3\times 11\times10^3} = 2099.5\ \text{A}, so If=2099.5/0.68338=3072 AI_f = 2099.5/0.68338 = 3072\ \text{A}.

Reactor to reduce fault level by 40 %

New fault level =0.6×58.53=35.12= 0.6\times58.53 = 35.12 MVA.

Xeq,new=4035.12=0.683380.6=1.13897 puXadded=1.13897−0.68338=0.45559 puXadded(Ω)=0.45559×3.025=1.378 Ω\begin{aligned} X_{eq,new} &= \frac{40}{35.12} = \frac{0.68338}{0.6} = 1.13897\ \text{pu} \\ X_{added} &= 1.13897 - 0.68338 = 0.45559\ \text{pu} \\ X_{added}(\Omega) &= 0.45559\times3.025 = 1.378\ \Omega \end{aligned}

Answer: Fault level = 58.53 MVA (about 3.07 kA). A reactor of about 1.378 Ω (0.4556 pu on 40 MVA) in series with the 2 Ω feeder reduces it by 40 % to 35.12 MVA.