Fault level: four 25 MVA generators, bus reactor

Short answer

On 25 MVA base, four 0.16 pu generators in parallel give equivalent reactance 0.04 pu, so fault level is 625 MVA. To reduce to 375 MVA, a bus-bar reactor between B and C must be 0.32 pu, about 1.549 Ω.

The figure below shows four identical generators, each rated 11 kV, 25 MVA and each having sub-transient reactance of 16% on its own rating. Find 3-ϕ fault level at one of the outgoing feeder. Also calculate the value of reactance to be connected in the bus bar between "B" and "C" so that fault level reduces by 40%. [Figure: four generators connected to a busbar at points A, B, C, D; outgoing feeders leave the busbar, with a 3-ϕ fault on the feeder between C and D]

All four generators are identical, so work on their own base. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}.

Base: 25 MVA, 11 kV; Xg=0.16X_g = 0.16 pu; Zbase=112/25=4.84 ΩZ_{base} = 11^2/25 = 4.84\ \Omega.

  G1      G2         G3      G4
  |       |          |       |
  A-------B---[X]----C-------D   bus
                         |
                         F (feeder between C and D)

Fault level without reactor

Xeq=0.164=0.04 puFault MVA=250.04=625 MVA\begin{aligned} X_{eq} &= \frac{0.16}{4} = 0.04\ \text{pu} \\ \text{Fault MVA} &= \frac{25}{0.04} = 625\ \text{MVA} \end{aligned}

(If=625/(3×11)=32.80I_f = 625/(\sqrt3\times11) = 32.80 kA.)

Reactor between B and C for 40 % reduction

New fault MVA =0.6×625=375= 0.6\times625 = 375 MVA, so Xeq,new=25/375=0.06667X_{eq,new} = 25/375 = 0.06667 pu.

With the reactor, G3 and G4 feed the fault directly (0.16∥0.16=0.080.16\parallel0.16 = 0.08 pu) and G1, G2 feed it through XX (0.08+X0.08 + X):

10.06667=10.08+10.08+X15=12.5+10.08+X0.08+X=0.4X=0.32 pu\begin{aligned} \frac{1}{0.06667} &= \frac{1}{0.08} + \frac{1}{0.08+X} \\ 15 &= 12.5 + \frac{1}{0.08+X} \\ 0.08 + X &= 0.4 \\ X &= 0.32\ \text{pu} \end{aligned} X(Ω)=0.32×4.84=1.549 ΩX(\Omega) = 0.32\times4.84 = 1.549\ \Omega

Answer: Fault level = 625 MVA; bus-bar reactor between B and C = 0.32 pu (32 %) on 25 MVA ≈ 1.549 Ω, giving 375 MVA.