- 2073 Shrawan · 5 marks
Fault level: four 25 MVA generators, bus reactor
Short answer
On 25 MVA base, four 0.16 pu generators in parallel give equivalent reactance 0.04 pu, so fault level is 625 MVA. To reduce to 375 MVA, a bus-bar reactor between B and C must be 0.32 pu, about 1.549 Ω.
The figure below shows four identical generators, each rated 11 kV, 25 MVA and each having sub-transient reactance of 16% on its own rating. Find 3-ϕ fault level at one of the outgoing feeder. Also calculate the value of reactance to be connected in the bus bar between "B" and "C" so that fault level reduces by 40%. [Figure: four generators connected to a busbar at points A, B, C, D; outgoing feeders leave the busbar, with a 3-ϕ fault on the feeder between C and D]
All four generators are identical, so work on their own base. Fault MVA .
Base: 25 MVA, 11 kV; pu; .
G1 G2 G3 G4
| | | |
A-------B---[X]----C-------D bus
|
F (feeder between C and D)
Fault level without reactor
( kA.)
Reactor between B and C for 40 % reduction
New fault MVA MVA, so pu.
With the reactor, G3 and G4 feed the fault directly ( pu) and G1, G2 feed it through ():
Answer: Fault level = 625 MVA; bus-bar reactor between B and C = 0.32 pu (32 %) on 25 MVA ≈ 1.549 Ω, giving 375 MVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault level: two 50 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- HV bus fault and limiting reactor · Power System Analysis II, chapter 3
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×