- Asked 2/24
- 2081 Bhadra · 8 marks
- 2083 Baishakh (new course) · 4+3 marks
Fault MVA at bus 5 with inductive lines
Short answer
On 100 MVA base, each source branch 0.25 pu, L2 and L3 0.0902 pu; L1 carries no current. Thevenin reactance at bus 5 = 0.1701 pu. Fault MVA = 588.0 MVA, fault current = 2.572 kA at 132 kV.
Figure below shows a power system network. Each alternator G1 and G2 are rated at 100 MVA, 11 kV and has a sub-transient reactance of 20%. Each of the transformer is rated at 100 MVA, 11/132 kV and has a leakage reactance of 5%. The line L1 of 1.2 mH/phase/km and a length of 100 km. Lines L2 and L3 have inductance of 1.0 mH/phase/km and has a length of 50 km each. Find the fault MVA and fault current for the fault at the bus 5 (point F). [Figure: G2 at bus 2 - T2 - bus 4; G1 at bus 1 - T1 - bus 3; L1 between buses 4 and 3; L2 from bus 4 to bus 5; L3 from bus 5 to bus 3; the fault F is at bus 5]
Base: 100 MVA, 11 kV (generator side), 132 kV (line side), Hz. Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation).
Per-unit reactances
- G1, G2: pu each (already on 100 MVA, 11 kV).
- T1, T2: pu each.
- So from each generator EMF to its 132 kV bus: pu.
Lines ():
Reactance diagram
E=1 E=1
| |
j0.25 (G1+T1) j0.25 (G2+T2)
| |
bus3 ------- L1 j0.216 ------- bus4
\ /
L3 j0.090 L2 j0.090
\ /
bus 5 (F)
Thevenin reactance at bus 5
Both generator EMFs are equal (1 pu), and the two halves of the network are identical (0.25 pu to each source, ). So buses 3 and 4 are always at the same potential and line L1 carries no current; it can be removed. The two paths (0.25 + 0.0902) are then in parallel:
(The same value is obtained as of the bus impedance matrix.)
Fault current and fault MVA
Answer: fault MVA MVA and fault current kA at 132 kV.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- L-G fault at bus 3, parallel lines · Power System Analysis II, chapter 5
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3