Fault MVA at bus 5 with inductive lines

Short answer

On 100 MVA base, each source branch 0.25 pu, L2 and L3 0.0902 pu; L1 carries no current. Thevenin reactance at bus 5 = 0.1701 pu. Fault MVA = 588.0 MVA, fault current = 2.572 kA at 132 kV.

Figure below shows a power system network. Each alternator G1 and G2 are rated at 100 MVA, 11 kV and has a sub-transient reactance of 20%. Each of the transformer is rated at 100 MVA, 11/132 kV and has a leakage reactance of 5%. The line L1 of 1.2 mH/phase/km and a length of 100 km. Lines L2 and L3 have inductance of 1.0 mH/phase/km and has a length of 50 km each. Find the fault MVA and fault current for the fault at the bus 5 (point F). [Figure: G2 at bus 2 - T2 - bus 4; G1 at bus 1 - T1 - bus 3; L1 between buses 4 and 3; L2 from bus 4 to bus 5; L3 from bus 5 to bus 3; the fault F is at bus 5]

Base: 100 MVA, 11 kV (generator side), 132 kV (line side), f=50f = 50 Hz. Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation).

Per-unit reactances

  • G1, G2: X′′=0.20X'' = 0.20 pu each (already on 100 MVA, 11 kV).
  • T1, T2: X=0.05X = 0.05 pu each.
  • So from each generator EMF to its 132 kV bus: 0.20+0.05=0.250.20 + 0.05 = 0.25 pu.

Lines (X=2πfLX = 2\pi fL):

Zbase=1322100=174.24 ΩXL1=2π(50)(1.2×10−3×100)=37.699 Ω=37.699174.24=0.2164 puXL2=XL3=2π(50)(1.0×10−3×50)=15.708 Ω=0.0902 pu\begin{aligned} Z_{base} &= \frac{132^2}{100} = 174.24\ \Omega \\ X_{L1} &= 2\pi(50)(1.2 \times 10^{-3} \times 100) = 37.699\ \Omega = \frac{37.699}{174.24} = 0.2164\ \text{pu} \\ X_{L2} = X_{L3} &= 2\pi(50)(1.0 \times 10^{-3} \times 50) = 15.708\ \Omega = 0.0902\ \text{pu} \end{aligned}

Reactance diagram

  E=1                         E=1
   |                           |
 j0.25 (G1+T1)               j0.25 (G2+T2)
   |                           |
 bus3 ------- L1 j0.216 ------- bus4
    \                         /
  L3 j0.090            L2 j0.090
       \                   /
            bus 5 (F)

Thevenin reactance at bus 5

Both generator EMFs are equal (1 pu), and the two halves of the network are identical (0.25 pu to each source, XL2=XL3X_{L2} = X_{L3}). So buses 3 and 4 are always at the same potential and line L1 carries no current; it can be removed. The two paths (0.25 + 0.0902) are then in parallel:

Xth=0.25+0.09022=0.1701 pu\begin{aligned} X_{th} &= \frac{0.25 + 0.0902}{2} = 0.1701\ \text{pu} \end{aligned}

(The same value is obtained as Z55Z_{55} of the bus impedance matrix.)

Fault current and fault MVA

If=10.1701=5.8797 puIbase=100×1063(132×103)=437.39 AIf=5.8797×437.39=2571.7 AFault MVA=1000.1701=587.97 MVA\begin{aligned} I_f &= \frac{1}{0.1701} = 5.8797\ \text{pu} \\ I_{base} &= \frac{100 \times 10^6}{\sqrt{3}(132 \times 10^3)} = 437.39\ \text{A} \\ I_f &= 5.8797 \times 437.39 = 2571.7\ \text{A} \\ \text{Fault MVA} &= \frac{100}{0.1701} = 587.97\ \text{MVA} \end{aligned}

Answer: fault MVA ≈588.0\approx 588.0 MVA and fault current ≈2.572\approx 2.572 kA at 132 kV.