L-G fault at bus 3, parallel lines

Short answer

Thevenin Z1=Z2=j0.1364 pu, Z0=j0.1766 pu at bus 3. For bolted L-G fault, sequence currents in series: Ia1 = -j2.2255 pu; fault current I_f = 3Ia0 = 6.676 pu = 1.75 kA at 220 kV.

Determine the Fault current when a line to ground fault occurs at Bus 3 as shown in figure below. G1, G2: 100 MVA, 11 kV, X1 = X2 = 15%, X0 = 5%, Xn = 6%; T1, T2: 100 MVA, 11 kV/220 kV, Xleak = 10%; L1, L2: X1 = X2 = 10%, X0 = 10% on a base of 100 MVA. [Figure: G1 (Y grounded through Xn) - bus 1 - T1 (Y grounded/Y grounded) - bus 2 - parallel lines L1 and L2 - bus 3 - T2 (Y grounded/Y grounded) - bus 4 - G2 (Y grounded through Xn)]

Base: 100 MVA; 11 kV on generator side, 220 kV on line side. All data are already on this base. Xn=0.06X_n = 0.06 pu for each generator. Pre-fault voltage E=1∠0∘E = 1\angle0^\circ pu, system unloaded.

Single line diagram

 G1        T1                 L1            T2        G2
 (~)--(1)--)(--(2)====================(3)--)(--(4)--(~)
  |       Yg Yg     ====== L2 =======      Yg Yg     |
 Xn                                                  Xn
 |                                                   |
gnd                      F (L-G at bus 3)           gnd

Per-unit reactances

ElementX1X_1X2X_2X0X_0
G1, G20.150.150.05 + 3(0.06) = 0.23
T1, T20.100.100.10
L1 ∥ L20.050.050.05

Positive sequence network

 E1-j0.15-(1)-j0.1-(2)-j0.05-(3)-j0.1-(4)-j0.15-E2
                            |
                            F
Z1=j(0.15+0.1+0.05) ∥ j(0.1+0.15)=j0.30 ∥ j0.25=j0.1364 puZ_1 = j(0.15+0.1+0.05)\ \|\ j(0.1+0.15) = j0.30\ \|\ j0.25 = j0.1364\ \text{pu}

Negative sequence network

Same as positive, without the sources:

Z2=j0.1364 puZ_2 = j0.1364\ \text{pu}

Zero sequence network

Both transformers are Yg–Yg, so zero-sequence current passes through them; generator neutrals are grounded through XnX_n, which appears as 3Xn3X_n.

 ref-j0.23-(1)-j0.1-(2)-j0.05-(3)-j0.1-(4)-j0.23-ref
                             |
                             F
Z0=j(0.23+0.1+0.05) ∥ j(0.1+0.23)=j0.38 ∥ j0.33=j0.1766 puZ_0 = j(0.23+0.1+0.05)\ \|\ j(0.1+0.23) = j0.38\ \|\ j0.33 = j0.1766\ \text{pu}

Fault current (L-G at bus 3, Zf=0Z_f = 0)

Sequence networks in series:

Ia1=Ia2=Ia0=EZ1+Z2+Z0=1j(0.1364+0.1364+0.1766)=1j0.4494=−j2.2255 puIf=3Ia0=−j6.676 pu\begin{aligned} I_{a1} = I_{a2} = I_{a0} &= \frac{E}{Z_1+Z_2+Z_0} = \frac{1}{j(0.1364+0.1364+0.1766)} = \frac{1}{j0.4494} = -j2.2255\ \text{pu} \\ I_f &= 3I_{a0} = -j6.676\ \text{pu} \end{aligned}

Base current at 220 kV:

Ibase=100×1063×220×103=262.43 AI_{base} = \frac{100\times10^6}{\sqrt3 \times 220\times10^3} = 262.43\ \text{A} If=6.676×262.43=1752 AI_f = 6.676 \times 262.43 = 1752\ \text{A}

Phase currents at the fault

  • Ia=If=6.676∠−90∘I_a = I_f = 6.676\angle{-90^\circ} pu =1.752= 1.752 kA
  • Ib=Ic=0I_b = I_c = 0 (healthy phases, unloaded system)

Fault MVA (for reference)

Fault MVA =∣If∣×= |I_f| \times base MVA (with Vf=1V_f = 1) =6.676×100=667.6= 6.676 \times 100 = 667.6 MVA.

Answer: L-G fault current at bus 3 ≈ 6.68 pu ≈ 1.75 kA.

Note: Z0Z_0 (0.1766) is larger than Z1Z_1 (0.1364) mainly because of the neutral reactances, so here the L-G current (6.68 pu) is less than the three-phase fault current (1/0.1364=7.331/0.1364 = 7.33 pu).

✓ Answer checked by Claude Sonnet 5.5