- 2078 Bhadra · 16 marks
L-G fault at bus 3, parallel lines
Short answer
Thevenin Z1=Z2=j0.1364 pu, Z0=j0.1766 pu at bus 3. For bolted L-G fault, sequence currents in series: Ia1 = -j2.2255 pu; fault current I_f = 3Ia0 = 6.676 pu = 1.75 kA at 220 kV.
Determine the Fault current when a line to ground fault occurs at Bus 3 as shown in figure below. G1, G2: 100 MVA, 11 kV, X1 = X2 = 15%, X0 = 5%, Xn = 6%; T1, T2: 100 MVA, 11 kV/220 kV, Xleak = 10%; L1, L2: X1 = X2 = 10%, X0 = 10% on a base of 100 MVA. [Figure: G1 (Y grounded through Xn) - bus 1 - T1 (Y grounded/Y grounded) - bus 2 - parallel lines L1 and L2 - bus 3 - T2 (Y grounded/Y grounded) - bus 4 - G2 (Y grounded through Xn)]
Base: 100 MVA; 11 kV on generator side, 220 kV on line side. All data are already on this base. pu for each generator. Pre-fault voltage pu, system unloaded.
Single line diagram
G1 T1 L1 T2 G2
(~)--(1)--)(--(2)====================(3)--)(--(4)--(~)
| Yg Yg ====== L2 ======= Yg Yg |
Xn Xn
| |
gnd F (L-G at bus 3) gnd
Per-unit reactances
| Element | |||
|---|---|---|---|
| G1, G2 | 0.15 | 0.15 | 0.05 + 3(0.06) = 0.23 |
| T1, T2 | 0.10 | 0.10 | 0.10 |
| L1 ∥ L2 | 0.05 | 0.05 | 0.05 |
Positive sequence network
E1-j0.15-(1)-j0.1-(2)-j0.05-(3)-j0.1-(4)-j0.15-E2
|
F
Negative sequence network
Same as positive, without the sources:
Zero sequence network
Both transformers are Yg–Yg, so zero-sequence current passes through them; generator neutrals are grounded through , which appears as .
ref-j0.23-(1)-j0.1-(2)-j0.05-(3)-j0.1-(4)-j0.23-ref
|
F
Fault current (L-G at bus 3, )
Sequence networks in series:
Base current at 220 kV:
Phase currents at the fault
- pu kA
- (healthy phases, unloaded system)
Fault MVA (for reference)
Fault MVA base MVA (with ) MVA.
Answer: L-G fault current at bus 3 ≈ 6.68 pu ≈ 1.75 kA.
Note: (0.1766) is larger than (0.1364) mainly because of the neutral reactances, so here the L-G current (6.68 pu) is less than the three-phase fault current ( pu).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- Reactance diagram: three generators, two 220 kV lines · Power System Analysis I, chapter 3
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- p.u. impedance diagram: G, T1, line, T2, M · Power System Analysis I, chapter 3