- 2081 Baisakh · 6 marks
Fault level: three generators, feeder reactor
Short answer
On 100 MVA base, G1: 0.5 pu, G2: 0.6667 pu, G3: 0.75 pu, parallel Xeq = 0.2069 pu. Fault level = 100/0.2069 = 483.33 MVA, fault current ≈ 25.37 kA. To reduce by 40% (to 290 MVA), series reactor needed = 0.1379 pu = 0.167 Ω.
The given figure shows three generators operating in parallel. Find the fault current and fault level if three phase to ground fault occurs in the outgoing feeder. What should be the value of feeder reactor to be added to reduce the fault level by 40%? [Figure: G1 20 MVA, 11 kV, X1 = 0.1 pu; G2 30 MVA, 11 kV, X2 = 0.2 pu; G3 40 MVA, 11 kV, X3 = 0.3 pu; all three connected to a common busbar (points A, B, C); an outgoing feeder from the busbar through a circuit breaker, with the fault point on the feeder beyond the C.B.]
Convert all reactances to one base, combine the three parallel generators, and use Fault MVA . The feeder reactance is not given, so it is taken as zero (fault just beyond the C.B.).
Base: 100 MVA, 11 kV. ; .
G1 20MVA G2 30MVA G3 40MVA
0.1pu 0.2pu 0.3pu
|A |B |C
==+==========+==========+=== 11 kV
|
C.B.
|---- F
Reactances on 100 MVA base
| Generator | Calculation | (pu) |
|---|---|---|
| G1 | 0.5 | |
| G2 | 0.6667 | |
| G3 | 0.75 |
Fault level and fault current
Feeder reactor for 40 % reduction
New fault MVA MVA.
Answer: Fault level = 483.33 MVA, fault current ≈ 25.37 kA; feeder reactor ≈ 0.167 Ω (0.1379 pu on 100 MVA) brings the level down to 290 MVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Fault level: two 50 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Feeder reactor: 40 and 30 MVA, 40% reduction · Power Plant Equipment, chapter 4 · asked 4×
- HV bus fault and limiting reactor · Power System Analysis II, chapter 3
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×