- 2080 Bhadra · 8 marks
Fault level: two 50 MVA generators, 50% reduction
Short answer
Fault level is 500 MVA. Halving it requires doubling the existing 0.1 pu reactance to 0.2 pu; thus add a feeder reactor of 0.1 pu (0.242 Ω), giving a new fault level of 250 MVA.
For the power system network given below, calculate the fault level in MVA at the outgoing feeder for a 3 phase to ground fault on the feeder. Calculate the value of reactance to be connected in the feeder in order to reduce the fault level by 50%. Ratings of the generators are: G1 = 50 MVA, 11 kV, Xg1 = 0.15 p.u.; G2 = 50 MVA, 11 kV, Xg2 = 0.3 p.u. [Figure: G1 and G2 connected to a common busbar with a single outgoing feeder]
Generators in parallel feed the fault through the bus. Fault MVA . Feeder reactance (not given) is taken as zero before adding the reactor.
Base: 50 MVA, 11 kV; . Both generators are already on 50 MVA.
G1 50MVA,0.15 G2 50MVA,0.3
| |
=====+=======+=======+==== 11 kV
| feeder (+X)
F
Fault level
Reactance for 50 % reduction
New fault MVA = 250 MVA, so
(Halving the fault level needs the total reactance to double, so the added reactance equals the existing .)
Answer: Fault level = 500 MVA; feeder reactance = 0.1 pu = 0.242 Ω (fault level becomes 250 MVA).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault level: two 25 MVA generators, 50% reduction · Power Plant Equipment, chapter 4
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Feeder reactor: 40 and 30 MVA, 50% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×