- 2080 Baisakh · 6 marks
Fault level: adding a third generator
Short answer
Fault level is 400 MVA, fault current ≈ 20.99 kA. After adding G3, equivalent reactance drops to 0.04444 pu; to restore 0.05 pu total, add a feeder reactor of 0.00556 pu (0.0336 Ω).
Following figure shows two generators operating parallel. i) If a 3-phase to ground fault occurs on the outgoing feeder, calculate the fault current and fault level on the feeder. ii) If a 3rd generator (G3: 10MVA, 11kV, X3=0.2 pu) is added at point 'C', calculate the value of reactor to be added on the outgoing feeder so that the fault level remains same as before. [Figure: G1 20 MVA, 11 kV, X1 = 0.1 pu (path-1) and G2 20 MVA, 11 kV, X2 = 0.1 pu (path-2) connected to a common busbar at points A and B; busbar extends to point C; outgoing feeder from the busbar through a C.B., fault point 'F' on the outgoing feeder]
Fault MVA . The feeder has no reactance at first (none given).
Base: 20 MVA, 11 kV; ; .
G1 20MVA G2 20MVA G3 10MVA (added)
0.1pu 0.1pu 0.2pu
|A |B |C
==+==========+==========+=== 11 kV
|
C.B.--[X]-- F
(i) Fault current and fault level (two generators)
(ii) Reactor after adding G3
G3 on 20 MVA base: .
To keep 400 MVA the total must stay at 0.05 pu:
Answer: (i) Fault level = 400 MVA, 20.99 kA. (ii) Feeder reactor ≈ 0.00556 pu = 0.0336 Ω keeps the fault level at 400 MVA after G3 is added.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Fault current: four 1600 kVA generators · Power Plant Equipment, chapter 4
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Power by two generators, 1.05∠5° and 1.05∠20° pu · Power System Analysis I, chapter 3 · asked 2×
- Power by two generators, 1.1∠15° and 1.1∠0° pu · Power System Analysis I, chapter 3 · asked 2×