L-G fault and 3-phase fault, 30 MVA generator

Short answer

For L-G fault, sequence networks in series give fault current 6.667 pu = 10.50 kA. Line-to-line voltages during fault: Vab = 5.60 kV, Vbc = 11.0 kV, Vca = 5.60 kV. Three-phase fault line current = 5 pu = 7.87 kA.

A 30 MVA, 11 kV solidly grounded generator has positive, negative and zero sequence impedance of j0.2 pu, j0.2 pu and j0.05 pu. Generator is under unloaded condition. i) Calculate fault current and line to line voltages during fault condition if L-G fault occurs at the generator terminals. ii) Find the line current for 3-phase fault.

Data: 30 MVA, 11 kV, Z1=Z2=j0.2Z_1 = Z_2 = j0.2, Z0=j0.05Z_0 = j0.05 pu, solidly grounded, unloaded, so Ea=1∠0∘E_a = 1\angle0^\circ pu.

Base current: Ibase=30×1063×11×103=1574.6I_{base} = \dfrac{30\times10^6}{\sqrt3 \times 11\times10^3} = 1574.6 A; base phase voltage =11/3=6.351= 11/\sqrt3 = 6.351 kV.

(i) L-G fault on phase a

Sequence networks in series:

Ia1=Ia2=Ia0=EaZ1+Z2+Z0=1j0.45=−j2.222 puIf=Ia=3Ia1=−j6.667 pu∣If∣=6.667×1574.6=10 497 A\begin{aligned} I_{a1} = I_{a2} = I_{a0} &= \frac{E_a}{Z_1+Z_2+Z_0} = \frac{1}{j0.45} = -j2.222\ \text{pu} \\ I_f = I_a &= 3I_{a1} = -j6.667\ \text{pu} \\ |I_f| &= 6.667 \times 1574.6 = 10\,497\ \text{A} \end{aligned}

Sequence voltages

Va1=Ea−Z1Ia1=1−(j0.2)(−j2.222)=0.5556Va2=−Z2Ia2=−0.4444Va0=−Z0Ia0=−0.1111\begin{aligned} V_{a1} &= E_a - Z_1 I_{a1} = 1 - (j0.2)(-j2.222) = 0.5556 \\ V_{a2} &= -Z_2 I_{a2} = -0.4444 \\ V_{a0} &= -Z_0 I_{a0} = -0.1111 \end{aligned}

Phase voltages (V=Va0+a2Va1+aVa2V = V_{a0} + a^2 V_{a1} + aV_{a2} for phase b, etc.)

Va=0.5556−0.4444−0.1111=0Vb=Va0+a2Va1+aVa2=0.8819∠−100.89∘ puVc=Va0+aVa1+a2Va2=0.8819∠100.89∘ pu\begin{aligned} V_a &= 0.5556 - 0.4444 - 0.1111 = 0 \\ V_b &= V_{a0} + a^2V_{a1} + aV_{a2} = 0.8819\angle{-100.89^\circ}\ \text{pu} \\ V_c &= V_{a0} + aV_{a1} + a^2V_{a2} = 0.8819\angle{100.89^\circ}\ \text{pu} \end{aligned}

Line-to-line voltages

Vab=Va−Vb=0.8819∠79.11∘ pu⇒0.8819×6.351=5.60 kVVbc=Vb−Vc=1.7321∠−90∘ pu⇒1.7321×6.351=11.0 kVVca=Vc−Va=0.8819∠100.89∘ pu⇒5.60 kV\begin{aligned} V_{ab} &= V_a - V_b = 0.8819\angle{79.11^\circ}\ \text{pu} \Rightarrow 0.8819 \times 6.351 = 5.60\ \text{kV} \\ V_{bc} &= V_b - V_c = 1.7321\angle{-90^\circ}\ \text{pu} \Rightarrow 1.7321 \times 6.351 = 11.0\ \text{kV} \\ V_{ca} &= V_c - V_a = 0.8819\angle{100.89^\circ}\ \text{pu} \Rightarrow 5.60\ \text{kV} \end{aligned}

(Line voltages are converted with the phase base 6.351 kV because the pu values are on a phase-voltage base.)

(ii) Three-phase fault

If=EaZ1=1j0.2=−j5 pu⇒5×1574.6=7873 AI_f = \frac{E_a}{Z_1} = \frac{1}{j0.2} = -j5\ \text{pu} \Rightarrow 5 \times 1574.6 = 7873\ \text{A}

Results

QuantityValue
L-G fault current6.667 pu = 10.50 kA
VabV_{ab}, VbcV_{bc}, VcaV_{ca} during L-G5.60 kV, 11.0 kV, 5.60 kV
3-phase fault line current5 pu = 7.87 kA

The L-G current is larger than the 3-phase current because Z0Z_0 (0.05) is much less than Z1Z_1.