DLG fault on 30 MVA generator

Short answer

Sequence networks parallel: I_a1=-j4.167 pu, I_a0=j3.333 pu. Line currents: Ia=0, Ib=Ic=6.614 pu=10.42 kA. Fault current If=3I_a0=10 pu=15.75 kA. Line-neutral voltages: Va=0.5 pu (3.18 kV), Vb=Vc=0.

A double line to ground fault occur at generator terminal of 30 MVA, 11 kV and having Z1 = Z2 = j0.2 pu and Z0 = j0.05 pu. Find the line currents, fault current and line to neutral voltages under fault condition.

Data: 30 MVA, 11 kV, Z1=Z2=j0.2Z_1 = Z_2 = j0.2, Z0=j0.05Z_0 = j0.05 pu, solidly grounded, unloaded (Ea=1∠0∘E_a = 1\angle0^\circ). Fault: phases b and c to ground.

Ibase=30×1063×11×103=1574.6I_{base} = \dfrac{30\times10^6}{\sqrt3\times11\times10^3} = 1574.6 A; Vbase,ph=11/3=6.351V_{base,ph} = 11/\sqrt3 = 6.351 kV.

Fault conditions

Ia=0I_a = 0, Vb=Vc=0V_b = V_c = 0, giving Va0=Va1=Va2V_{a0} = V_{a1} = V_{a2}: the three sequence networks are in parallel.

Sequence currents

Z2∥Z0=(j0.2)(j0.05)j0.25=j0.04Ia1=EaZ1+Z2∥Z0=1j0.24=−j4.1667 puIa2=−Ia1Z0Z2+Z0=j4.1667×0.2=j0.8333 puIa0=−Ia1Z2Z2+Z0=j4.1667×0.8=j3.3333 pu\begin{aligned} Z_2 \| Z_0 &= \frac{(j0.2)(j0.05)}{j0.25} = j0.04 \\ I_{a1} &= \frac{E_a}{Z_1 + Z_2\|Z_0} = \frac{1}{j0.24} = -j4.1667\ \text{pu} \\ I_{a2} &= -I_{a1}\frac{Z_0}{Z_2+Z_0} = j4.1667 \times 0.2 = j0.8333\ \text{pu} \\ I_{a0} &= -I_{a1}\frac{Z_2}{Z_2+Z_0} = j4.1667 \times 0.8 = j3.3333\ \text{pu} \end{aligned}

Line currents

Ia=Ia0+Ia1+Ia2=0Ib=Ia0+a2Ia1+aIa2=6.614∠130.89∘ pu⇒6.614×1574.6=10 415 AIc=Ia0+aIa1+a2Ia2=6.614∠49.11∘ pu⇒10 415 A\begin{aligned} I_a &= I_{a0} + I_{a1} + I_{a2} = 0 \\ I_b &= I_{a0} + a^2I_{a1} + aI_{a2} = 6.614\angle{130.89^\circ}\ \text{pu} \Rightarrow 6.614 \times 1574.6 = 10\,415\ \text{A} \\ I_c &= I_{a0} + aI_{a1} + a^2I_{a2} = 6.614\angle{49.11^\circ}\ \text{pu} \Rightarrow 10\,415\ \text{A} \end{aligned}

Fault current (to ground)

If=Ib+Ic=3Ia0=j10.0 pu⇒10×1574.6=15 746 AI_f = I_b + I_c = 3I_{a0} = j10.0\ \text{pu} \Rightarrow 10 \times 1574.6 = 15\,746\ \text{A}

Line-to-neutral voltages

Va1=Va2=Va0=Ea−Z1Ia1=1−(j0.2)(−j4.1667)=0.1667 puVa=3Va1=0.5 pu=0.5×6.351=3.175 kVVb=Vc=0\begin{aligned} V_{a1} = V_{a2} = V_{a0} &= E_a - Z_1I_{a1} = 1 - (j0.2)(-j4.1667) = 0.1667\ \text{pu} \\ V_a &= 3V_{a1} = 0.5\ \text{pu} = 0.5 \times 6.351 = 3.175\ \text{kV} \\ V_b &= V_c = 0 \end{aligned}

Results

QuantitypuActual
IaI_a00
IbI_b, IcI_c6.61410.41 kA
Fault current IfI_f10.015.75 kA
VaV_a0.53.18 kV
VbV_b, VcV_c00

✓ Answer checked by Claude Sonnet 5.5

All Power System Analysis II chapter 5 questions →