- 2074 Chaitra · 9 marks
DLG fault on 30 MVA generator
Short answer
Sequence networks parallel: I_a1=-j4.167 pu, I_a0=j3.333 pu. Line currents: Ia=0, Ib=Ic=6.614 pu=10.42 kA. Fault current If=3I_a0=10 pu=15.75 kA. Line-neutral voltages: Va=0.5 pu (3.18 kV), Vb=Vc=0.
A double line to ground fault occur at generator terminal of 30 MVA, 11 kV and having Z1 = Z2 = j0.2 pu and Z0 = j0.05 pu. Find the line currents, fault current and line to neutral voltages under fault condition.
Data: 30 MVA, 11 kV, , pu, solidly grounded, unloaded (). Fault: phases b and c to ground.
A; kV.
Fault conditions
, , giving : the three sequence networks are in parallel.
Sequence currents
Line currents
Fault current (to ground)
Line-to-neutral voltages
Results
| Quantity | pu | Actual |
|---|---|---|
| 0 | 0 | |
| , | 6.614 | 10.41 kA |
| Fault current | 10.0 | 15.75 kA |
| 0.5 | 3.18 kV | |
| , | 0 | 0 |
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-L fault currents and voltages, 30 MVA generator · Power System Analysis II, chapter 5
- Equivalent Z0, Z1, Z2 at bus 3 · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Generator and motor currents for terminal fault · Power System Analysis II, chapter 3
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- L-L fault on 40 MVA generator · Power System Analysis II, chapter 5
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×