L-L fault on 40 MVA generator

Short answer

Positive and negative sequence networks parallel, Ia1 = -Ia2 = 1/(j0.6) = -j1.667 pu. Fault current magnitude in phases b and c = sqrt(3)*|Ia1| = 2.887 pu = 6.06 kA.

A 40 MVA, 11 kV generator has Z1 = Z2 = j0.3 pu, Z0 = j0.4 pu. A line to line fault occurs on the generator terminals. Find the fault current.

Data: 40 MVA, 11 kV, Z1=Z2=j0.3Z_1 = Z_2 = j0.3 pu, Z0=j0.4Z_0 = j0.4 pu. Generator unloaded, Ea=1∠0∘E_a = 1\angle0^\circ pu. Fault between phases b and c.

Fault conditions

Ia=0, Ib=−Ic, Vb=VcI_a = 0,\ I_b = -I_c,\ V_b = V_c, which give Ia0=0I_{a0} = 0 and Ia2=−Ia1I_{a2} = -I_{a1}: the positive and negative sequence networks are connected in parallel (opposing), and Z0Z_0 does not appear.

Sequence currents

Ia1=−Ia2=EaZ1+Z2=1j0.6=−j1.667 puI_{a1} = -I_{a2} = \frac{E_a}{Z_1 + Z_2} = \frac{1}{j0.6} = -j1.667\ \text{pu}

Fault current

Ib=(a2−a)Ia1=−j3 Ia1=−j3(−j1.667)=−2.887 puIc=−Ib=2.887 pu\begin{aligned} I_b &= (a^2 - a)I_{a1} = -j\sqrt3\, I_{a1} = -j\sqrt3(-j1.667) = -2.887\ \text{pu} \\ I_c &= -I_b = 2.887\ \text{pu} \end{aligned}

Base current:

Ibase=40×1063×11×103=2099.5 AI_{base} = \frac{40\times10^6}{\sqrt3 \times 11\times10^3} = 2099.5\ \text{A} ∣If∣=2.887×2099.5=6061 A|I_f| = 2.887 \times 2099.5 = 6061\ \text{A}

Answer: L-L fault current = 2.887 pu ≈ 6.06 kA (equal and opposite in phases b and c; Ia=0I_a = 0).

For comparison, a 3-phase fault would give 1/0.3=3.3331/0.3 = 3.333 pu, so ILL=32I3ϕI_{LL} = \frac{\sqrt3}{2} I_{3\phi} when Z1=Z2Z_1 = Z_2.