- 2078 Kartik · 8 marks
L-L fault on 40 MVA generator
Short answer
Positive and negative sequence networks parallel, Ia1 = -Ia2 = 1/(j0.6) = -j1.667 pu. Fault current magnitude in phases b and c = sqrt(3)*|Ia1| = 2.887 pu = 6.06 kA.
A 40 MVA, 11 kV generator has Z1 = Z2 = j0.3 pu, Z0 = j0.4 pu. A line to line fault occurs on the generator terminals. Find the fault current.
Data: 40 MVA, 11 kV, pu, pu. Generator unloaded, pu. Fault between phases b and c.
Fault conditions
, which give and : the positive and negative sequence networks are connected in parallel (opposing), and does not appear.
Sequence currents
Fault current
Base current:
Answer: L-L fault current = 2.887 pu ≈ 6.06 kA (equal and opposite in phases b and c; ).
For comparison, a 3-phase fault would give pu, so when .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Equivalent Z0, Z1, Z2 at bus 3 · Power System Analysis II, chapter 5
- L-L fault currents and voltages, 30 MVA generator · Power System Analysis II, chapter 5
- DLG fault on 30 MVA generator · Power System Analysis II, chapter 5
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Subtransient currents for fault at motor terminals · Power System Analysis II, chapter 3
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3