- 2076 Asoj · 8 marks
Subtransient currents for fault at motor terminals
Short answer
With 30 MVA, 13.2 kV base and internal EMFs from pre-fault load, subtransient generator current is 3972 A, motor current is 7096 A, and fault current is 10906 A.
A synchronous generator and motor are rated 30 MVA, 13.2 kV and both have subtransient reactances of 20%. The line connecting them has reactance of 8% on the base of the machine ratings. The motor is drawing 20 MW at 0.8 pf leading and terminal voltage of 12.8 kV when a symmetrical three phase fault occurs at the motor terminals. Find the subtransient currents in the generator, the motor and fault by using the internal voltages of machines.
Base: 30 MVA, 13.2 kV (the machine ratings). The motor terminal voltage is the reference. Internal EMFs are found from the pre-fault load, then each machine's contribution to the fault at the motor terminals is found separately.
Per-unit data
- pu, line pu.
- pu.
- Motor load: pu at 0.8 pf leading.
Eg --j0.2--+--j0.08--+--j0.2-- Em
(gen) (Vf) motor terminals
|
F
Pre-fault current
Internal voltages
Sub-transient currents with the fault at the motor terminals
Base current: A.
| Current | pu | Amperes |
|---|---|---|
| Generator | 3.0267 | 3972 |
| Motor | 5.4080 | 7096 |
| Fault | 8.3117 | 10906 |
Check (Thevenin): pu, the same.
Answer: A, A, A.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-L fault currents and voltages, 30 MVA generator · Power System Analysis II, chapter 5
- Generator and motor currents for terminal fault · Power System Analysis II, chapter 3
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- DLG fault on 30 MVA generator · Power System Analysis II, chapter 5
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3