Subtransient currents for fault at motor terminals

Short answer

With 30 MVA, 13.2 kV base and internal EMFs from pre-fault load, subtransient generator current is 3972 A, motor current is 7096 A, and fault current is 10906 A.

A synchronous generator and motor are rated 30 MVA, 13.2 kV and both have subtransient reactances of 20%. The line connecting them has reactance of 8% on the base of the machine ratings. The motor is drawing 20 MW at 0.8 pf leading and terminal voltage of 12.8 kV when a symmetrical three phase fault occurs at the motor terminals. Find the subtransient currents in the generator, the motor and fault by using the internal voltages of machines.

Base: 30 MVA, 13.2 kV (the machine ratings). The motor terminal voltage is the reference. Internal EMFs are found from the pre-fault load, then each machine's contribution to the fault at the motor terminals is found separately.

Per-unit data

  • Xg′′=Xm′′=0.20X''_g = X''_m = 0.20 pu, line XL=0.08X_L = 0.08 pu.
  • Vf=12.813.2=0.9697∠0∘V_f = \dfrac{12.8}{13.2} = 0.9697\angle 0^\circ pu.
  • Motor load: P=20/30=0.6667P = 20/30 = 0.6667 pu at 0.8 pf leading.
 Eg --j0.2--+--j0.08--+--j0.2-- Em
          (gen)       (Vf) motor terminals
                       |
                       F

Pre-fault current

∣IL∣=0.66670.9697×0.8=0.8594 puIL=0.8594∠36.87∘=0.6875+j0.5156 pu\begin{aligned} |I_L| &= \frac{0.6667}{0.9697 \times 0.8} = 0.8594\ \text{pu} \\ I_L &= 0.8594\angle 36.87^\circ = 0.6875 + j0.5156\ \text{pu} \end{aligned}

Internal voltages

Eg′′=Vf+j(XL+Xg′′)IL=0.9697+j0.28(0.6875+j0.5156)=0.8253+j0.1925 puEm′′=Vf−jXm′′IL=0.9697−j0.2(0.6875+j0.5156)=1.0728−j0.1375 pu\begin{aligned} E''_g &= V_f + j(X_L + X''_g)I_L = 0.9697 + j0.28(0.6875 + j0.5156) = 0.8253 + j0.1925\ \text{pu} \\ E''_m &= V_f - jX''_mI_L = 0.9697 - j0.2(0.6875 + j0.5156) = 1.0728 - j0.1375\ \text{pu} \end{aligned}

Sub-transient currents with the fault at the motor terminals

Ig′′=Eg′′j(Xg′′+XL)=0.8253+j0.1925j0.28=0.6875−j2.9476 puIm′′=Em′′jXm′′=1.0728−j0.1375j0.2=−0.6875−j5.3641 puIf′′=Ig′′+Im′′=−j8.3117 pu\begin{aligned} I''_g &= \frac{E''_g}{j(X''_g + X_L)} = \frac{0.8253 + j0.1925}{j0.28} = 0.6875 - j2.9476\ \text{pu} \\ I''_m &= \frac{E''_m}{jX''_m} = \frac{1.0728 - j0.1375}{j0.2} = -0.6875 - j5.3641\ \text{pu} \\ I''_f &= I''_g + I''_m = -j8.3117\ \text{pu} \end{aligned}

Base current: Ibase=30×1063×13.2×103=1312.2I_{base} = \dfrac{30 \times 10^6}{\sqrt{3} \times 13.2 \times 10^3} = 1312.2 A.

CurrentpuAmperes
Generator Ig′′I''_g3.02673972
Motor Im′′I''_m5.40807096
Fault If′′I''_f8.311710906

Check (Thevenin): If′′=Vf(1j0.28+1j0.2)=−j8.3117I''_f = V_f\left(\frac{1}{j0.28} + \frac{1}{j0.2}\right) = -j8.3117 pu, the same.

Answer: Ig′′≈3972I''_g \approx 3972 A, Im′′≈7096I''_m \approx 7096 A, If′′≈10906I''_f \approx 10906 A.