L-L fault currents and voltages, 30 MVA generator

Short answer

Z1=Z2=j0.2 pu, I_a1=-j2.5 pu. Line currents: Ia=0, Ib=-4.33 pu, Ic=4.33 pu; fault current = 4.33 pu = 6.82 kA. Line-neutral voltages: Va=1.0 pu (6.35 kV), Vb=Vc=0.5 pu (3.18 kV).

A 30 MVA, 11 kV generator has Z1 = Z2 = j0.2 pu, Z0 = j0.05 pu. A line to line fault occurs on the generator terminals. Find the line currents, fault currents and line to neutral voltage under fault conditions.

Data: 30 MVA, 11 kV, Z1=Z2=j0.2Z_1 = Z_2 = j0.2, Z0=j0.05Z_0 = j0.05 pu. Unloaded, Ea=1∠0∘E_a = 1\angle0^\circ pu. Fault between phases b and c (no ground).

Ibase=30×1063×11×103=1574.6I_{base} = \dfrac{30\times10^6}{\sqrt3\times11\times10^3} = 1574.6 A; Vbase,ph=11/3=6.351V_{base,ph} = 11/\sqrt3 = 6.351 kV.

Fault conditions

Ia=0I_a = 0, Ib=−IcI_b = -I_c, Vb=VcV_b = V_c → Ia0=0I_{a0} = 0, Ia2=−Ia1I_{a2} = -I_{a1}, Va1=Va2V_{a1} = V_{a2}. Positive and negative networks in parallel; zero network not involved.

Sequence currents

Ia1=−Ia2=EaZ1+Z2=1j0.4=−j2.5 pu,Ia0=0I_{a1} = -I_{a2} = \frac{E_a}{Z_1+Z_2} = \frac{1}{j0.4} = -j2.5\ \text{pu}, \quad I_{a0} = 0

Line currents and fault current

Ia=0Ib=(a2−a)Ia1=(−j3)(−j2.5)=−4.330 puIc=−Ib=4.330 pu∣If∣=4.330×1574.6=6818 A\begin{aligned} I_a &= 0 \\ I_b &= (a^2 - a)I_{a1} = (-j\sqrt3)(-j2.5) = -4.330\ \text{pu} \\ I_c &= -I_b = 4.330\ \text{pu} \\ |I_f| &= 4.330 \times 1574.6 = 6818\ \text{A} \end{aligned}

Line-to-neutral voltages

Va1=Va2=Ea−Z1Ia1=1−(j0.2)(−j2.5)=0.5 pu,Va0=0Va=Va1+Va2=1.0 pu=6.351 kVVb=(a2+a)Va1=−Va1=−0.5 pu=3.175 kV (∠180∘)Vc=Vb=−0.5 pu=3.175 kV (∠180∘)\begin{aligned} V_{a1} = V_{a2} &= E_a - Z_1I_{a1} = 1 - (j0.2)(-j2.5) = 0.5\ \text{pu}, \quad V_{a0} = 0 \\ V_a &= V_{a1}+V_{a2} = 1.0\ \text{pu} = 6.351\ \text{kV} \\ V_b &= (a^2 + a)V_{a1} = -V_{a1} = -0.5\ \text{pu} = 3.175\ \text{kV}\ (\angle180^\circ) \\ V_c &= V_b = -0.5\ \text{pu} = 3.175\ \text{kV}\ (\angle180^\circ) \end{aligned}

Results

QuantitypuActual
IaI_a00
Ib=−IcI_b = -I_c (fault current)4.3306.82 kA
VaV_a1.0∠0°6.35 kV
Vb=VcV_b = V_c0.5∠180°3.18 kV

The line voltage between the faulted phases is zero, and Vab=Vac=1.5V_{ab} = V_{ac} = 1.5 pu =9.53= 9.53 kV.