L-L fault line voltages, 25 MVA alternator
Short answer
For a bolted line-to-line fault, I_a1 = -I_a2 = E_a / j(X1+X2). Using X1=0.25 pu, X2=0.35 pu, and E_a=1 pu, sequence voltages are V_a1=V_a2=0.5833 pu, V_a0=0. Phase voltages yield V_ab = 1.75 pu and V_ca = -1.75 pu. On a 13.2 kV (line) base, V_ab = 13.34∠0° kV, V_bc = 0, V_ca = 13.34∠180° kV.
A 25 MVA, 13.2 kV alternator with solidly grounded neutral had a sub-transient reactance of 0.25 pu. The negative and zero sequence reactances are 0.35 and 0.1 pu respectively. A line to line fault occurs at the terminals of an alternator. Determine the line to line voltages under fault conditions. Neglect resistance.
For a line-to-line fault at the generator terminals, and , and for a bolted fault ; the phase voltages follow from these.
Data: , , pu; pu (no-load prefault); fault between phases b and c, .
Sequence currents
Sequence voltages
Phase voltages
Line voltages
These are in per unit of the base phase voltage kV:
| Quantity | pu (phase base) | Actual |
|---|---|---|
| 1.75∠0° | 13.34∠0° kV | |
| 0 | 0 | |
| 1.75∠180° | 13.34∠180° kV |
(Fault current for reference: pu A.)
Answer: kV, , kV.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance/resistance to limit L-G current · Power System Analysis II, chapter 5
- Sequence reactances from fault currents · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance and L-G fault severity · Power System Analysis II, chapter 5 · asked 2×
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3