Neutral reactance/resistance to limit L-G current
Short answer
Rated line current = 1 pu. To limit SLG fault current from 4 pu to 1 pu, set 3/|0.75+j3Xn|=1 → Xn=0.75 pu (4.36 Ω); for resistance, 3/√((3Rn)²+0.75²)=1 → Rn=0.9682 pu (5.62 Ω).
A 30 MVA, 13.2 kV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. Determine the following: i) The value of reactance that must be placed in the generator neutral so that the fault current for a line-to-ground fault of zero fault impedance shall not exceed the rated line current. ii) The value of resistance to be placed in the neutral that will serve the same purpose.
Data: 30 MVA, 13.2 kV; , , pu. Rated line current pu. Pre-fault voltage pu.
With a neutral impedance , the zero-sequence impedance becomes :
Without : pu, i.e. four times rated current, so it must be limited to 1 pu.
(i) Neutral reactance
(ii) Neutral resistance
The resistance is in quadrature with the reactances:
Answer: (i) neutral reactance pu ; (ii) neutral resistance pu .
A larger ohmic value is needed with resistance because it adds to the network reactance in quadrature, not directly.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Equal positive and negative sequence impedances · Power System Analysis II, chapter 4
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Fault currents of isolated-neutral 380 V generator · Power System Analysis II, chapter 5
- L-L fault line voltages, 25 MVA alternator · Power System Analysis II, chapter 5 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3