- 2081 Bhadra · 6+2 marks
Equal positive and negative sequence impedances
Short answer
For a symmetrical static circuit, Z1 = Z2 = Zs − Zm because the phase impedance matrix has equal self and mutual impedances, making the positive and negative sequence terms identical. In a generator, the rotor motion causes positive sequence MMF to be stationary relative to the rotor, while negative sequence MMF rotates opposite, inducing different magnetic reactions, so impedances differ.
With proper mathematical interpretations, justify that for a symmetrical static circuit, positive and negative sequence impedances are equal. Also discuss why the sequence impedances for a generator are not equal.
A symmetrical static circuit (transmission line, transformer, static load) has equal self impedances in all phases and equal mutual impedances between all pairs of phases; for such a circuit .
Mathematical proof
Voltage drops across the three phases:
Transform with , : .
Write ( = unit matrix, = matrix of ones). Since and (column sums of are , , ):
Hence
Physically, in a static circuit the impedance does not depend on the order in which the phase currents reach their peaks (a-b-c or a-c-b); reversing the phase sequence only interchanges b and c, which gives the same circuit. So . Zero sequence currents are in phase, so the mutual effects add () and is different, usually larger.
Why generator sequence impedances are not equal
A synchronous generator is a rotating machine, so the sequence of the current changes the field it produces relative to the rotor:
- Positive sequence: the armature MMF rotates at synchronous speed in the same direction as the rotor, so it is stationary relative to the rotor. The reactance is , or depending on the time after the fault.
- Negative sequence: the MMF rotates opposite to the rotor at relative speed . It induces double-frequency currents in the field and damper windings, which oppose the flux, so the reactance is low, about .
- Zero sequence: the three in-phase currents produce almost no air-gap MMF (they cancel in space), so only leakage flux remains and is the smallest.
So for a generator (which changes with time from to ) is not equal to , and is different again and usually the smallest. Hence .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Sequence networks decoupled for static circuit · Power System Analysis II, chapter 4
- L-G fault of unloaded generator: equal currents · Power System Analysis II, chapter 5
- Sequence impedances of star load with Zn · Power System Analysis II, chapter 4 · asked 2×
- Sequence impedances and zero sequence comment · Power System Analysis II, chapter 4 · asked 2×
- Initial symmetrical current, load short circuit · Power System Analysis II, chapter 3
- Sequence networks with parallel transformer banks · Power System Analysis II, chapter 4
- De Morgan; positive NAND equals negative NOR · Digital Logic, chapter 2
- Static vs dynamic mathematical model · Simulation and Modeling, chapter 2 · asked 3×
- Static mathematical model with example · Simulation and Modeling, chapter 2
- Justify synchronous motor is not self starting · Electric Machines II, chapter 2