- 2079 Bhadra · 4 marks
Initial symmetrical current, load short circuit
Short answer
Using internal voltage from pre-fault resistive load, the initial symmetrical rms current is 5.0636 pu (73.1 kA on 500 MVA, 20 kV base).
A synchronous generator is rated 500 MVA, 20 kV, 60 Hz with having subtransient reactance (Xd'') = 0.20 per unit. It supplies a purely (resistive) load of 400 MW at 20 kV. The load is connected directly across the terminals of generator. If all the three phase of load are short circuited simultaneously, find the initial symmetrical rms current in the generator in per unit on a base of 500 MVA, 20 kV by using internal voltages of the machine.
Base: 500 MVA, 20 kV. The terminal voltage is pu.
Pre-fault load current
The load is purely resistive, so the current is in phase with :
Internal (sub-transient) voltage
Fault current
When all three load phases are shorted, the terminals are at zero voltage and the generator sees only :
In amperes: A, so kA.
Answer: initial symmetrical rms current pu (about 73.1 kA).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Subtransient currents for fault at motor terminals · Power System Analysis II, chapter 3
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance/resistance to limit L-G current · Power System Analysis II, chapter 5
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Short circuit at load B (ohmic data) · Power System Analysis II, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×