Initial symmetrical current, load short circuit

Short answer

Using internal voltage from pre-fault resistive load, the initial symmetrical rms current is 5.0636 pu (73.1 kA on 500 MVA, 20 kV base).

A synchronous generator is rated 500 MVA, 20 kV, 60 Hz with having subtransient reactance (Xd'') = 0.20 per unit. It supplies a purely (resistive) load of 400 MW at 20 kV. The load is connected directly across the terminals of generator. If all the three phase of load are short circuited simultaneously, find the initial symmetrical rms current in the generator in per unit on a base of 500 MVA, 20 kV by using internal voltages of the machine.

Base: 500 MVA, 20 kV. The terminal voltage is Vt=1∠0∘V_t = 1\angle 0^\circ pu.

Pre-fault load current

The load is purely resistive, so the current is in phase with VtV_t:

IL=PVt=400/5001=0.8∠0∘ puI_L = \frac{P}{V_t} = \frac{400/500}{1} = 0.8\angle 0^\circ\ \text{pu}

Internal (sub-transient) voltage

E′′=Vt+jXd′′IL=1+j0.2(0.8)=1+j0.16=1.0127∠9.09∘ pu\begin{aligned} E'' &= V_t + jX''_dI_L = 1 + j0.2(0.8) \\ &= 1 + j0.16 = 1.0127\angle 9.09^\circ\ \text{pu} \end{aligned}

Fault current

When all three load phases are shorted, the terminals are at zero voltage and the generator sees only Xd′′X''_d:

I′′=E′′jXd′′=1+j0.16j0.2=0.8000−j5.0000 pu∣I′′∣=0.82+52=5.0636 pu\begin{aligned} I'' &= \frac{E''}{jX''_d} = \frac{1 + j0.16}{j0.2} = 0.8000 - j5.0000\ \text{pu} \\ |I''| &= \sqrt{0.8^2 + 5^2} = 5.0636\ \text{pu} \end{aligned}

In amperes: Ibase=500×1063×20×103=14433.8I_{base} = \dfrac{500 \times 10^6}{\sqrt{3} \times 20 \times 10^3} = 14433.8 A, so ∣I′′∣=5.0636×14433.8≈73.09|I''| = 5.0636 \times 14433.8 \approx 73.09 kA.

Answer: initial symmetrical rms current =5.0636= 5.0636 pu (about 73.1 kA).