Sequence impedances and zero sequence comment
Short answer
Sequence impedances are defined as Z1, Z2, Z0 as above. For a Y load with Zn, the matrix is diagonal: Z1=Z2=Zs, Z0=Zs+3Zn. Zero-sequence impedance is larger because neutral carries 3Ia0; solid grounding gives Z0=Zs, ungrounded shows infinite Z0, blocking zero-sequence current.
Define sequence impedances. For the star connected load, verify that impedance matrix has non-zero elements on its diagonal matrix. Comment on zero sequence impedance.
Sequence impedance of an element is the impedance it offers to the flow of currents of one particular sequence: (positive), (negative) and (zero sequence), when only that sequence is present.
Star connected load
Consider a balanced star load with impedance per phase and neutral grounded through (solid grounding: ).
Circuit and phase equations
Ia --> Zs
a o-----/\/\---+
Ib --> Zs |
b o-----/\/\---+ n
Ic --> Zs |
c o-----/\/\---+
| In = Ia+Ib+Ic
Zn
|
ground
Voltage of each phase to ground = drop in + drop in :
In matrix form with
Transformation to sequence quantities
Put and :
with , .
Write , where is the unit matrix and is the matrix of all ones. Then . For : every row of is (since column sums of are ), and times that gives
Hence
The sequence impedance matrix has non-zero elements only on its diagonal:
All off-diagonal elements are zero, which means a current of one sequence produces a voltage drop of the same sequence only. So the three sequence networks are decoupled and can be solved separately, which is the main advantage of symmetrical components.
The same holds if the load also has equal mutual impedances between phases: then and , still diagonal.
Comment on zero sequence impedance
- is larger than and , because zero sequence currents of all three phases are in phase and add up to in the neutral; the drop is felt by each phase.
- Solidly grounded star (): .
- Ungrounded star (): ; zero sequence current cannot flow, and the zero sequence network is open.
- Delta connected load: no return path, so seen from the lines is infinite.
- In a fault study, the method of neutral grounding therefore mainly changes the zero sequence network and hence the single line to ground fault current; this is why resistance or reactance grounding is used to limit earth fault current.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Sequence impedance matrix of star load · Power System Analysis II, chapter 4 · asked 2×
- Sequence impedances of star load with Zn · Power System Analysis II, chapter 4 · asked 2×
- Sequence impedance of load with mutual coupling · Power System Analysis II, chapter 4
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Star three impedances four-wire system · Basic Electrical Engineering, chapter 8