Sequence impedances and zero sequence comment

Short answer

Sequence impedances are defined as Z1, Z2, Z0 as above. For a Y load with Zn, the matrix is diagonal: Z1=Z2=Zs, Z0=Zs+3Zn. Zero-sequence impedance is larger because neutral carries 3Ia0; solid grounding gives Z0=Zs, ungrounded shows infinite Z0, blocking zero-sequence current.

Define sequence impedances. For the star connected load, verify that impedance matrix has non-zero elements on its diagonal matrix. Comment on zero sequence impedance.

Sequence impedance of an element is the impedance it offers to the flow of currents of one particular sequence: Z1=Va1/Ia1Z_1 = V_{a1}/I_{a1} (positive), Z2=Va2/Ia2Z_2 = V_{a2}/I_{a2} (negative) and Z0=Va0/Ia0Z_0 = V_{a0}/I_{a0} (zero sequence), when only that sequence is present.

Star connected load

Consider a balanced star load with impedance ZsZ_s per phase and neutral grounded through ZnZ_n (solid grounding: Zn=0Z_n = 0).

Circuit and phase equations

   Ia -->  Zs
 a o-----/\/\---+
   Ib -->  Zs   |
 b o-----/\/\---+ n
   Ic -->  Zs   |
 c o-----/\/\---+
                |  In = Ia+Ib+Ic
               Zn
                |
              ground

Voltage of each phase to ground = drop in ZsZ_s + drop in ZnZ_n:

Va=ZsIa+Zn(Ia+Ib+Ic)Vb=ZsIb+Zn(Ia+Ib+Ic)Vc=ZsIc+Zn(Ia+Ib+Ic)\begin{aligned} V_a &= Z_s I_a + Z_n (I_a + I_b + I_c) \\ V_b &= Z_s I_b + Z_n (I_a + I_b + I_c) \\ V_c &= Z_s I_c + Z_n (I_a + I_b + I_c) \end{aligned}

In matrix form Vp=ZpIpV_p = Z_p I_p with

Zp=[Zs+ZnZnZnZnZs+ZnZnZnZnZs+Zn]Z_p = \begin{bmatrix} Z_s+Z_n & Z_n & Z_n \\ Z_n & Z_s+Z_n & Z_n \\ Z_n & Z_n & Z_s+Z_n \end{bmatrix}

Transformation to sequence quantities

Put Vp=AVsV_p = A V_s and Ip=AIsI_p = A I_s:

AVs=ZpAIs  ⇒  Vs=A−1ZpA Is=ZsseqIsA V_s = Z_p A I_s \;\Rightarrow\; V_s = A^{-1} Z_p A\, I_s = Z_s^{seq} I_s

with A=[1111a2a1aa2]A = \begin{bmatrix} 1&1&1\\1&a^2&a\\1&a&a^2 \end{bmatrix}, A−1=13[1111aa21a2a]A^{-1} = \frac13\begin{bmatrix} 1&1&1\\1&a&a^2\\1&a^2&a \end{bmatrix}.

Write Zp=ZsU+ZnJZ_p = Z_s U + Z_n J, where UU is the unit matrix and JJ is the matrix of all ones. Then A−1(ZsU)A=ZsUA^{-1}(Z_sU)A = Z_sU. For JJ: every row of JAJ A is [3  0  0][3\ \ 0\ \ 0] (since column sums of AA are 3,1+a2+a=0,1+a+a2=03, 1+a^2+a=0, 1+a+a^2=0), and A−1A^{-1} times that gives

A−1JA=[300000000]A^{-1} J A = \begin{bmatrix} 3&0&0\\0&0&0\\0&0&0 \end{bmatrix}

Hence

Zseq=A−1ZpA=[Zs+3Zn000Zs000Zs]Z_{seq} = A^{-1} Z_p A = \begin{bmatrix} Z_s+3Z_n & 0 & 0 \\ 0 & Z_s & 0 \\ 0 & 0 & Z_s \end{bmatrix}

The sequence impedance matrix has non-zero elements only on its diagonal:

Z0=Zs+3Zn,Z1=Zs,Z2=ZsZ_0 = Z_s + 3Z_n, \qquad Z_1 = Z_s, \qquad Z_2 = Z_s

All off-diagonal elements are zero, which means a current of one sequence produces a voltage drop of the same sequence only. So the three sequence networks are decoupled and can be solved separately, which is the main advantage of symmetrical components.

The same holds if the load also has equal mutual impedances ZmZ_m between phases: then Z1=Z2=Zs−ZmZ_1 = Z_2 = Z_s - Z_m and Z0=Zs+2Zm+3ZnZ_0 = Z_s + 2Z_m + 3Z_n, still diagonal.

Comment on zero sequence impedance

  • Z0=Zs+3ZnZ_0 = Z_s + 3Z_n is larger than Z1Z_1 and Z2Z_2, because zero sequence currents of all three phases are in phase and add up to 3Ia03I_{a0} in the neutral; the drop 3Ia0Zn3I_{a0}Z_n is felt by each phase.
  • Solidly grounded star (Zn=0Z_n = 0): Z0=ZsZ_0 = Z_s.
  • Ungrounded star (Zn=∞Z_n = \infty): Z0=∞Z_0 = \infty; zero sequence current cannot flow, and the zero sequence network is open.
  • Delta connected load: no return path, so Z0Z_0 seen from the lines is infinite.
  • In a fault study, the method of neutral grounding therefore mainly changes the zero sequence network and hence the single line to ground fault current; this is why resistance or reactance grounding is used to limit earth fault current.