L-G fault of unloaded generator: equal currents

Short answer

Boundary conditions I_b=I_c=0 and V_a=Z_f I_a give I_a0=I_a1=I_a2=I_a/3, so all three sequence networks are in series. The fault current for a bolted single line-to-ground fault is I_f = 3E_a/(Z1+Z2+Z0); with fault impedance Z_f it is I_f = 3E_a/(Z1+Z2+Z0+3Z_f).

Draw positive sequence, negative sequence and zero sequence network of synchronous generator. Show that all three sequence currents of faulty phase are equal in case of single line to ground fault of unloaded synchronous generator. Also find the expression of fault current.

For an L-G fault on phase a of an unloaded generator, Ib=Ic=0I_b = I_c = 0, which gives Ia0=Ia1=Ia2=Ia/3I_{a0} = I_{a1} = I_{a2} = I_a/3; the three sequence networks are in series and If=3Ea/(Z1+Z2+Z0)I_f = 3E_a/(Z_1+Z_2+Z_0) (bolted) or 3Ea/(Z1+Z2+Z0+3Zf)3E_a/(Z_1+Z_2+Z_0+3Z_f) with fault impedance.

Generator: star connected, balanced EMFs EaE_a, a2Eaa^2E_a, aEaaE_a; neutral grounded through ZnZ_n.

Sequence networks of an unloaded generator

The generator EMFs are balanced (positive sequence only), so with Z0=Zg0+3ZnZ_0 = Z_{g0} + 3Z_n:

Va0=−Z0Ia0,Va1=Ea−Z1Ia1,Va2=−Z2Ia2V_{a0} = -Z_0I_{a0}, \qquad V_{a1} = E_a - Z_1I_{a1}, \qquad V_{a2} = -Z_2I_{a2}
 Positive        Negative        Zero
  F1 o            F2 o            F0 o
     |Ia1 ^          |Ia2 ^          |Ia0 ^
    Z1              Z2              Z0
     |               |               |
   (Ea)              |               |
     |               |               |
  N1 o            N2 o            N0 o
  • Positive sequence: contains the EMF EaE_a and Z1Z_1 (sub-transient reactance Xd′′X_d'' for fault studies). No current flows in ZnZ_n.
  • Negative sequence: no EMF, impedance Z2Z_2, connected to the neutral directly.
  • Zero sequence: no EMF, impedance Z0=Zg0+3ZnZ_0 = Z_{g0} + 3Z_n; the current through the neutral is 3Ia03I_{a0}.

Boundary conditions (fault on phase a through ZfZ_f)

  a o----------+
  b o---  (Ib=0)
  c o---  (Ic=0)
               |  Ia = If
              Zf
               |
            ground
Ib=0,Ic=0,Va=ZfIaI_b = 0, \qquad I_c = 0, \qquad V_a = Z_fI_a

Sequence currents are equal

[Ia0Ia1Ia2]=13[1111aa21a2a][Ia00]⇒Ia0=Ia1=Ia2=Ia3\begin{bmatrix} I_{a0}\\I_{a1}\\I_{a2} \end{bmatrix} = \frac13\begin{bmatrix} 1&1&1\\1&a&a^2\\1&a^2&a \end{bmatrix}\begin{bmatrix} I_a\\0\\0 \end{bmatrix} \quad\Rightarrow\quad I_{a0} = I_{a1} = I_{a2} = \frac{I_a}{3}

So the same current flows in all three sequence networks, which means they are in series.

Voltage condition

Va=Va0+Va1+Va2=ZfIa=3ZfIa1V_a = V_{a0} + V_{a1} + V_{a2} = Z_fI_a = 3Z_fI_{a1}

Substituting the network equations:

−Z0Ia1+Ea−Z1Ia1−Z2Ia1=3ZfIa1-Z_0I_{a1} + E_a - Z_1I_{a1} - Z_2I_{a1} = 3Z_fI_{a1} Ia1=Ia2=Ia0=EaZ1+Z2+Z0+3ZfI_{a1} = I_{a2} = I_{a0} = \frac{E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

Fault current

If=Ia=3Ia1=3EaZ1+Z2+Z0+3ZfI_f = I_a = 3I_{a1} = \frac{3E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

For a bolted fault (Zf=0Z_f = 0): If=3EaZ1+Z2+Z0I_f = \dfrac{3E_a}{Z_1+Z_2+Z_0}.

Interconnection of sequence networks

   F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
   |                                                       |
   +------------------------[ 3Zf ]------------------------+
              common current  Ia1 = Ia2 = Ia0

The three networks are connected in series with 3Zf3Z_f: N1N_1 is joined to F2F_2 (the "==" links), N2N_2 is joined to F0F_0, and N0N_0 returns to F1F_1 through 3Zf3Z_f. The common current Ia1I_{a1} flows through all of them. Both conditions (Ia0=Ia1=Ia2I_{a0} = I_{a1} = I_{a2} and Va0+Va1+Va2=3ZfIa1V_{a0}+V_{a1}+V_{a2} = 3Z_fI_{a1}) are satisfied only by this series connection.

✓ Answer checked by Claude Sonnet 5.5