- 2080 Bhadra · 8 marks
L-G fault of unloaded generator: equal currents
Short answer
Boundary conditions I_b=I_c=0 and V_a=Z_f I_a give I_a0=I_a1=I_a2=I_a/3, so all three sequence networks are in series. The fault current for a bolted single line-to-ground fault is I_f = 3E_a/(Z1+Z2+Z0); with fault impedance Z_f it is I_f = 3E_a/(Z1+Z2+Z0+3Z_f).
Draw positive sequence, negative sequence and zero sequence network of synchronous generator. Show that all three sequence currents of faulty phase are equal in case of single line to ground fault of unloaded synchronous generator. Also find the expression of fault current.
For an L-G fault on phase a of an unloaded generator, , which gives ; the three sequence networks are in series and (bolted) or with fault impedance.
Generator: star connected, balanced EMFs , , ; neutral grounded through .
Sequence networks of an unloaded generator
The generator EMFs are balanced (positive sequence only), so with :
Positive Negative Zero
F1 o F2 o F0 o
|Ia1 ^ |Ia2 ^ |Ia0 ^
Z1 Z2 Z0
| | |
(Ea) | |
| | |
N1 o N2 o N0 o
- Positive sequence: contains the EMF and (sub-transient reactance for fault studies). No current flows in .
- Negative sequence: no EMF, impedance , connected to the neutral directly.
- Zero sequence: no EMF, impedance ; the current through the neutral is .
Boundary conditions (fault on phase a through )
a o----------+
b o--- (Ib=0)
c o--- (Ic=0)
| Ia = If
Zf
|
ground
Sequence currents are equal
So the same current flows in all three sequence networks, which means they are in series.
Voltage condition
Substituting the network equations:
Fault current
For a bolted fault (): .
Interconnection of sequence networks
F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
| |
+------------------------[ 3Zf ]------------------------+
common current Ia1 = Ia2 = Ia0
The three networks are connected in series with : is joined to (the "==" links), is joined to , and returns to through . The common current flows through all of them. Both conditions ( and ) are satisfied only by this series connection.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Equal positive and negative sequence impedances · Power System Analysis II, chapter 4
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Fault currents of isolated-neutral 380 V generator · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- No zero sequence in line-to-line fault · Power System Analysis II, chapter 5 · asked 2×
- L-G fault through Zf: currents and voltages · Power System Analysis II, chapter 5
- Positive/negative bias current effect and reduction · Advanced Electronics, chapter 2
- Delta load line currents and power, ABC sequence · Basic Electrical Engineering, chapter 8
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4