Fault currents of isolated-neutral 380 V generator

Short answer

With isolated neutral, the zero-sequence network is open. (i) L-G fault: 0 A, no return path. (ii) L-L-G fault reduces to an L-L fault: |Ib|=|Ic|= sqrt(3)*219.39/(2+0.5)=152.0 A, ground current zero. (iii) Three-phase fault: 219.39/2=109.7 A. L-L current exceeds three-phase because Z2 < Z1.

A 3-phase synchronous generator with isolated neutral at no-load is subjected to different types of faults at their terminal. Considering the line-to-line voltage rating of generator as 380V and positive, negative & zero sequence impedances of the generator are j2Ω, j0.5Ω & j0.25Ω respectively, determine the fault current for (i) L-G fault, (ii) L-L-G fault, and (iii) L-L-L-G fault. Comment on the results.

Data: VL=380V_L = 380 V, so phase emf at no load E=380/3=219.39E = 380/\sqrt3 = 219.39 V. Z1=j2 ΩZ_1 = j2\ \Omega, Z2=j0.5 ΩZ_2 = j0.5\ \Omega, Z0=j0.25 ΩZ_0 = j0.25\ \Omega. Neutral is isolated, so the neutral impedance Zn=∞Z_n = \infty and the zero-sequence network is open: no zero-sequence current can flow.

(i) L-G fault (phase a to ground)

If=3Ia0=3EZ1+Z2+Z0+3ZnI_f = 3I_{a0} = \frac{3E}{Z_1 + Z_2 + Z_0 + 3Z_n}

With Zn→∞Z_n \to \infty:

If=0 AI_f = 0\ \text{A}

There is no return path for the current, so no fault current flows. Only the potential of the neutral shifts: the faulted phase goes to ground potential and the healthy phase voltages to ground rise to line voltage (380 V).

(ii) L-L-G fault (phases b, c to ground)

Ia0=0I_{a0} = 0 because the zero-sequence network is open. The fault behaves like an L-L fault:

Ia1=EZ1+Z2=219.39j2.5=−j87.76 A∣Ib∣=∣Ic∣=3 ∣Ia1∣=3×219.392.5=152.0 A\begin{aligned} I_{a1} &= \frac{E}{Z_1 + Z_2} = \frac{219.39}{j2.5} = -j87.76\ \text{A} \\ |I_b| = |I_c| &= \sqrt3\,|I_{a1}| = \frac{\sqrt3 \times 219.39}{2.5} = 152.0\ \text{A} \end{aligned}

Current to ground =3Ia0=0= 3I_{a0} = 0. The line currents are 152.0 A each (flowing from b to c).

(iii) L-L-L-G fault

Balanced fault, only the positive sequence network acts:

If=E∣Z1∣=219.392=109.70 AI_f = \frac{E}{|Z_1|} = \frac{219.39}{2} = 109.70\ \text{A}

Results

FaultFault current
L-G0 A
L-L-G152.0 A (ground current 0)
L-L-L-G109.7 A

Comments

  • With an isolated neutral, faults involving ground give no zero-sequence current; an L-G fault gives no fault current and an L-L-G fault reduces to an L-L fault.
  • The L-L (and L-L-G) current, 152 A, is larger than the three-phase current, 109.7 A, because Z2Z_2 (0.5 Ω) is much smaller than Z1Z_1 (2 Ω): ILL/I3ϕ=3Z1/(Z1+Z2)=1.386I_{LL}/I_{3\phi} = \sqrt3 Z_1/(Z_1+Z_2) = 1.386.
  • If the neutral were solidly grounded, the L-G current would be 3E/(Z1+Z2+Z0)=3×219.39/2.75=239.33E/(Z_1+Z_2+Z_0) = 3\times219.39/2.75 = 239.3 A, the highest of all. Isolating the neutral therefore removes the severe earth fault current but lets healthy phases rise to line voltage, which stresses insulation.

✓ Answer checked by Claude Sonnet 5.5

All Power System Analysis II chapter 5 questions →