- 2082 Baishakh · 6+2 marks
Fault currents of isolated-neutral 380 V generator
Short answer
With isolated neutral, the zero-sequence network is open. (i) L-G fault: 0 A, no return path. (ii) L-L-G fault reduces to an L-L fault: |Ib|=|Ic|= sqrt(3)*219.39/(2+0.5)=152.0 A, ground current zero. (iii) Three-phase fault: 219.39/2=109.7 A. L-L current exceeds three-phase because Z2 < Z1.
A 3-phase synchronous generator with isolated neutral at no-load is subjected to different types of faults at their terminal. Considering the line-to-line voltage rating of generator as 380V and positive, negative & zero sequence impedances of the generator are j2Ω, j0.5Ω & j0.25Ω respectively, determine the fault current for (i) L-G fault, (ii) L-L-G fault, and (iii) L-L-L-G fault. Comment on the results.
Data: V, so phase emf at no load V. , , . Neutral is isolated, so the neutral impedance and the zero-sequence network is open: no zero-sequence current can flow.
(i) L-G fault (phase a to ground)
With :
There is no return path for the current, so no fault current flows. Only the potential of the neutral shifts: the faulted phase goes to ground potential and the healthy phase voltages to ground rise to line voltage (380 V).
(ii) L-L-G fault (phases b, c to ground)
because the zero-sequence network is open. The fault behaves like an L-L fault:
Current to ground . The line currents are 152.0 A each (flowing from b to c).
(iii) L-L-L-G fault
Balanced fault, only the positive sequence network acts:
Results
| Fault | Fault current |
|---|---|
| L-G | 0 A |
| L-L-G | 152.0 A (ground current 0) |
| L-L-L-G | 109.7 A |
Comments
- With an isolated neutral, faults involving ground give no zero-sequence current; an L-G fault gives no fault current and an L-L-G fault reduces to an L-L fault.
- The L-L (and L-L-G) current, 152 A, is larger than the three-phase current, 109.7 A, because (0.5 Ω) is much smaller than (2 Ω): .
- If the neutral were solidly grounded, the L-G current would be A, the highest of all. Isolating the neutral therefore removes the severe earth fault current but lets healthy phases rise to line voltage, which stresses insulation.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Equal positive and negative sequence impedances · Power System Analysis II, chapter 4
- No zero sequence in line-to-line fault · Power System Analysis II, chapter 5 · asked 2×
- L-G fault through Zf: currents and voltages · Power System Analysis II, chapter 5
- Line currents with isolated and grounded neutral · Power System Analysis II, chapter 4
- L-G fault of unloaded generator: equal currents · Power System Analysis II, chapter 5
- Generator and motor currents for terminal fault · Power System Analysis II, chapter 3
- Delta load line currents and power, ABC sequence · Basic Electrical Engineering, chapter 8
- Neutral current and power, 380 V unbalanced load · Basic Electrical Engineering, chapter 8
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×