Generator and motor currents for terminal fault

Short answer

Using sub-transient EMFs from pre-fault load on 100 MVA base, the generator fault current is 19.17 kA, motor fault current is 13.15 kA, and total fault current is 32.02 kA.

An 11 kV 100 MVA alternator having a sub-transient reactance of 0.25 pu is supplying a 50 MVA motor having a sub-transient reactance of 0.2 pu through a transmission line. The line reactance is 0.05 pu on a base of 100 MVA. The motor is drawing 40 MW at 0.8 p.f. leading with a terminal voltage of 10.95 kV when three phase fault occurs at the generator terminals. Calculate the total current in generator and motor under fault conditions.

Use the internal (sub-transient) EMFs of both machines found from the pre-fault load. Base: 100 MVA, 11 kV.

Per-unit values

  • Generator: Xg′′=0.25X''_g = 0.25 pu.
  • Motor: Xm′′=0.2×10050=0.4X''_m = 0.2 \times \dfrac{100}{50} = 0.4 pu.
  • Line: XL=0.05X_L = 0.05 pu.
  • Motor terminal voltage: Vm=10.9511=0.9955∠0∘V_m = \dfrac{10.95}{11} = 0.9955\angle 0^\circ pu (reference).
  • Motor input: P=40/100=0.4P = 40/100 = 0.4 pu at 0.8 pf leading.
 Eg --j0.25--(Vt)--j0.05--(Vm)--j0.4-- Em
             |
             F (fault at generator terminals)

Pre-fault current

∣I∣=PVmcos⁡ϕ=0.40.9955×0.8=0.5023 puI=0.5023∠36.87∘=0.4018+j0.3014 pu (leading)\begin{aligned} |I| &= \frac{P}{V_m\cos\phi} = \frac{0.4}{0.9955 \times 0.8} = 0.5023\ \text{pu} \\ I &= 0.5023\angle 36.87^\circ = 0.4018 + j0.3014\ \text{pu}\ \text{(leading)} \end{aligned}

Internal EMFs

Vt=Vm+jXLI=0.9955+j0.05(0.4018+j0.3014)=0.9804+j0.0201 puEg′′=Vt+jXg′′I=0.9804+j0.0201+j0.25(0.4018+j0.3014)=0.9050+j0.1205=0.9130∠7.59∘ puEm′′=Vm−jXm′′I=0.9955−j0.4(0.4018+j0.3014)=1.1160−j0.1607=1.1275∠−8.20∘ pu\begin{aligned} V_t &= V_m + jX_LI = 0.9955 + j0.05(0.4018 + j0.3014) = 0.9804 + j0.0201\ \text{pu} \\ E''_g &= V_t + jX''_gI = 0.9804 + j0.0201 + j0.25(0.4018 + j0.3014) = 0.9050 + j0.1205 = 0.9130\angle 7.59^\circ\ \text{pu} \\ E''_m &= V_m - jX''_mI = 0.9955 - j0.4(0.4018 + j0.3014) = 1.1160 - j0.1607 = 1.1275\angle -8.20^\circ\ \text{pu} \end{aligned}

Currents during the fault

With the generator terminals shorted, each machine feeds the fault through its own reactance:

Ig′′=Eg′′jXg′′=0.9050+j0.1205j0.25=0.4822−j3.6202=3.6521∠−82.41∘ puIm′′=Em′′j(Xm′′+XL)=1.1160−j0.1607j0.45=−0.3572−j2.4800=2.5056∠−98.20∘ puIf=Ig′′+Im′′=0.1250−j6.1002=6.1015∠−88.83∘ pu\begin{aligned} I''_g &= \frac{E''_g}{jX''_g} = \frac{0.9050 + j0.1205}{j0.25} = 0.4822 - j3.6202 = 3.6521\angle -82.41^\circ\ \text{pu} \\ I''_m &= \frac{E''_m}{j(X''_m + X_L)} = \frac{1.1160 - j0.1607}{j0.45} = -0.3572 - j2.4800 = 2.5056\angle -98.20^\circ\ \text{pu} \\ I_f &= I''_g + I''_m = 0.1250 - j6.1002 = 6.1015\angle -88.83^\circ\ \text{pu} \end{aligned}

Base current at 11 kV: Ibase=100×1063×11×103=5248.6I_{base} = \dfrac{100 \times 10^6}{\sqrt{3} \times 11 \times 10^3} = 5248.6 A.

CurrentpuAmperes
Generator, Ig′′I''_g3.652119169
Motor, Im′′I''_m2.505613151
Fault, IfI_f6.101532024

Check: If=Vt(1j0.25+1j0.45)=0.1250−j6.1002I_f = V_t\left(\frac{1}{j0.25} + \frac{1}{j0.45}\right) = 0.1250 - j6.1002 pu, the same.

Answer: generator current ≈19.17\approx 19.17 kA, motor current ≈13.15\approx 13.15 kA, total fault current ≈32.02\approx 32.02 kA.

✓ Answer checked by Claude Sonnet 5.5