Fault at generator terminal feeding motor
Short answer
Base 50 MVA, 11 kV. Motor-side series reactance = 0.1967 pu; in parallel with generator 0.1 pu gives Thevenin reactance 0.0663 pu. Fault current = 1/0.0663 = 15.08 pu = 39.6 kA. Fault MVA = 50/0.0663 = 754 MVA.
An alternator is connected to a synchronous motor through a transmission line and two transformers as shown in the figure below. The rated MVA, voltage rating and percentage reactance of the components are depicted in the figure. The transmission line reactance is also shown in the figure in Ω. Compute the fault current, if a 3-phase bolted fault occurs at the terminal of the generator. Consider the pre fault voltage as 1 p.u. Also determine the fault MVA at the generator terminal. [Figure: generator 50 MVA, 11 kV, 10% - T1 100 MVA, 11/132 kV, 5% - line j25 Ω - T2 50 MVA, 132/6.6 kV, 4% - motor 50 MVA, 6.6 kV, 6%]
For a bolted fault at the generator terminal, both the generator and the synchronous motor (acting as a source) feed the fault. with pu.
Per unit values
Base: 50 MVA, 11 kV at the generator, so 132 kV on the line and 6.6 kV at the motor (voltage bases follow the transformer ratios, so no voltage correction is needed). .
| Element | Calculation | X (pu) |
|---|---|---|
| Generator (50 MVA, 10%) | own base | 0.10 |
| T1 (100 MVA, 5%) | 0.025 | |
| Line (25 Ω) | 0.0717 | |
| T2 (50 MVA, 4%) | own base | 0.04 |
| Motor (50 MVA, 6%) | own base | 0.06 |
F
G o T1 Line T2 M
(~)-0.1-+-0.025--0.0717--0.04--0.06-(~)
| |
+====== reference (EMF = 1 pu) =====+
Fault current
Reactance on the motor side seen from F:
Contributions: generator pu (26.24 kA); motor side pu (13.34 kA).
Fault MVA at the generator terminal
Check: MVA.
Answer: Fault current ≈ 15.08 pu ≈ 39.6 kA; fault MVA ≈ 754 MVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Generator and motor currents for terminal fault · Power System Analysis II, chapter 3
- L-L fault line voltages, 25 MVA alternator · Power System Analysis II, chapter 5 · asked 2×
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- SLG fault at mid-line through 4.033 Ω · Power System Analysis II, chapter 5
- L-L fault through Zf with two motors · Power System Analysis II, chapter 5
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3