No zero sequence in line-to-line fault

Short answer

In a line-to-line fault, I_b = –I_c and I_a=0, so I_a0 = (I_a+I_b+I_c)/3 = 0. The zero sequence current is absent, and fault current I_f = –j√3 V_f/(Z_1+Z_2+Z_f) depends only on positive and negative sequence impedances.

From suitable diagram and mathematics show that during a line to line (double line) fault in a transmission line, zero sequence component is absent in the expression of fault current.

In a line-to-line fault there is no path to ground and the two fault currents are equal and opposite, so Ia+Ib+Ic=0I_a + I_b + I_c = 0 and the zero sequence current Ia0=0I_{a0} = 0; the fault current depends only on Z1Z_1 and Z2Z_2.

Model: at the fault point on the line, the system is replaced by its Thevenin sequence networks: prefault voltage VfV_f and impedances Z1Z_1, Z2Z_2, Z0Z_0 seen from the fault point.

Boundary conditions (fault between phases b and c through ZfZ_f)

  a o-----------  Ia = 0
  b o-----+        Ib = If -->
          Zf
  c o-----+        Ic = -Ib
Ia=0,Ib+Ic=0,Vb−Vc=ZfIbI_a = 0, \qquad I_b + I_c = 0, \qquad V_b - V_c = Z_fI_b

Sequence currents

Ia0=13(Ia+Ib+Ic)=13(0+Ib−Ib)=0Ia1=13(Ia+aIb+a2Ic)=13(a−a2)IbIa2=13(Ia+a2Ib+aIc)=13(a2−a)Ib\begin{aligned} I_{a0} &= \tfrac13(I_a + I_b + I_c) = \tfrac13(0 + I_b - I_b) = 0 \\ I_{a1} &= \tfrac13(I_a + aI_b + a^2I_c) = \tfrac13(a - a^2)I_b \\ I_{a2} &= \tfrac13(I_a + a^2I_b + aI_c) = \tfrac13(a^2 - a)I_b \end{aligned}

Hence

Ia0=0,Ia2=−Ia1I_{a0} = 0, \qquad I_{a2} = -I_{a1}

So the zero sequence current is absent: with no connection to ground, current that leaves through phase b returns through phase c, and the three line currents sum to zero.

Voltage condition

Vb−Vc=(a2−a)Va1+(a−a2)Va2=(a2−a)(Va1−Va2)ZfIb=Zf (a2Ia1+aIa2)=Zf(a2−a)Ia1\begin{aligned} V_b - V_c &= (a^2 - a)V_{a1} + (a - a^2)V_{a2} = (a^2 - a)(V_{a1} - V_{a2}) \\ Z_fI_b &= Z_f\,(a^2I_{a1} + aI_{a2}) = Z_f(a^2 - a)I_{a1} \end{aligned}

so

Va1−Va2=ZfIa1V_{a1} - V_{a2} = Z_fI_{a1}

With Va1=Vf−Z1Ia1V_{a1} = V_f - Z_1I_{a1} and Va2=−Z2Ia2=Z2Ia1V_{a2} = -Z_2I_{a2} = Z_2I_{a1}:

Ia1=−Ia2=VfZ1+Z2+ZfI_{a1} = -I_{a2} = \frac{V_f}{Z_1 + Z_2 + Z_f}

Fault current

If=Ib=Ia0+a2Ia1+aIa2=(a2−a)Ia1=−j3 Ia1=−j3 VfZ1+Z2+Zf\begin{aligned} I_f = I_b &= I_{a0} + a^2I_{a1} + aI_{a2} = (a^2 - a)I_{a1} \\ &= -j\sqrt3\,I_{a1} = \frac{-j\sqrt3\,V_f}{Z_1 + Z_2 + Z_f} \end{aligned}

Z0Z_0 does not appear in the expression, confirming that the zero sequence network plays no part.

Interconnection of sequence networks

        Ia1 -->           <-- Ia2
  +--(Ea)--Z1---o F1--Zf--o F2---Z2--+
  |                                  |
  N1 ------------------------------- N2

  Zero sequence network: not connected (Ia0 = 0)

The positive and negative sequence networks are connected in parallel (in opposition) through ZfZ_f; the zero sequence network is left open.

Consequences

  • The L-L fault current does not depend on the grounding of the neutral or on line zero sequence impedance.
  • With Z1=Z2Z_1 = Z_2 and Zf=0Z_f = 0: If=32⋅VfZ1=0.866×I3ϕI_f = \frac{\sqrt3}{2}\cdot\frac{V_f}{Z_1} = 0.866 \times I_{3\phi}, i.e. smaller than the three-phase fault current.
  • Also Va0=0V_{a0} = 0 at the fault, since the zero sequence network carries no current.