No zero sequence in line-to-line fault
Short answer
In a line-to-line fault, I_b = –I_c and I_a=0, so I_a0 = (I_a+I_b+I_c)/3 = 0. The zero sequence current is absent, and fault current I_f = –j√3 V_f/(Z_1+Z_2+Z_f) depends only on positive and negative sequence impedances.
From suitable diagram and mathematics show that during a line to line (double line) fault in a transmission line, zero sequence component is absent in the expression of fault current.
In a line-to-line fault there is no path to ground and the two fault currents are equal and opposite, so and the zero sequence current ; the fault current depends only on and .
Model: at the fault point on the line, the system is replaced by its Thevenin sequence networks: prefault voltage and impedances , , seen from the fault point.
Boundary conditions (fault between phases b and c through )
a o----------- Ia = 0
b o-----+ Ib = If -->
Zf
c o-----+ Ic = -Ib
Sequence currents
Hence
So the zero sequence current is absent: with no connection to ground, current that leaves through phase b returns through phase c, and the three line currents sum to zero.
Voltage condition
so
With and :
Fault current
does not appear in the expression, confirming that the zero sequence network plays no part.
Interconnection of sequence networks
Ia1 --> <-- Ia2
+--(Ea)--Z1---o F1--Zf--o F2---Z2--+
| |
N1 ------------------------------- N2
Zero sequence network: not connected (Ia0 = 0)
The positive and negative sequence networks are connected in parallel (in opposition) through ; the zero sequence network is left open.
Consequences
- The L-L fault current does not depend on the grounding of the neutral or on line zero sequence impedance.
- With and : , i.e. smaller than the three-phase fault current.
- Also at the fault, since the zero sequence network carries no current.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- No zero sequence current in delta lines · Power System Analysis II, chapter 4 · asked 2×
- L-L fault: I0 absent and I1 = −I2 · Power System Analysis II, chapter 5
- Line-to-line fault current calculation · Power System Analysis II, chapter 5 · asked 4×
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Fault at both ends of a 50 Ω line · Power System Analysis II, chapter 3
- Line voltage Fourier series: triplen harmonics absent · Power Electronics, chapter 5
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Double-tone AM expression, bandwidth and modulation index · Communication Systems, chapter 2