Line-to-line fault current calculation
Short answer
For a line-to-line fault, I_a0=0 and I_a2 = –I_a1, so positive and negative networks connect in parallel opposition through Z_f. I_a1 = V_f/(Z_1+Z_2+Z_f). Fault current I_f = –j√3 V_f/(Z_1+Z_2+Z_f). Sequence voltages at the fault bus are V_a1=V_f–Z_1 I_a1, V_a2=Z_2 I_a1; voltages at other buses follow from the Z-bus matrices.
Explain (derive) with necessary mathematical expressions and diagrams how fault current and bus voltages are calculated when a line-to-line fault occurs in a 3-phase power system network. Draw a diagram showing interconnection of sequence networks for this type of fault.
In a line-to-line (L-L) fault the zero sequence current is zero, , and the positive and negative sequence networks are connected in parallel (opposition) through at the fault point. Fault current is .
Model: the network is represented at the fault bus k by its Thevenin sequence equivalents: prefault voltage and impedances , , (from the sequence Z-bus matrices). For a generator terminal fault, and are the machine's own values.
Boundary conditions (fault between phases b and c through )
a o----------- Ia = 0
b o-----+ Ib = If -->
Zf
c o-----+ Ic = -Ib
Sequence currents
Hence
Voltage condition
so
With and :
Fault current
Voltages at the fault bus
For a bolted fault (), , so and .
Voltages at other buses (i) of a network
Using the sequence bus impedance matrices, with the fault at bus k:
Phase voltages follow from (with the phase shift of Δ-Y transformers applied to the positive and negative sequence values when crossing them). Line currents then follow from in each sequence network.
Interconnection of sequence networks
Ia1 --> <-- Ia2
+--(Ea)--Z1---o F1--Zf--o F2---Z2--+
| |
N1 ------------------------------- N2
Zero sequence network: not connected (Ia0 = 0)
The positive and negative sequence networks are connected in parallel (in opposition) through ; the zero sequence network is left open.
Steps in summary
- Form , at the fault point (Thevenin), and take = prefault voltage.
- , .
- .
- Find sequence voltages, then phase voltages at the fault and other buses.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- L-L fault line voltages, 25 MVA alternator · Power System Analysis II, chapter 5 · asked 2×
- LLG fault sequence currents at bus 3 · Power System Analysis II, chapter 5
- Interconnected system SLD with bus voltages · Power System Analysis I, chapter 1
- Reactance diagram of eight-bus system · Power System Analysis I, chapter 3
- External actors and library system sequence diagram · Object Oriented Analysis and Design, chapter 2
- Star load (8+j6) line, phase current · Basic Electrical Engineering, chapter 8