Line-to-line fault current calculation

Short answer

For a line-to-line fault, I_a0=0 and I_a2 = –I_a1, so positive and negative networks connect in parallel opposition through Z_f. I_a1 = V_f/(Z_1+Z_2+Z_f). Fault current I_f = –j√3 V_f/(Z_1+Z_2+Z_f). Sequence voltages at the fault bus are V_a1=V_f–Z_1 I_a1, V_a2=Z_2 I_a1; voltages at other buses follow from the Z-bus matrices.

Explain (derive) with necessary mathematical expressions and diagrams how fault current and bus voltages are calculated when a line-to-line fault occurs in a 3-phase power system network. Draw a diagram showing interconnection of sequence networks for this type of fault.

In a line-to-line (L-L) fault the zero sequence current is zero, Ia1=−Ia2I_{a1} = -I_{a2}, and the positive and negative sequence networks are connected in parallel (opposition) through ZfZ_f at the fault point. Fault current is If=−j3 Ea/(Z1+Z2+Zf)I_f = -j\sqrt3\,E_a/(Z_1+Z_2+Z_f).

Model: the network is represented at the fault bus k by its Thevenin sequence equivalents: prefault voltage Vf=Vk(0)V_f = V_k(0) and impedances Z1=Zkk(1)Z_1 = Z_{kk}^{(1)}, Z2=Zkk(2)Z_2 = Z_{kk}^{(2)}, Z0=Zkk(0)Z_0 = Z_{kk}^{(0)} (from the sequence Z-bus matrices). For a generator terminal fault, Vf=EaV_f = E_a and ZZ are the machine's own values.

Boundary conditions (fault between phases b and c through ZfZ_f)

  a o-----------  Ia = 0
  b o-----+        Ib = If -->
          Zf
  c o-----+        Ic = -Ib
Ia=0,Ib+Ic=0,Vb−Vc=ZfIbI_a = 0, \qquad I_b + I_c = 0, \qquad V_b - V_c = Z_fI_b

Sequence currents

Ia0=13(Ia+Ib+Ic)=13(0+Ib−Ib)=0Ia1=13(Ia+aIb+a2Ic)=13(a−a2)IbIa2=13(Ia+a2Ib+aIc)=13(a2−a)Ib\begin{aligned} I_{a0} &= \tfrac13(I_a + I_b + I_c) = \tfrac13(0 + I_b - I_b) = 0 \\ I_{a1} &= \tfrac13(I_a + aI_b + a^2I_c) = \tfrac13(a - a^2)I_b \\ I_{a2} &= \tfrac13(I_a + a^2I_b + aI_c) = \tfrac13(a^2 - a)I_b \end{aligned}

Hence

Ia0=0,Ia2=−Ia1I_{a0} = 0, \qquad I_{a2} = -I_{a1}

Voltage condition

Vb−Vc=(a2−a)Va1+(a−a2)Va2=(a2−a)(Va1−Va2)ZfIb=Zf (a2Ia1+aIa2)=Zf(a2−a)Ia1\begin{aligned} V_b - V_c &= (a^2 - a)V_{a1} + (a - a^2)V_{a2} = (a^2 - a)(V_{a1} - V_{a2}) \\ Z_fI_b &= Z_f\,(a^2I_{a1} + aI_{a2}) = Z_f(a^2 - a)I_{a1} \end{aligned}

so

Va1−Va2=ZfIa1V_{a1} - V_{a2} = Z_fI_{a1}

With Va1=Vf−Z1Ia1V_{a1} = V_f - Z_1I_{a1} and Va2=−Z2Ia2=Z2Ia1V_{a2} = -Z_2I_{a2} = Z_2I_{a1}:

Ia1=−Ia2=VfZ1+Z2+ZfI_{a1} = -I_{a2} = \frac{V_f}{Z_1 + Z_2 + Z_f}

Fault current

Ib=Ia0+a2Ia1+aIa2=(a2−a)Ia1=−j3 Ia1If=Ib=−Ic=−j3 VfZ1+Z2+Zf\begin{aligned} I_b &= I_{a0} + a^2I_{a1} + aI_{a2} = (a^2 - a)I_{a1} = -j\sqrt3\,I_{a1} \\ I_f &= I_b = -I_c = \frac{-j\sqrt3\,V_f}{Z_1 + Z_2 + Z_f} \end{aligned}

Voltages at the fault bus

Va1=Vf−Z1Ia1,Va2=Z2Ia1,Va0=0Va=Va1+Va2,Vb=a2Va1+aVa2,Vc=aVa1+a2Va2\begin{aligned} V_{a1} &= V_f - Z_1I_{a1}, \quad V_{a2} = Z_2I_{a1}, \quad V_{a0} = 0 \\ V_a &= V_{a1} + V_{a2}, \quad V_b = a^2V_{a1} + aV_{a2}, \quad V_c = aV_{a1} + a^2V_{a2} \end{aligned}

For a bolted fault (Zf=0Z_f = 0), Va1=Va2V_{a1} = V_{a2}, so Va=2Va1V_a = 2V_{a1} and Vb=Vc=−Va1V_b = V_c = -V_{a1}.

Voltages at other buses (i) of a network

Using the sequence bus impedance matrices, with the fault at bus k:

Vi(1)=Vi(0)−Zik(1)Ia1,Vi(2)=−Zik(2)Ia2,Vi(0)=0V_i^{(1)} = V_i(0) - Z_{ik}^{(1)}I_{a1}, \qquad V_i^{(2)} = -Z_{ik}^{(2)}I_{a2}, \qquad V_i^{(0)} = 0

Phase voltages follow from Vabc=AV012V_{abc} = AV_{012} (with the ±30∘\pm30^\circ phase shift of Δ-Y transformers applied to the positive and negative sequence values when crossing them). Line currents then follow from Iij=(Vi−Vj)/zijI_{ij} = (V_i - V_j)/z_{ij} in each sequence network.

Interconnection of sequence networks

        Ia1 -->           <-- Ia2
  +--(Ea)--Z1---o F1--Zf--o F2---Z2--+
  |                                  |
  N1 ------------------------------- N2

  Zero sequence network: not connected (Ia0 = 0)

The positive and negative sequence networks are connected in parallel (in opposition) through ZfZ_f; the zero sequence network is left open.

Steps in summary

  1. Form Z1Z_1, Z2Z_2 at the fault point (Thevenin), and take VfV_f = prefault voltage.
  2. Ia1=−Ia2=Vf/(Z1+Z2+Zf)I_{a1} = -I_{a2} = V_f/(Z_1+Z_2+Z_f), Ia0=0I_{a0} = 0.
  3. If=−j3Ia1I_f = -j\sqrt3 I_{a1}.
  4. Find sequence voltages, then phase voltages at the fault and other buses.