SLG fault: sequence networks in series

Short answer

Boundary conditions give I_a0 = I_a1 = I_a2 and V_a = 3Z_f I_a1. Substituting V_a1 = E_a – Z_1 I_a1, etc., yields I_a1 = E_a / (Z_1+Z_2+Z_0+3Z_f). The same current flows through all, so the three sequence networks connect in series. Fault current I_f = 3E_a/(Z_1+Z_2+Z_0+3Z_f).

Starting from a suitable point, show that the three sequence networks are connected in series during a single line to ground fault in a 3-phase power system (unloaded generator), and develop the mathematical expression for the fault current.

In a single line to ground (L-G) fault, the three sequence currents of the faulted phase are equal and the sequence voltages add to 3ZfIa13Z_fI_{a1}, so the positive, negative and zero sequence networks are connected in series, and If=3Ea/(Z1+Z2+Z0+3Zf)I_f = 3E_a/(Z_1+Z_2+Z_0+3Z_f).

Starting point: an unloaded star-connected generator with neutral grounded through ZnZ_n, generating balanced EMFs EaE_a, a2Eaa^2E_a, aEaaE_a; fault on phase a through fault impedance ZfZ_f.

Sequence networks of an unloaded generator

The generator EMFs are balanced (positive sequence only), so with Z0=Zg0+3ZnZ_0 = Z_{g0} + 3Z_n:

Va0=−Z0Ia0,Va1=Ea−Z1Ia1,Va2=−Z2Ia2V_{a0} = -Z_0I_{a0}, \qquad V_{a1} = E_a - Z_1I_{a1}, \qquad V_{a2} = -Z_2I_{a2}
 Positive        Negative        Zero
  F1 o            F2 o            F0 o
     |Ia1 ^          |Ia2 ^          |Ia0 ^
    Z1              Z2              Z0
     |               |               |
   (Ea)              |               |
     |               |               |
  N1 o            N2 o            N0 o

Boundary conditions (fault on phase a through ZfZ_f)

  a o----------+
  b o---  (Ib=0)
  c o---  (Ic=0)
               |  Ia = If
              Zf
               |
            ground
Ib=0,Ic=0,Va=ZfIaI_b = 0, \qquad I_c = 0, \qquad V_a = Z_fI_a

Sequence currents

[Ia0Ia1Ia2]=13[1111aa21a2a][Ia00]⇒Ia0=Ia1=Ia2=Ia3\begin{bmatrix} I_{a0}\\I_{a1}\\I_{a2} \end{bmatrix} = \frac13\begin{bmatrix} 1&1&1\\1&a&a^2\\1&a^2&a \end{bmatrix}\begin{bmatrix} I_a\\0\\0 \end{bmatrix} \quad\Rightarrow\quad I_{a0} = I_{a1} = I_{a2} = \frac{I_a}{3}

So the same current flows in all three sequence networks, which means they are in series.

Voltage condition

Va=Va0+Va1+Va2=ZfIa=3ZfIa1V_a = V_{a0} + V_{a1} + V_{a2} = Z_fI_a = 3Z_fI_{a1}

Substituting the network equations:

−Z0Ia1+Ea−Z1Ia1−Z2Ia1=3ZfIa1-Z_0I_{a1} + E_a - Z_1I_{a1} - Z_2I_{a1} = 3Z_fI_{a1} Ia1=Ia2=Ia0=EaZ1+Z2+Z0+3ZfI_{a1} = I_{a2} = I_{a0} = \frac{E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

Fault current

If=Ia=3Ia1=3EaZ1+Z2+Z0+3ZfI_f = I_a = 3I_{a1} = \frac{3E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}

For a bolted fault (Zf=0Z_f = 0): If=3EaZ1+Z2+Z0I_f = \dfrac{3E_a}{Z_1+Z_2+Z_0}.

Interconnection of sequence networks

   F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
   |                                                       |
   +------------------------[ 3Zf ]------------------------+
              common current  Ia1 = Ia2 = Ia0

The three networks are connected in series with 3Zf3Z_f: N1N_1 is joined to F2F_2 (the "==" links), N2N_2 is joined to F0F_0, and N0N_0 returns to F1F_1 through 3Zf3Z_f. The common current Ia1I_{a1} flows through all of them. Both conditions (Ia0=Ia1=Ia2I_{a0} = I_{a1} = I_{a2} and Va0+Va1+Va2=3ZfIa1V_{a0}+V_{a1}+V_{a2} = 3Z_fI_{a1}) are satisfied only by this series connection.

Remarks

  • The neutral current is In=3Ia0=IfI_n = 3I_{a0} = I_f; it flows only if the neutral is grounded. For an ungrounded neutral, Z0=∞Z_0 = \infty and If=0I_f = 0.
  • If Z0Z_0 is small (solidly grounded), the L-G fault current can exceed the three-phase fault current Ea/Z1E_a/Z_1.

✓ Answer checked by Claude Sonnet 5.5