SLG fault: sequence networks in series
Short answer
Boundary conditions give I_a0 = I_a1 = I_a2 and V_a = 3Z_f I_a1. Substituting V_a1 = E_a – Z_1 I_a1, etc., yields I_a1 = E_a / (Z_1+Z_2+Z_0+3Z_f). The same current flows through all, so the three sequence networks connect in series. Fault current I_f = 3E_a/(Z_1+Z_2+Z_0+3Z_f).
Starting from a suitable point, show that the three sequence networks are connected in series during a single line to ground fault in a 3-phase power system (unloaded generator), and develop the mathematical expression for the fault current.
In a single line to ground (L-G) fault, the three sequence currents of the faulted phase are equal and the sequence voltages add to , so the positive, negative and zero sequence networks are connected in series, and .
Starting point: an unloaded star-connected generator with neutral grounded through , generating balanced EMFs , , ; fault on phase a through fault impedance .
Sequence networks of an unloaded generator
The generator EMFs are balanced (positive sequence only), so with :
Positive Negative Zero
F1 o F2 o F0 o
|Ia1 ^ |Ia2 ^ |Ia0 ^
Z1 Z2 Z0
| | |
(Ea) | |
| | |
N1 o N2 o N0 o
Boundary conditions (fault on phase a through )
a o----------+
b o--- (Ib=0)
c o--- (Ic=0)
| Ia = If
Zf
|
ground
Sequence currents
So the same current flows in all three sequence networks, which means they are in series.
Voltage condition
Substituting the network equations:
Fault current
For a bolted fault (): .
Interconnection of sequence networks
F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
| |
+------------------------[ 3Zf ]------------------------+
common current Ia1 = Ia2 = Ia0
The three networks are connected in series with : is joined to (the "==" links), is joined to , and returns to through . The common current flows through all of them. Both conditions ( and ) are satisfied only by this series connection.
Remarks
- The neutral current is ; it flows only if the neutral is grounded. For an ungrounded neutral, and .
- If is small (solidly grounded), the L-G fault current can exceed the three-phase fault current .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-G fault of unloaded generator: equal currents · Power System Analysis II, chapter 5
- SLG fault on bus with three alternators · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Single-phase cycloconverter with mathematical expression · Power Electronics, chapter 6
- Delta connected coils line current and power · Basic Electrical Engineering, chapter 8
- Temporary overvoltage for SLG fault at line middle · High Voltage Engineering, chapter 3
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4