- 2073 Shrawan · 8 marks
Delta connected coils line current and power
Short answer
Coil impedance Z = 7 + j9.425 = 11.74∠53.4° Ω. Phase current = 400/11.74 = 34.07 A. Line current = √3 × 34.07 = 59.0 A. Total power = 3 × 34.07² × 7 = 24.4 kW.
Three similar coils each of resistance 7Ω and inductance of 0.03 H are connected in Delta to a 400 V, 3 phase, 50 Hz supply. Calculate the line current and the total power consumed.
Each coil: R = 7 Ω, L = 0.03 H, delta connected to V_L = 400 V, 50 Hz.
- X_L = 2πfL = 314.16 × 0.03 = 9.425 Ω
- Z_ph = 7 + j9.425 = 11.74∠53.4° Ω
- Power factor = R/Z = 7/11.74 = 0.596 lagging
Phase current
In delta, V_ph = V_L = 400 V.
I_ph = 400/11.74 = 34.07 A
Line current
I_L = √3 I_ph = 1.732 × 34.07 = 59.0 A
Total power
P = 3 I_ph² R = 3 × 34.07² × 7 = 24 380 W ≈ 24.4 kW
Check: √3 V_L I_L cos φ = 1.732 × 400 × 59.01 × 0.596 = 24.4 kW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Delta load phase currents, power, line currents · Basic Electrical Engineering, chapter 8
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8
- Coil on 240 V, power, current, inductance · Basic Electrical Engineering, chapter 6
- Star load (8+j6) line, phase current · Basic Electrical Engineering, chapter 8
- Delta load 20∠60° power and wattmeter readings · Basic Electrical Engineering, chapter 8
- Three coils in delta, 415 V · Basic Electrical and Electronics Engineering, chapter 1
- Three-phase full converter at 50% of maximum output · Power Electronics, chapter 3
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4