- 2067 Asoj · 8 marks
Delta load phase currents, power, line currents
Short answer
Phase currents: Iab=10 A, Ibc=20 A, Ica=10 A. Total power = sum of I²R in each branch = 3 kW. Line current magnitudes: |Ia|=18.56 A, |Ib|=12.39 A, |Ic|=29.81 A.
For the delta connected load as below, determine (i) phase currents (ii) total power consumed (iii) line currents. [Figure: delta load supplied at 100 V; one arm has 6 Ω with an inductor; another arm 6 Ω and 8 Ω; third arm 8 Ω and 4 Ω with a 3 Ω capacitor; lines a, b and c.]
From the figure: a delta load supplied from lines a, b and c at 100 V. The three arms are:
- Arm a–c: 8 Ω resistor in series with a 6 Ω inductive reactance, Z_ac = 8 + j6 = 10∠36.87° Ω
- Arm a–b: 6 Ω resistor in series with an 8 Ω inductive reactance, Z_ab = 6 + j8 = 10∠53.13° Ω
- Arm c–b: 4 Ω resistor in series with a 3 Ω capacitive reactance, Z_cb = 4 − j3 = 5∠−36.87° Ω
Assumptions: balanced 100 V line voltages with sequence a → b → c: V_ab = 100∠0°, V_bc = 100∠−120°, V_ca = 100∠120° V.
(i) Phase currents
- I_ab = 100/(6 + j8) = 10 A ∠−53.13° = 6.00 − j8.00
- I_bc = 100∠−120°/(4 − j3) = 20 A ∠−83.13° = 2.39 − j19.86
- I_ca = 100∠120°/(8 + j6) = 10 A ∠83.13° = 1.20 + j9.93
(ii) Total power
- P_ab = 10² × 6 = 600 W
- P_bc = 20² × 4 = 1600 W
- P_ca = 10² × 8 = 800 W
Total power = 3000 W = 3 kW (reactive power per arm: 800 VAR, −1200 VAR and 600 VAR, so the net is 200 VAR lagging)
(iii) Line currents
- I_a = I_ab − I_ca = 4.80 − j17.93 = 18.56 A (∠−75.0°)
- I_b = I_bc − I_ab = −3.61 − j11.86 = 12.39 A (∠−106.9°)
- I_c = I_ca − I_bc = −1.19 + j29.79 = 29.81 A (∠92.3°)
(Their sum is zero.) The line current magnitudes depend on the phase sequence assumed, whereas the phase currents and total power do not.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8
- Delta load line currents and power, ABC sequence · Basic Electrical Engineering, chapter 8
- Delta connected coils line current and power · Basic Electrical Engineering, chapter 8
- Unbalanced delta loads currents and power · Basic Electrical Engineering, chapter 8
- Delta load 20∠60° power and wattmeter readings · Basic Electrical Engineering, chapter 8
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8
- Classical: inductor current and capacitor voltage, 100 V · Electrical Circuit Theory, chapter 3
- Laplace: inductor and capacitor currents, 12 V · Electrical Circuit Theory, chapter 4 · asked 3×
- Bridge cycloconverter numerical (one-third frequency) · Power Electronics, chapter 6
- G-S one iteration with π-model lines · Power System Analysis II, chapter 2