- 2069 Chaitra · 3×2+4 marks
G-S one iteration with π-model lines
Short answer
Using nominal-π Ybus with line charging, one G-S iteration gives V2=1.0281∠−4.6106° pu and V3=1.0796∠−7.6322° pu. Slack bus complex power is S1=1.6206−j0.1054 pu.
The single line diagram of a power system network is shown in figure below. The per km line series reactance is 0.001 p.u and shunt susceptance is 0.0016 p.u. [Figure: line 1-2 is 100 km, line 1-3 is 200 km, line 2-3 is 400 km] The power and bus voltages are as follows:
| Bus No. | PLoad | QLoad | Pgen | Qgen | V |
|---|---|---|---|---|---|
| 1 | 0 | 0 | ? | ? | 1.05∠0° |
| 2 | 1.0 | 0.6 | 0 | 0 | ? |
| 3 | 0.8 | 0.3 | 0 | 0 | ? |
Using Ybus from the nominal pi-model of lines, compute the voltage at bus 2 & 3 using G-S method for one iteration and also the slack bus complex power using the computed and specified bus voltages. Start the analysis assuming unknown bus voltage magnitudes as 1 p.u. & phase angles zero degree.
Each line is modelled as a nominal-π: series reactance = 0.001 × length, total shunt susceptance = 0.0016 × length, half at each end. Bus 1 is the slack bus (); buses 2 and 3 are load buses with and pu.
Line parameters
| Line | Length (km) | (pu) | (pu) | each end (pu) |
|---|---|---|---|---|
| 1-2 | 100 | 0.1 | ||
| 1-3 | 200 | 0.2 | ||
| 2-3 | 400 | 0.4 |
Y-bus
Bus voltages after one G-S iteration
Iteration 1
Slack bus complex power
Using the specified and the computed , :
(Bus 1 has no load, so . The negative shows that the slack generator absorbs reactive power, because the long lines produce a lot of charging current at this light loading.)
Answer: pu, pu, pu.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Ybus for 3-bus lines with shunt susceptance · Power System Analysis II, chapter 1
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×
- N-R first iteration, line reactance 0.1 · Power System Analysis II, chapter 2
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×
- N-R one iteration, P2 = 0.4 pu · Power System Analysis II, chapter 2
- Node equations and Ybus, six-bus network · Power System Analysis II, chapter 1
- Reactance diagram of eight-bus system · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Insulator discs per string, 180 MW over 200 km · Transmission and Distribution System Design, chapter 3
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3