L-L fault: I0 absent and I1 = −I2

Short answer

Boundary conditions I_a = 0, I_b = -I_c give I_a0 = 0, I_a1 = (1/3)(a - a^2)I_b, I_a2 = (1/3)(a^2 - a)I_b. Hence I_a2 = -I_a1, so the positive and negative sequence currents have equal magnitude and are 180° out of phase. The zero sequence component is absent because there is no ground path.

With the help of suitable mathematical aid verify that, for a line to line fault in a synchronous generator the zero sequence component of current is absent and positive-sequence of current is equal to the negative sequence component of the current.

For a line-to-line fault (phases b and c) on a synchronous generator, the line currents sum to zero, so Ia0=0I_{a0} = 0; and transforming the boundary conditions gives Ia2=−Ia1I_{a2} = -I_{a1}, i.e. the positive and negative sequence currents are equal in magnitude (opposite in phase).

Generator and fault

An unloaded generator produces balanced EMFs; its sequence equations are

Va1=Ea−Z1Ia1,Va2=−Z2Ia2,Va0=−Z0Ia0V_{a1} = E_a - Z_1I_{a1}, \qquad V_{a2} = -Z_2I_{a2}, \qquad V_{a0} = -Z_0I_{a0}

Boundary conditions (fault between phases b and c through ZfZ_f)

  a o-----------  Ia = 0
  b o-----+        Ib = If -->
          Zf
  c o-----+        Ic = -Ib
Ia=0,Ib+Ic=0,Vb−Vc=ZfIbI_a = 0, \qquad I_b + I_c = 0, \qquad V_b - V_c = Z_fI_b

Sequence currents

Ia0=13(Ia+Ib+Ic)=13(0+Ib−Ib)=0Ia1=13(Ia+aIb+a2Ic)=13(a−a2)IbIa2=13(Ia+a2Ib+aIc)=13(a2−a)Ib\begin{aligned} I_{a0} &= \tfrac13(I_a + I_b + I_c) = \tfrac13(0 + I_b - I_b) = 0 \\ I_{a1} &= \tfrac13(I_a + aI_b + a^2I_c) = \tfrac13(a - a^2)I_b \\ I_{a2} &= \tfrac13(I_a + a^2I_b + aI_c) = \tfrac13(a^2 - a)I_b \end{aligned}

Hence

Ia0=0,Ia2=−Ia1I_{a0} = 0, \qquad I_{a2} = -I_{a1}

Since a−a2=j3a - a^2 = j\sqrt3:

Ia1=j33Ib=j3Ib,Ia2=−j3IbI_{a1} = \frac{j\sqrt3}{3}I_b = \frac{j}{\sqrt3}I_b, \qquad I_{a2} = -\frac{j}{\sqrt3}I_b

So ∣Ia1∣=∣Ia2∣=∣Ib∣/3|I_{a1}| = |I_{a2}| = |I_b|/\sqrt3: the positive and negative sequence currents have equal magnitude; they are 180° apart. The zero sequence current is absent because there is no ground connection and no neutral current flows (In=3Ia0=0I_n = 3I_{a0} = 0).

Voltage condition

Vb−Vc=(a2−a)Va1+(a−a2)Va2=(a2−a)(Va1−Va2)ZfIb=Zf (a2Ia1+aIa2)=Zf(a2−a)Ia1\begin{aligned} V_b - V_c &= (a^2 - a)V_{a1} + (a - a^2)V_{a2} = (a^2 - a)(V_{a1} - V_{a2}) \\ Z_fI_b &= Z_f\,(a^2I_{a1} + aI_{a2}) = Z_f(a^2 - a)I_{a1} \end{aligned}

so

Va1−Va2=ZfIa1V_{a1} - V_{a2} = Z_fI_{a1}

With Va1=Ea−Z1Ia1V_{a1} = E_a - Z_1I_{a1} and Va2=−Z2Ia2=Z2Ia1V_{a2} = -Z_2I_{a2} = Z_2I_{a1}:

Ia1=−Ia2=EaZ1+Z2+ZfI_{a1} = -I_{a2} = \frac{E_a}{Z_1 + Z_2 + Z_f}

Fault current

If=Ib=−Ic=(a2−a)Ia1=−j3 Ia1=−j3 EaZ1+Z2+ZfI_f = I_b = -I_c = (a^2 - a)I_{a1} = -j\sqrt3\,I_{a1} = \frac{-j\sqrt3\,E_a}{Z_1 + Z_2 + Z_f}

Interconnection of sequence networks

        Ia1 -->           <-- Ia2
  +--(Ea)--Z1---o F1--Zf--o F2---Z2--+
  |                                  |
  N1 ------------------------------- N2

  Zero sequence network: not connected (Ia0 = 0)

The positive and negative sequence networks are connected in parallel (in opposition) through ZfZ_f; the zero sequence network is left open.

Because the two networks form one series loop, the current entering the negative sequence network equals the current leaving the positive network, which is another way of seeing Ia1=−Ia2I_{a1} = -I_{a2} in magnitude.

Fault-point voltages (bolted fault)

Va1=Va2=Ea−Z1Ia1V_{a1} = V_{a2} = E_a - Z_1I_{a1}, Va0=0V_{a0} = 0, so Va=2Va1V_a = 2V_{a1} and Vb=Vc=−Va1V_b = V_c = -V_{a1}.

✓ Answer checked by Claude Sonnet 5.5