- 2069 Chaitra · 10 marks
L-L fault: I0 absent and I1 = −I2
Short answer
Boundary conditions I_a = 0, I_b = -I_c give I_a0 = 0, I_a1 = (1/3)(a - a^2)I_b, I_a2 = (1/3)(a^2 - a)I_b. Hence I_a2 = -I_a1, so the positive and negative sequence currents have equal magnitude and are 180° out of phase. The zero sequence component is absent because there is no ground path.
With the help of suitable mathematical aid verify that, for a line to line fault in a synchronous generator the zero sequence component of current is absent and positive-sequence of current is equal to the negative sequence component of the current.
For a line-to-line fault (phases b and c) on a synchronous generator, the line currents sum to zero, so ; and transforming the boundary conditions gives , i.e. the positive and negative sequence currents are equal in magnitude (opposite in phase).
Generator and fault
An unloaded generator produces balanced EMFs; its sequence equations are
Boundary conditions (fault between phases b and c through )
a o----------- Ia = 0
b o-----+ Ib = If -->
Zf
c o-----+ Ic = -Ib
Sequence currents
Hence
Since :
So : the positive and negative sequence currents have equal magnitude; they are 180° apart. The zero sequence current is absent because there is no ground connection and no neutral current flows ().
Voltage condition
so
With and :
Fault current
Interconnection of sequence networks
Ia1 --> <-- Ia2
+--(Ea)--Z1---o F1--Zf--o F2---Z2--+
| |
N1 ------------------------------- N2
Zero sequence network: not connected (Ia0 = 0)
The positive and negative sequence networks are connected in parallel (in opposition) through ; the zero sequence network is left open.
Because the two networks form one series loop, the current entering the negative sequence network equals the current leaving the positive network, which is another way of seeing in magnitude.
Fault-point voltages (bolted fault)
, , so and .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- L-L fault: I1 and I2 equal and opposite · Power System Analysis II, chapter 5
- Equal positive and negative sequence impedances · Power System Analysis II, chapter 4
- No zero sequence in line-to-line fault · Power System Analysis II, chapter 5 · asked 2×
- L-G fault of unloaded generator: equal currents · Power System Analysis II, chapter 5
- No zero sequence current in delta lines · Power System Analysis II, chapter 4 · asked 2×
- Fault currents of isolated-neutral 380 V generator · Power System Analysis II, chapter 5
- Positive/negative logic; verify 3-variable De Morgan · Digital Logic, chapter 2
- Show i1 = i2 = -V/(R1+R2+R3) at t=0+ · Electrical Circuit Theory, chapter 2
- Positive/negative bias current effect and reduction · Advanced Electronics, chapter 2
- Laplace: i1, i2 with 2 V charged capacitor · Electrical Circuit Theory, chapter 4 · asked 2×