L-L fault: I1 and I2 equal and opposite
Short answer
From I_a=0 and I_b=-I_c, sequence currents become I_a0=0, I_a1 = (j/√3)I_b, I_a2 = -(j/√3)I_b. Thus I_a2 = -I_a1: equal magnitude, 180° phase difference. The positive and negative sequence networks connect in parallel (opposition) through the fault impedance; the zero sequence network is left open.
Show that positive and negative sequence currents are equal in magnitude but out of phase by 180° in a line to line fault on a power system network. Draw a diagram showing inter-connection of sequence networks for this type of fault.
In a line-to-line fault, : the positive and negative sequence currents have equal magnitude and are 180° out of phase, while .
Boundary conditions (fault between phases b and c through )
a o----------- Ia = 0
b o-----+ Ib = If -->
Zf
c o-----+ Ic = -Ib
Sequence currents
Hence
Now and , so
Both have magnitude and differ in angle by 180°: they are equal and opposite.
Voltage condition
so
With and :
Fault current: .
Interconnection of sequence networks
Ia1 --> <-- Ia2
+--(Ea)--Z1---o F1--Zf--o F2---Z2--+
| |
N1 ------------------------------- N2
Zero sequence network: not connected (Ia0 = 0)
The positive and negative sequence networks are connected in parallel (in opposition) through ; the zero sequence network is left open.
The positive network drives out of F1 and the same current enters F2 of the negative network, so .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Equal positive and negative sequence impedances · Power System Analysis II, chapter 4
- L-G fault of unloaded generator: equal currents · Power System Analysis II, chapter 5
- L-L fault: I0 absent and I1 = −I2 · Power System Analysis II, chapter 5
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- Laplace: currents i1 and i2 with L and C branches · Electrical Circuit Theory, chapter 4
- Laplace: i1, i2 in unenergised two-mesh network · Electrical Circuit Theory, chapter 4 · asked 3×
- Delta load line currents and power, ABC sequence · Basic Electrical Engineering, chapter 8
- Show i1 = i2 = -V/(R1+R2+R3) at t=0+ · Electrical Circuit Theory, chapter 2