Short answer

On 50 MVA, 220 kV base: G1,G2 X1=X2=0.40 pu, X0=0.16 pu; neutral reactances 0.10 pu give 3Xn=0.30 pu in zero-sequence. Transformers X=0.375 pu, lines X1=X2=0.0517 pu, X0=0.0129 pu. Positive/negative network: parallel paths give 0.4008 pu between buses, machines 0.40 pu. Zero-sequence: bus tie 0.3815 pu, each machine branch 0.46 pu (0.16 + 0.30).

Draw the positive, negative and zero sequence impedance networks for the power system shown in figure below. Choose a base of 50 MVA, 220 kV in 50 Ω transmission lines and mark all reactances in pu. The ratings of the generators and transformers are: Generator 1: 25 MVA, 11 kV, X'' = 20%; Generator 2: 25 MVA, 11 kV, X'' = 20%; Three-phase transformer (each): 20 MVA, 11 Y/220 kV, x = 15%. The negative sequence reactance of each synchronous machine is equal to its subtransient reactance. The zero sequence reactance of each machine is 8%. Assume that the zero sequence reactances of lines are 25% of their positive sequence reactances. [Figure: machine 1 (star, neutral grounded through X = 5% on machine 1 rating) at bus 1; from bus 1 two parallel paths, each consisting of a Y-grounded/Y-grounded transformer, a j50 Ω line and another Y-grounded/Y-grounded transformer, to bus 2; machine 2 (star, neutral grounded through X = 5% on machine 2 rating) at bus 2]

Sequence networks are drawn by replacing each element with its positive, negative or zero sequence reactance on a common base. Only the generators have EMFs (positive network); neutral reactances appear as 3Xn3X_n in the zero sequence network only.

Base values

Sb=50S_b = 50 MVA; Vb=220V_b = 220 kV on the lines and 11 kV at the machines. Zb,line=2202/50=968 ΩZ_{b,line} = 220^2/50 = 968\ \Omega.

Per unit reactances

ElementPositiveNegativeZero
G1, G2: 0.20×50/250.20 \times 50/250.400.400.08×2=0.160.08 \times 2 = 0.16
Neutral reactance: 0.05×50/25=0.100.05 \times 50/25 = 0.10––3Xn=0.303X_n = 0.30
Each transformer: 0.15×50/200.15 \times 50/200.3750.3750.375
Each line: 50/96850/9680.05170.05170.25×0.0517=0.01290.25 \times 0.0517 = 0.0129

Each parallel path (transformer + line + transformer):

  • Positive/negative: 0.375+0.0517+0.375=0.80170.375 + 0.0517 + 0.375 = 0.8017 pu; two paths in parallel =0.4008= 0.4008 pu
  • Zero: 0.375+0.0129+0.375=0.76290.375 + 0.0129 + 0.375 = 0.7629 pu; two paths in parallel =0.3815= 0.3815 pu

All transformers are star-grounded/star-grounded, so zero sequence current passes through them (series path, as in the positive network).

Positive sequence network

  1                                     2
  o---j0.375--j0.0517--j0.375---o
  |                             |
  +---j0.375--j0.0517--j0.375---+
  |                             |
 j0.40                        j0.40
  |                             |
 (E1)                          (E2)
  |                             |
  +======= reference bus =======+

Negative sequence network

Same as positive but without EMFs: G1 and G2 are j0.40 each, connected straight to the reference; the two paths of 0.8017 pu each between buses 1 and 2.

Zero sequence network

  1                                     2
  o---j0.375--j0.0129--j0.375---o
  |                             |
  +---j0.375--j0.0129--j0.375---+
  |                             |
 j0.16                        j0.16
  |                             |
 j0.30 (3Xn)                  j0.30 (3Xn)
  |                             |
  +===== reference (ground) ====+

Each machine branch in the zero sequence network: 0.16+0.30=0.460.16 + 0.30 = 0.46 pu.

Summary: Positive: buses 1-2 joined by j0.4008j0.4008 (equivalent), machines j0.40j0.40 with EMFs. Negative: same, no EMFs. Zero: buses joined by j0.3815j0.3815 (equivalent), machines j0.46j0.46 to ground.

✓ Answer checked by Claude Sonnet 5.5