- 2079 Bhadra · 8 marks
Sequence networks with parallel transformer banks
Short answer
On 50 MVA, 220 kV base: G1,G2 X1=X2=0.40 pu, X0=0.16 pu; neutral reactances 0.10 pu give 3Xn=0.30 pu in zero-sequence. Transformers X=0.375 pu, lines X1=X2=0.0517 pu, X0=0.0129 pu. Positive/negative network: parallel paths give 0.4008 pu between buses, machines 0.40 pu. Zero-sequence: bus tie 0.3815 pu, each machine branch 0.46 pu (0.16 + 0.30).
Draw the positive, negative and zero sequence impedance networks for the power system shown in figure below. Choose a base of 50 MVA, 220 kV in 50 Ω transmission lines and mark all reactances in pu. The ratings of the generators and transformers are: Generator 1: 25 MVA, 11 kV, X'' = 20%; Generator 2: 25 MVA, 11 kV, X'' = 20%; Three-phase transformer (each): 20 MVA, 11 Y/220 kV, x = 15%. The negative sequence reactance of each synchronous machine is equal to its subtransient reactance. The zero sequence reactance of each machine is 8%. Assume that the zero sequence reactances of lines are 25% of their positive sequence reactances. [Figure: machine 1 (star, neutral grounded through X = 5% on machine 1 rating) at bus 1; from bus 1 two parallel paths, each consisting of a Y-grounded/Y-grounded transformer, a j50 Ω line and another Y-grounded/Y-grounded transformer, to bus 2; machine 2 (star, neutral grounded through X = 5% on machine 2 rating) at bus 2]
Sequence networks are drawn by replacing each element with its positive, negative or zero sequence reactance on a common base. Only the generators have EMFs (positive network); neutral reactances appear as in the zero sequence network only.
Base values
MVA; kV on the lines and 11 kV at the machines. .
Per unit reactances
| Element | Positive | Negative | Zero |
|---|---|---|---|
| G1, G2: | 0.40 | 0.40 | |
| Neutral reactance: | – | – | |
| Each transformer: | 0.375 | 0.375 | 0.375 |
| Each line: | 0.0517 | 0.0517 |
Each parallel path (transformer + line + transformer):
- Positive/negative: pu; two paths in parallel pu
- Zero: pu; two paths in parallel pu
All transformers are star-grounded/star-grounded, so zero sequence current passes through them (series path, as in the positive network).
Positive sequence network
1 2
o---j0.375--j0.0517--j0.375---o
| |
+---j0.375--j0.0517--j0.375---+
| |
j0.40 j0.40
| |
(E1) (E2)
| |
+======= reference bus =======+
Negative sequence network
Same as positive but without EMFs: G1 and G2 are j0.40 each, connected straight to the reference; the two paths of 0.8017 pu each between buses 1 and 2.
Zero sequence network
1 2
o---j0.375--j0.0129--j0.375---o
| |
+---j0.375--j0.0129--j0.375---+
| |
j0.16 j0.16
| |
j0.30 (3Xn) j0.30 (3Xn)
| |
+===== reference (ground) ====+
Each machine branch in the zero sequence network: pu.
Summary: Positive: buses 1-2 joined by (equivalent), machines with EMFs. Negative: same, no EMFs. Zero: buses joined by (equivalent), machines to ground.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Zero sequence Thevenin impedance at bus 2 · Power System Analysis II, chapter 4
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Equal positive and negative sequence impedances · Power System Analysis II, chapter 4
- L-G fault at bus 3, parallel lines · Power System Analysis II, chapter 5
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3